Air Conditioner Service Manual
11
5.1.7 Sleeping mode
While AC works in sleeping mode, the light of POWER SUPPLY and SLEEP always ON, and the temperature display
will be OFF after 15s.
In this mode, the AC unit works according to the SLEEP CURVE as designed.
Sleeping mode the unit can work 10 hours continuously, after that it will quit from this mode and work as previous
presetting.
5.1.8 Emergency switch
When the EMERGENCY switch is pressed one time, COOLING mode is selected and if it pressed again within 3s,
HEATING mode selected, while press once again, the unit will be switched off.
When the remote controller out of function, batteries lost power, for example, the EMERGENCY button in the
front of indoor unit can be used for function test.
NOTE: Do not press the EMERGEMCY switch during normal operation.
5.1.9 Auto-restart function
While air conditioner is operating in one mode, all of its operation data, such as working mode, preset temperature
etc. would be memorized into IC by main PCB. If power supply cut off due to reasons and recover again, the AUTO-
RESTART function will set
synchronously and the air conditioner would work at the same mode as before.
Note: The function setting:
Within 3 min while power on unit, set the unit on cooling mode, set temperature 30℃, and mid fan speed, press the
ECO or SLEEP button 10 times within 8s, the AUTO-RESTART will be activated.
5.1.10 Protection
5.1.10.1 Overload protection
1. Overload protection for Cooling or Dry mode
1). if:
a. OPT≥62℃, unit stops working for overload protection.
b. OPT<55℃, after compressor stopped for 3 min, can the unit be started to operate.
2). When OPT≥55℃, the compressor will be frequency limited/reduced for over load protection.
3). If unit have 6 times of over load stop-working protection continuously, this protection can’t be recovered unless
press ON/OFF button, and unit will show failure code.
In the process of operation, once the compressor runs continuously more than 6 min, the counter of over load stop-
working protection will be reset to zero and start a new counting process.
The failure and times for protection will eliminate immediately once the unit to be switched off, on fan mode or
changed to be heating mode from others.
Note: If the defective failure can’t be recovered, the failure can’t eliminate even if operation mode changed.
2. Overload protection for Heating mode
1). If:
a. IPT≥62℃, unit stops working for overload protection.
b. IPT<55℃, after compressor stopped for 3 min, can the unit be started to operate.
2). When IPT≥55℃, the compressor will be frequency limited/reduced for over load protection.
3). If unit have 6 times of over load stop-working protection continuously, this protection can’t be recovered unless
press ON/OFF button, and unit will show failure code.
In the process of operation, once the compressor runs continuously more than 6 min, the counter of over load stop-
working protection will be reset to zero and start a new counting process.
The failure and times for protection will eliminate immediately once the unit to be switched off, on fan mode or
changed to be heating mode from others.
Note: If the defective failure can’t be recovered, the failure can’t eliminate even if operation mode changed.
5.1.10.2 The compressor discharge temperature protection
1. If ODT≥115℃, unit stops working for over temperature protection;
While ODT<100℃, & after compressor stopped for 3 min, the unit can be started to operate.
2. If ODT≥100℃, the compressor will be frequency limited/reduced for over temperature protection.
3. If unit have 6 times of discharge over temperature stop working protection continuously, this protection can’t
be recovered unless press ON/OFF button, and unit will show failure code.
In the process of operation, once the compressor runs continuously more than 6 min, the counter of discharge over
temperature stop working protection will be reset to zero and start a new counting process.