Master Station Safe Use, Installation and Maintenance Manual
3. Rotork Master Station Technical Datasheet
Rotork Master Station Features
Power supply,
AC frequency
and current
consumption
AC
100 – 240 V~ (±10%), 50 / 60 Hz (P4740)
Power consumption: Max. 50 VA (single Master Station) Max. 100 VA (hot standby and dual Master Stations)
Power supply type must be specified at time of order.
Power connection
Standard: AC, IEC-C13 Connector (Schurter v-lock compatible)
Located at the front of the Master Station, behind the display, one on either side for hot standby and dual
Master Stations.
Housing
Standard: 19” rack mount and panel mount fixings
Box dimensions (without fixings): width 440 mm, height 177 mm (4U), depth 237 mm
Single Master Station with 7” touch screen interface
Option: Dual Master Station, second independent Master Station in same housing (2 displays).
Hot standby, second redundant standby Master Station in same housing, linked to primary Master Station (2 displays).
Communication
between
Master Station
and FCUs
Standard: There is no standard communication module. The field network must be specified at time of order.
Option: The Master Station has 4 AIM (Add In Module) slots that can be fitted with host or field network modules. Only
one host AIM can be fitted; only one Modbus RTU AIM can be fitted; up to two Pakscan Classic AIMs can be fitted.
There are two field network AIM types.
Pakscan Classic (P4720).
Modbus RTU (P4724).
Both field network protocols are described briefly below:
Pakscan Classic (P4720):
• Redundant loop topology.
• Does NOT require external repeaters or external termination.
• Network total length up to 20 km.
• No limitation for distance between FCUs within the 20 km limit.
• A single network can control 240 FCUs.
• Data transfer via robust current loop network.
• Network baud rate ranges between 110 to 2400.
• Network scan rate (60 FCUs on 4 km loop) less than 1 second.
• Twisted pair instrumentation cable (1 pair).
• Communications parameters set up using handheld tool via network or using actuator menu.
• Ideal for isolating duty applications.
Modbus RTU (P4724):
• Standard open Modbus protocol.
• Compatible with any manufacturer's Modbus device.
• Single highway, dual highway or redundant loop topology.
• Single and dual highway option standard Modbus topology.
• Redundant loop 1.2 km maximum distances between FCUs.
• Network Baud rate up to 115k200.
• A single network can control up to 240 FCUs.
• Ideal for isolating duty applications.
FCU connectivity
The maximum number of FCUs that can connect to a Master Station is 240. When ordering a Master Station, select the
appropriate maximum FCU count for the application. It is possible to order Master Stations for 60, 120, 180 or 240 FCUs.
The following devices can be connected to the Rotork Master Station:
Any Rotork electric actuator with a:
• Pakscan Classic (current loop) network interface card (A, AQ, Q, IQ, IQT, SI, EH, CVA, CMA, ROMpak, CK).
• Modbus network interface card (Q, IQ, IQT, SI, EH, CMA, ROMpak, CK).
Any Rotork switch box or pneumatic / hydraulic actuator fitted with a:
• Pakscan Classic General Purpose Field Control Unit (GPFCU).
Any Rotork Modbus enabled device such as:
• Bifold Orange controller
Any third party manufacturers Modbus device:
• Contact Rotork for details of how to integrate
Communication
between the
Master Station
and the Host
Standard: 2 off RJ45 Ethernet (10/100/1000 Mbps) connections supporting Modbus TCP, located on each CPU module
(module P4710).
Other services on the Ethernet connection are:
Web server (built in web pages).
Option: Host Serial AIM (module P4727).
Serial communications via, 2 off 9-way D-type connections supporting Modbus RTU.
Individually configurable RS-232 to RS-485 via DIP switches.
Termination for RS-485 enabled via HMI or web pages (resistor network 120 Ω passive with 1 kΩ biasing).
Termination stays in place on power down.
Baud rate 2,400 to 115,200.
A hot standby system contains duplicate modules so the number of host connections is doubled. With the standard
CPU and optional Host Serial AIM installed, a total of four host connections of each type is available.
Service port Standard: 1 off RJ45 Ethernet port (10/100/1000 Mbps) for temporary connection to a computer. Intended for service or
configuration use only. Supports the same Ethernet services as the host connection.
A4US
US
A4
US A4
US
A4