SA-01WL
Installation Instructions
Digital Wired Passive Infrared
Motion Detector
1 0706-0960160+00
1. Introduction
The SA-01WL Digital Wired Passive Infrared (PIR) motion
detector is a high-performance intrusion sensor with
advanced design ideal for residential and commercial
applications.
The PIR senses slight motion within a coverage pattern by
detecting infrared energy with a Pyro sensor. Serving as an
anti-intrusion sensor, the PIR can monitor open space within
line of sight.
The SA-01WL uses fuzzy logic to improve
detections and reduce false alarms. It
also provides digital temperature
compensation and self-test capability.
The SA-01WL is supplied with a cover
tamper to detect tampering with the
sensor by opening the case.
2. Technical Specifications
2.1 Optical Characteristics
Lens Type: High density Polytilan type
Optical Filter: White light protection
Maximum Coverage: 14 × 14 m (45.9 × 45.9 ft)
Vertical Adjustment: By slot (+/- 2°)
2.2 Electrical Characteristics
Input Power: Nominal +12 V DC 10mA (+9 to +16 V).
Detector Type: Dual PYRO IR element (IR filter 5um÷14um)
Alarm Signaling: Red LED 2 seconds on (EN/DIS jumper)
Alarm Output: Solid states relay (SSR) N.C (35V/100ma max)
Sensitivity: 3 levels fuzzy logic (jumper setting)
Speed Detect: 0.2M/s ÷ 5M/s ∆t= 1.1°C
(0.66 ft/s ÷ 16.4 ft /s ∆t= 2° F)
Temperature Compensation: Digital dual slope (+/- 1°C)
Tamper Switches: Cover tamper
Supervisory Signals: Electronic malfunction, temperature out
of range (by flashing LED)
2.3 Environmental Characteristics
Operating Environment: Indoor use
Operating Temperature: -10 to 60°C (14 to 140°F)
Operating Humidity: 0 to 95% (non-condensing)
RFI Protection: >20 V/m up to 1000 MHz
2.4 Physical Characteristics
Dimensions: 90mm x 65mm x 52mm
(3.5 in. x 2.5 in. x 2.2 in.)
Weight: 84.2 grams (2.97 oz)
Note: The SA-01WL is an indoor use PIR, and should not
be used in outdoor applications.
Figure 1: Lens Top View
Figure 2: Lens Side View
3. SA-01WL Features
These are the main features of the SA-01WL:
•Advanced micro-controller electronics: 10-bit A-to-D
and advanced algorithms for superior movement speed
spectrum analysis
•Shielded dual-element Pyro: Inside a dust-proof
chamber designed to reduce thermal changes and
insect protection
•Three levels of sensitivity: High, medium or low; by
jumper selection
•Input/output Line protection: For added resistance to
transient shock, ESD, and RFI interference
•Adjustable height calibration of PCB: The detector may
be adjusted and placed at any height from 1.8 meters
to 2.3 meters
•Cover tamper switch: Protection against opening the
cover for higher security
•Walk test mode: Detection is indicated by a red LED
(enabled or disabled) with an internal jumper for
additional security
•Energy detection system: By using fuzzy logic algorithms,
detection is improved and false alarms are reduced
•Environment temperature compensation: Maintains
constant detection capability
•Adaptive filter:Compensates for changes in a detected
object’s speed
•Continuous monitoring: Sends visual alerts in case of
malfunction (digital and analog) and temperature alerts
if the environment temperature is out of range
•Solid state relay: Provides a nearly unlimited lifespan,
EMC resistance and silent operation
•Digital Electrical and Magnetic Protection: Distinguishes
between electrical interference and real temperature
changes
4. Installation
4.1 False Alarm Reduction Effort
To reduce false alarms caused by detector installation.
•AVOID: Placing the PIR facing windows, or in direct
sunlight as this heat energy can cause false alarms.
•AVOID: Wiring of the SA-01WL in such a way that it is
parallel to and sitting close to 110V AC or 220V AC
transmission equipment or mains power line.
•AVOID: Placing near or over heat and air ducts, ovens,
heat sources, radiators, and air conditioners as this may
cause a false detection.
•AVOID: Placing near PL lamps, electrical ballasts, above
cookers, and ovens, and above steam sources.
•NEVER: Touch the Pyro-electric sensor on the PCBA as
this causes permanent damage and loss of sensitivity.
Important Note: PIR works according to field of view and
cannot detect through walls. Avoid placing near
obstructions such as large plants, curtains, behind open
doors, and continuously moving objects.
4.2 Selecting the Physical Location
You need to select the best physical location to install the
PIR.
To select a physical location:
1) Select a corner or a flat wall within a room or hallway
that best matches the criteria in False Alarm Reduction
Effort.
2) Make sure that the PIR is mounted on a non-moving,
non-vibrating surface, or corner of the room.
3) Mount the PIR in the location.
4) After the installation, perform a walk test from the
mounting location to ensure that the sensor pattern can
detect within the coverage area (see the section,
Testing the Detector).
4.3 Wiring Information
The SA-01WL is wired using a terminal block with binding posts
that are opened using a thin Philips head screwdriver or a
flat head screwdriver and located on the front of the PCB.
Figure 3: Terminal Blocks
The terminal block consists of two parts, on the right two
normally closed alarm relay binding posts followed by two
tamper binding posts and on the left a + and – 12VDC
binding post.
To wire the SA-01WL:
1) Connect all the signaling cables.
2) Wire the power.
Note: When laying wires to the control panel ensure
that they are not in parallel with high voltage mains or
other radiation emitting equipment as this may cause
false alarms.
4.4 Mounting the PIR
The SA-01WL PIR is designed to be mounted onto a flat wall
surface or to a corner.
Flat Surface Mounting
To mount the PIR to a flat surface (Figure 4):
1) Remove the PCB from the back case.
2) Remove the knockouts from the back case, labeled “B”
by using a sharp tool or using a nail.
3) Affix the four screws onto the wall.
4) Replace the PCB and tighten the PCB locking screw.
5) Replace the top cover of the PIR.
INSIDE THE BACK CASE
A:
KNOCKOUT HOLE
FOR CORNER
MOUNTING
A
AA
A
BB
BB
B:
KNOCKOUT HOLE
FLAT SURFACE
MOUNTING
PHILIPS HEAD
SCREW FOR
LOCKING PCB
ANTIDUST
ADHESIVE
Figure 4: Inside the Plastic Case – Back
Alarm
N
.C
RLY
Tamper
12VDC
+
-
5. Jumpers Setting
5.1 Setting the Sensitivity
SA-01WL has two jumpers JP1, and JP2 to set the operation
method of the PIR. Insert a jumper to activate the desired
setting.
3
2
1
JP1
Figure 5: JP1 Jumper
To prevent false alarms in harsh environments, three sensitivity
modes were designated:
•Low – for harsh environments
•Medium – for normal usage
•High – for high sensitivity when there is little chance of
false alarms
To set the jumpers (Figure 5):
•Low – jumper on pins 1 and 2
•Medium – jumper off
•High – jumper on pins 2 and 3
To panel
From panel
2 0706-0960160+00
5.2 Setting LED Enable/Disable
You can disable the LED activity during Alarms by using the
JP2 jumper.
When the jumper is on, the LED is enabled.
When the jumper is off, the LED is disabled.
LED disabled – no jumper
LED enabled – with jumper
For security reasons, after a successful walk test, the jumper
should be taken out.
In both cases the LED will remain active for all trouble
annunciations
Figure 6: Front of PCB
5.3 Vertical Calibration
If the SA-01WL PIR has to be mounted at a height above 2.1
meters or below 1.8 meters, calibrate the PCB by fixing the
PCB as follows:
If mounting the PIR above 2.1 meters, move the PCB (+) up
so the detection area is focused closer to the unit.
If mounting the PIR below 1.8 meters, move the PCB down (-)
to increase the distance at which the unit works most
effectively.
The PCB mounting height
calibration scale is on the
right hand side of the top of
the PCB. Set the height using
the line on the side of the
housing.
0
-2
-4
2
4
(m)
6. Signaling
The LED on the front of the SA-01WL is used to send several signals to the user. The following table describes the signals for different
activities:
Activity LED Signal
Warm-Up The LED flashes on for 2 seconds and off for 2 seconds for a period of 1 minute. If the
warm-up is successful, the LED stops flashing and the system is ready for detection.
Detect Condition The LED flashes on for 2 seconds and then turns off.
PIR Problem The LED flashes on for 1 second and then off for 1 second. A PIR check is conducted once
every hour.
Temperature Problem The LED flashes on for 0.5 seconds and then off for 0.5 seconds.
7. Testing the Detector
The SA-01WL PIR has a built-in walk test function where the LED
of the PIR is enabled. This test is used to check the detection of
the PIR and the coverage pattern and to adjust the height
calibration accordingly.
To perform a walk test:
1) Ensure all of the settings in the PIR are adjusted as
necessary for the location according to the installation
instructions above, and that the PIR case is closed and the
locking screw is firm.
2) Ensure the LED jumper is installed and then close the cover
of the PIR.
3) Apply power to the unit. The LED flashes on for 2 seconds
and off for 2 seconds for a period of 1 minute. During this
time, all PIR paths are being self tested, after the test is
successful, the LED switches off. At this point a walk test
can be performed. For first time power up please allow
the system to stabilize for approximately 5 minutes before
conducting the walk test.
4) With the LED enabled, the LED flashes every time the
detector detects motion. There is a two second wait
period before the next detection.
5) It is recommended that the installer test the detection by
going over the protected area and seeing that the
detection pattern is good.
6) Take out the LED jumper after a successful walk test.
3 0706-0960110+00
8. Limited Warranty
ROSSLARE ENTERPRISES LIMITED S (Rosslare) ONE YEAR LIMITED
WARRANTY is applicable worldwide. This warranty supersedes any other
warranty. Rosslare's ONE YEAR LIMITED WARRANTY is subject to the
following conditions:
Warranty
Warranty of Rosslare's products extends to the original purchaser (Customer)
of the Rosslare product and is not transferable.
Products Covered By This Warranty and Duration
ROSSLARE ENTERPRISES LTD. AND / ORSUBSIDIARIES (ROSSLARE)
warrants that the SA-01WL Digital Wired Passive Infrared Motion Detector, to
be free from defects in materials and assembly in the course of normal use
and service. The warranty period commences with the date of shipment to the
original purchaser and extends for a period of 1 year (12 Months).
Warranty Remedy Coverage
In the event of a breach of warranty, ROSSLARE will credit Customer with the
price of the Product paid by Customer, provided that the warranty claim is
delivered to ROSSLARE by the Customer during the warranty period in
accordance with the terms of this warranty. Unless otherwise requested by
ROSSLARE ENTERPRISES LTD. AND / OR SUBSIDIARIES representative,
return of the failed product(s) is not immediately required.
If ROSSLARE has not contacted the Customer within a sixty (60) day holding
period following the delivery of the warranty claim, Customer will not be
required to return the failed product(s). All returned Product(s), as may be
requested at ROSSLARE ENTERPRISES LTD. AND /OR SUBSIDIARY’S sole
discretion, shall become the property of ROSSLARE ENTERPRISES LTD.
AND /OR SUBSIDIARIES.
To exercise the warranty, the user must contact Rosslare Enterprises Ltd. to
obtain an RMA number after which, the product must be returned to the
Manufacturer freight prepaid and insured
In the event ROSSLARE chooses to perform a product evaluation within the
sixty (60) day holding period and no defect is found, a minimum US$ 50.00 or
equivalent charge will be applied to each Product for labor required in the
evaluation.
Rosslare will repair or replace, at its discretion, any product that under normal
conditions of use and service proves to be defective in material or
workmanship. No charge will be applied for labor or parts with respect to
defects covered by this warranty, provided that the work is done by Rosslare
or a Rosslare authorized service center.
Exclusions and Limitations
ROSSLARE shall not be responsible or liable for any damage or loss resulting
from the operation or performance of any Product or any systems in which a
Product is incorporated. This warranty shall not extend to any ancillary
equipment not furnished by ROSSLARE, which is attached to or used in
conjunction with a Product, nor to any Product that is used with any ancillary
equipment, which is not furnished by ROSSLARE.
This warranty does not cover expenses incurred in the transportation, freight
cost to the repair center, removal or reinstallation of the product, whether or
not proven defective.
Specifically excluded from this warranty are any failures resulting from
Customer's improper testing, operation, installation, or damage resulting from
use of the Product in other than its normal and customary manner, or any
maintenance, modification, alteration, or adjustment or any type of abuse,
neglect, accident, misuse, improper operation, normal wear, defects or
damage due to lightning or other electrical discharge. This warranty does not
cover repair or replacement where normal use has exhausted the life of a part
or instrument, or any modification or abuse of, or tampering with, the Product if
Product disassembled or repaired in such a manner as to adversely affect
performance or prevent adequate inspection and testing to verify any warranty
claim.
ROSSLARE does not warrant the installation, maintenance, or service of the
Product. Service life of the product is dependent upon the care it receives and
the conditions under which it has to operate.
In no event shall Rosslare be liable for incidental or consequential damages.
Limited Warranty Terms
THIS WARRANTY SETS FORTH THE FULL EXTENT OF ROSSLARE
ENTERPRISES LTD.AND IT’S SUBSIDIARY'S WARRANTY
THE TERMS OF THIS WARRANTY MAY NOT BE VARIED BY ANY PERSON,
WHETHER OR NOT PURPORTING TO REPRESENT OR ACT ON BEHALF OF
ROSSLARE.
THIS LIMITED WARRANTY IS PROVIDED IN LIEU OF ALL OTHER
WARRANTIES.ALL OTHER WARRANTIES EXPRESSED OR IMPLIED,
INCLUDING WITHOUT LIMITATION,IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE,ARE
SPECIFICALLY EXCLUDED.
IN NO EVENT SHALL ROSSLARE BE LIABLE FOR DAMAGES IN EXCESS OF
THE PURCHASE PRICE OF THE PRODUCT,OR FOR ANY OTHER INCIDENTAL,
CONSEQUENTIAL OR SPECIAL DAMAGES,INCLUDING BUT NOT LIMITED TO
LOSS OF USE,LOSS OF TIME,COMMERCIAL LOSS,INCONVENIENCE,AND
LOSS OF PROFITS,ARISING OUT OF THE INSTALLATION,USE,OR INABILITY
TO USE SUCH PRODUCT,TO THE FULLEST EXTENT THAT ANY SUCH LOSS
OR DAMAGE MAY BE DISCLAIMED BY LAW.
THIS WARRANTY SHALL BECOME NULL AND VOID IN THE EVENT OF A
VIOLATION OF THE PROVISIONS OF THIS LIMITED WARRANTY.
9. Contact information
Asia Pacific, Middle East, Africa
Headquarters:
905-912 Wing Fat Industrial Bldg, 12 Wang Tai Road, Kowloon Bay HK
Tel:+852 2795-5630 Fax: +852 2795-1508
E-mail: [email protected]
United States and Canada
1600 Hart Court, Suite 103 Southlake, TX, USA 76092
Toll Free:+1-866-632-1101 Local:+1-817-305-0006 Fax: +1-817-305-0069
E-mail: [email protected]
Europe
Global Technical Support & Training Center:
HaMelecha 22 Rosh HaAyin, Israel 48091
Tel: +972 3 938-6838 Fax: +972 3 938-6830
E-mail: [email protected]
South America
Pringles 868, 1640 Martinez Buenos Aires Argentina
Tel: +54 11 4798-0095 Fax: +54 11 4798-2228
E-mail: [email protected]
Web Site: www.rosslaresecurity.com
4 0706-0960160+00

Other Rosslare Security Sensor manuals

Rosslare PYR-3011 User manual

Rosslare

Rosslare PYR-3011 User manual

Rosslare PYR-3011 User manual

Rosslare

Rosslare PYR-3011 User manual

Rosslare SA-01PW User manual

Rosslare

Rosslare SA-01PW User manual

Rosslare PYR-3011 H/G User manual

Rosslare

Rosslare PYR-3011 H/G User manual

Rosslare PYR-2021 User manual

Rosslare

Rosslare PYR-2021 User manual

Rosslare SA-01P User manual

Rosslare

Rosslare SA-01P User manual

Rosslare SA-17 User manual

Rosslare

Rosslare SA-17 User manual

Rosslare AS-36 User manual

Rosslare

Rosslare AS-36 User manual

Rosslare SA-01P User manual

Rosslare

Rosslare SA-01P User manual

Rosslare LK-M03 User manual

Rosslare

Rosslare LK-M03 User manual

Rosslare SA-20 User manual

Rosslare

Rosslare SA-20 User manual

Popular Security Sensor manuals by other brands

Franke FAID0003 Installation and operating instructions

Franke

Franke FAID0003 Installation and operating instructions

Spectrex SharpEye 40/40 Series quick start guide

Spectrex

Spectrex SharpEye 40/40 Series quick start guide

Wenglor SS2-00VA000R2 quick start

Wenglor

Wenglor SS2-00VA000R2 quick start

Satel AOCD-250 manual

Satel

Satel AOCD-250 manual

Arcane SEL MAX Operation manual

Arcane

Arcane SEL MAX Operation manual

Velocity VDOT-WGES24 Series manual

Velocity

Velocity VDOT-WGES24 Series manual

Weco 03.G5.PWS.KAP.110 user manual

Weco

Weco 03.G5.PWS.KAP.110 user manual

TQC LD8100 user guide

TQC

TQC LD8100 user guide

Level Sense Pro user manual

Level Sense

Level Sense Pro user manual

tau 300SA1 installation guide

tau

tau 300SA1 installation guide

Kidde DC-9103E-KID quick start guide

Kidde

Kidde DC-9103E-KID quick start guide

Lika SMA1 Series user manual

Lika

Lika SMA1 Series user manual

Thermo Scientific Corona Veo operating manual

Thermo Scientific

Thermo Scientific Corona Veo operating manual

Zennio EyeZen RF ZPDEZRF868 user manual

Zennio

Zennio EyeZen RF ZPDEZRF868 user manual

Honeywell PANORAMA Series instructions

Honeywell

Honeywell PANORAMA Series instructions

Inficon D-TEK Stratus 724-202-G1 operating manual

Inficon

Inficon D-TEK Stratus 724-202-G1 operating manual

STEINEL IR Quattro SLIM Series manual

STEINEL

STEINEL IR Quattro SLIM Series manual

Broadcast B044 Handbook

Broadcast

Broadcast B044 Handbook

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.