RRS Jade XRD-01RDHAM3 Series User manual

INSTALLATION INSTRUCTIONS
MODELS (-)XRD-01RDHAM3
HORIZONTAL AIRFLOW ECONOMIZERS
WARNING
THIS ACCESSORY IS TO BE INSTALLED BY A QUALIFIED, LICENSED SERVICE PERSON. TO AVOID
UNSATISFACTORY OPERATION OR DAMAGE TO THE PRODUCT AND POSSIBLE UNSAFE CONDITIONS,
INCLUDING ELECTRICAL SHOCK, REFRIGERANT LEAKAGE AND FIRE, THE INSTALLATION
INSTRUCTIONS PROVIDED WITH THIS ACCESSORY MUST BE STRICTLY FOLLOWED AND THE PARTS
SUPPLIED USED WITHOUT SUBSTITUTION. DAMAGE TO THE PRODUCT RESULTING FROM NOT
FOLLOWING THE INSTRUCTIONS OR USING UNAUTHORIZED PARTS MAY BE EXCLUDED FROM THE
MANUFACTURER’S WARRANTY COVERAGE.
DISCONNECT ELECTRICAL POWER TO THE UNIT. FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK
RESULTING IN PERSONAL INJURY OR DEATH.
WARNING
TOOLS REQUIRED FOR INSTALLATION:
38" electric drill with 516" socket Waterproof exterior duct sealant Sheet metal tools (e.g. shears)
PACKAGE CONTENTS (-)XRD-01RDHAM3 economizer with controller,
actuator, and outside enthalpy sensor attached
ITEM DESCRIPTION PART No.
1Discharge Air Sensor (Hardware Bag) 610431557
2(2) Permanent Filters (11.875" X 23.875") 420000077
3(2) Spotweld Assy - Bird Screen 6039013C / BSWA
4(2) Exhaust Air Rainhood - Top 6039013C / EHT2
5OA Rainhood Assy - Left Side **39013C / EHSL
6OA Rainhood Assy - Right Side **39013C / EHSR
7(2) Exhaust Air Rainhood - Left Side 6039013C / EHS3L
8(2) Exhaust Air Rainhood – Right Side 6039013C / EHS3R
9OA Rainhood Assy - Filter Bracket Strip **39013C / ADP
10 OA Rainhood Assy – Top **39013C / EHT
11 OA Rainhood - Front Filter Support **39013C / EHB
12 OA Filter Rail 6039013C / FCH
13 Hardware Bag 6039013C / HDW
** = Paint Color. 59 = Warm Dark Grey, 60 = Green, 61 = R-410A Beige, 62 = Light Grey
TABLE 1
RMIHEJ13B
SUPERSEDES 05-27-15
JUNE 3, 2015

STEP 1:
Immediately upon receipt, all cartons and contents
should be inspected for transit damage. Units with
damaged cartons should be opened immediately.
If damage is found, it should be noted on the
delivery papers and a damage claim filed with the
last carrier. Compare carton(s) contents to
PACKAGE CONTENTS List (TABLE 1) above to
note any missing items.
STEP 2:
Remove SUPPLY COVER, RETURN COVER, PANEL
– TOP LEFT, and PANEL – LEFT BOTTOM SECTION
from the unit and retain for reuse (SEE FIGURE 1).
Retain screws.
STEP 3:
Fasten RETURN COVER (SEE FIGURE 2) over
bottom return opening using 2 retained screws.
Fasten SUPPLY COVER over bottom supply opening
using 2 retained screws.
STEP 4:
Remove screws from 3 sides of ROOF PANEL so that it
can be raised during economizer insertion.
STEP 5:
Remove jumper plug and slide economizer
into unit return air section (SEE FIGURE
2). After the economizer is installed,
connect unit ECONOMIZER PLUG to
economizer mating plug. Reinstall jumper
plug PL7 to PL21 (located on economizer).
2
FIGURE 1
FIGURE 2
ST-A1230-02
ST-A1230-01
REMOVE LEFT PANEL - LOWER
(TO BE REPLACED AFTER
ECONOMIZER INSERTION)
REMOVE LEFT PANEL - UPPER
(TO BE USED IN ECONOMIZER
RAIN HOOD ASSEMBLY)
REMOVE SUPPLY AIR COVER
(TO BE MOVED TO
DOWNFLOW OPENING)
REMOVE RETURN AIR COVER
(TO BE MOVED TO
DOWNFLOW OPENING)
LEAVE TOP PANEL TOP
SCREWS ENGAGED
REMOVE REMAINING SCREWS ON
SIDES OF TOP PANEL SO AS TO
LIFT TOP PANEL SLIGHTLY TO
ALLOW ECONOMIZER TOP FLANGE
TO GO UNDER TOP PANEL FLANGE
SLIDE ECONOMIZER INTO RETURN
AIR OPENING AS SHOWN. PLUG IN
WIRE HARNESS TO MATCHING PLUG
INSTALL RETURN AIR COVER
OVER DOWNFLOW OPENING
INSTALL SUPPLY AIR COVER
OVER DOWNFLOW OPENING

3
STEP 6:
Mount PANEL – LEFT BOTTOM SECTION to unit (SEE
FIGURE 3). Use only 2 screws (one on each side) for easy removal
during calibration.
STEP 7:
Fasten FILTER BRACKET STRIP to unit using 2 screws
(one on each side). See TABLE 1 for identification.
STEP 8:
Fasten 12 OA FILTER RAIL to FILTER BRACKET STRIP
with 4 screws.
STEP 9:
Fasten OA RAINHOOD - LEFT SIDE and OA
RAINHOOD - RIGHT SIDE to unit using 2 screws
provided.
STEP 10:
Slide PERMANENT FILTERS between OA
RAINHOOD - LEFT SIDE and OA RAINHOOD - RIGHT
SIDE back into the 12 OA FILTER RAIL.
STEP 11:
Fasten 11 OA RAINHOOD - FRONT FILTER SUPPORT to
PANEL – TOP LEFT. The bottom lip should support the
PERMANENT FILTERS.
STEP 12:
Fasten PANEL – TOP LEFT to OA RAINHOOD - LEFT
SIDE and OA RAINHOOD - RIGHT SIDE and 11 OA
RAINHOOD - FRONT FILTER SUPPORT using 12
screws.
STEP 13:
Position the OA RAINHOOD ASSY – TOP under edge
of ROOF PANEL.
STEP 14:
Re-secure ROOF PANEL using existing screws.
FIGURE 3
ST-A1230-03
11
12
TOP PANEL
INSTALL LEFT PANEL - UPPER
TO LEFT AND RIGHT PANEL SUPPORTS

4
ST-A1230-05
STEP 15:
Provide opening in return air duct to mount the two
barometric relief dampers and hoods (SEE FIGURE 4).
Locate a convenient distance from unit.
STEP 16:
Using self-drilling screws provided, assemble exhaust air
rain hoods (EXHAUST AIR RAINHOOD – TOP,
EXHAUST AIR RAINHOOD - LEFT SIDE, EXHAUST
AIR RAINHOOD - RIGHT SIDE, SPOTWELD ASSY -
BIRD SCREEN) and install in return air duct. Use sealant
(not provided) as required.
STEP 17:
Either open the BLOWER MOTOR HINGED DOOR or
remove the BLOWER MOTOR ACCESS PANEL (SEE
FIGURE 5).
STEP 18:
Connect the DISCHARGE AIR SENSOR to wires 51
and 52 located in the blower motor compartment.
NOTE:
The sensor is a white wire that ships strapped to the
economizer wire harness. The sensor should be secured
with the included wire tie to avoid entanglement with the
blower and direct contact with any sheet metal surfaces.
STEP 19:
Either close the BLOWER MOTOR HINGED DOOR or
reinstall the BLOWER MOTOR ACCESS PANEL.
STEP 20:
Upon start-up check the economizer sequence of
operation using the steps provided in these instructions.
After testing unit operation and setting outside air damper
minimum position, secure PANEL – LEFT BOTTOM
SECTION (SEE FIGURE 3) with remaining screws.
17.790
16.290
18.500
1.500
MIN.
WIRE TIE TO
SECURE SENSOR
FIGURE 4
ST-A1230-07
.000
.000
34.080
RECOMMENDED DUCT OPENING
SUPPLY AIR DUCT
ATTACH TO UNIT
RETURN AIR DUCT
CUT OPENINGS AND
ATTACH TO UNIT RELIEF DAMPERS
SLIDE IN DUCT
OPENINGS
FIGURE 5

5
DIRECT MOUNT ECONOMIZER OPERATION
GENERAL
This accessory economizer package is designed to save
energy costs by using outdoor air for cooling and
ventilation in place of mechanical cooling whenever
possible. The economizer continuously monitors indoor
and outdoor air conditions and compares them to a
user-selected setpoint to determine if free cooling is
available. The economizer utilizes a fully-modulating
damper actuator, which will control the outside air damper
and return air damper in order to maintain a factory-set
mixed air/discharge air temperature.
ACCESSORIES
(-)XRX-AV04 - Dual Enthalpy Upgrade Kit
For maximum energy savings, this upgrade kit will allow
the economizer to compare the outdoor air enthalpy to the
return air enthalpy, instead of a user-selected setpoint to
determine if "free cooling" is available. This Sylk Bus
Sensor is a combination temperature and humidity sensor
which is powered by and communicates on the two-wire
communication bus of the W7220 economizer logic
module. All OA (Outside Air) and RA (Return Air) sensors
are the same. Sensor must be set for the type of sensing
using the three DIP switches located on the sensor during
INSTALLATION.
Dip Switch Setting C1 C2 C3
Return Air Enthalpy Sensor ON OFF OFF
Outside Air Enthalpy Sensor OFF OFF OFF
(-)XRX-AR02 - Wall-Mounted Carbon Dioxide Sensor
For installations requiring Demand Control Ventilation
(DCV) based upon indoor air levels of carbon dioxide
(CO2). When the unit supply fan is running, the CO2sensor
modulates the outside air damper to maintain a
user-selected CO2level inside the occupied space.
Energy savings are achieved by not bringing in excessive
amounts of outdoor air when the indoor air conditions are
suitable. Energy savings can be substantial on buildings
with highly variable occupancy rates.
NOTE: The (-)XRX-AR02 has a default setting of a 2-10
Vdc output for a 500-1500 ppm CO2input. The W7220
economizer controller requires jumper pins on the
sensor to be relocated to provide a 0-2000 ppm input.
SW2 SW1 AN (ppm) Relay (ppm)
ON ON 0 to 1000 1000
OFF ON 0 to 2000 ¬1200
ON OFF 500 to 1500 800
OFF OFF 500 to 2000 1200
DIP SWITCH LABEL
DIP SWITCHES (3)
SYLK BUS 2 PIN *EURO"
CONNECTOR
SYLK BUS TERMINALS
(1 AND 2)
Wiring Schematic for (-)XRX-AR02
Note: Black & brown wire common.
OFF
ON
OFF
ON
OUT AN
)Current
SW2 SW1
0-100%
20-100%
)Voltage
RXRX-AR02 NEW JUMPER POSITION
(-)XRX-BFF02C, (-)XRX-BFF02D, (-)XRX-BFF02Y
Power Exhaust Kit
For installations requiring more space static pressure relief
than can be obtained with the standard barometric relief
damper included with the economizer, a power exhaust kit
can be added.

6
ADJUSTMENT METHOD
The user interface consists of an LCD display and a
4-button keypad on the front of the Economizer module.
The LCD is a 16 character by 2 line dot matrix display.
Power Up Cycle
All setpoints and advanced settings are restored after any
power loss (a power loss is assumed if voltage falls below
18 Vac). Normal operation is restored when power returns
above 18 Vac.
Initial Menu Display
On initial startup, Honeywell displays on the first line and
Economizer W7220 on the second line. After a brief
pause, the revision of the software appears on the first line
(second line is blank). It then displays W7220 on the first
line and STATUS on the second line.
Keypad
The four navigation buttons illustrated in Figure 9 are used
to scroll through the menus and menu items, select menu
items, and to change parameter and configuration
settings.
Using the Keypad with Menus
To use the keypad when working with menus:
lPress the pbutton to move to the previous menu.
lPress the qbutton to move to the next menu.
lPress the 8button (Enter) to display the first item in
the currently displayed menu.
lPress the Óbutton (Menu up) to exit a menu’s item
and return to the list of menus.
Using the Keypad with Settings and Parameters
To use the keypad when working with Setpoints, System
and Advanced Settings, Checkout tests, and Alarms:
lNavigate to the desired menu.
lPress the 8button (Enter) to display the first item in
the currently displayed menu.
lUse the pand qbuttons to scroll to the desired
parameter.
lPress the 8button (Enter) to display the value of the
currently displayed item.
lPress the pbutton to increase (change) the
displayed parameter value.a
lPress the qbutton to decrease (change) the
displayed parameter value.a
lPress the 8button to accept the displayed value and
store it in non-volatile RAM.
lWhen the value is accepted, CHANGE STORED is
displayed on the LCD.
lPress the 8button (Enter) to return to the current
menu parameter.
lPress the Óbutton (MenuUp/Exit) to return to the
previous menu.
Time-out and Screensaver
When no buttons have been pressed for 10 minutes, the
LCD displays a screen saver, which cycles through the
Status items. Each Status items displays in turn and cycles
to the next item after 5 seconds.
SETUP AND CONFIGURATION
Before being placed into service, the JADE™ Economizer
module must be setup and configured for the installed
system. Use the System Setup menu, the Advanced Setup
menu (if necessary), and the Setpoints menu to
accomplish this.
Menu Structure
The following tables illustrate the complete hierarchy of
menus and parameters for the JADE™ Economizer
system.
The Menus in display order are:
lSTATUS
lSETPOINTS
lSYSTEM SETUP
lADVANCED SETUP
lCHECKOUT
lALARMS
IMPORTANT
Your menu parameters may be different depending on
your configuration. For example if you do not have a DCV
(CO2) sensor, then none of the DCV parameters appear.
aWhen values are displayed, pressing and holding the por q button
causes the display to automatically increment.
FIGURE 9

7
Parameter
Parameter
Default
Value
Parameter
Range and
IncrementaNotes
ECON AVAIL NO YES/NO YES = economizing available; the system can use Outdoor Air for free cooling when required.
ECONOMIZING NO YES/NO YES = Outdoor Air being used for 1st stage cooling.
OCCUPIED NO YES/NO YES = 24 Vac OCC signal received from space thermostat input.
NO = 0 Vac on terminal OCC.
HEAT PUMP COOL COOL/HEAT Displays COOL or HEAT when SYSTEM is set to heat pump (nonconventional)
COOL Y1-IN OFF ON/OFF
Y1-I signal from space thermostat input for cooling stage 1 or heat pump heating stage 1.
ON = 24 Vac on terminal Y1-I
OFF = 0 Vac on terminal Y1-I
COOL Y1-OUT OFF ON/OFF Cool Stage 1 Relay Output to stage 1 mechanical cooling (Y1-OUT terminal).
COOL Y2-IN OFF ON/OFF
Y2-I signal from space thermostat input for second stage cooling or heat pump heating stage 2.
ON = 24 Vac on terminal Y2-I
OFF = 0 Vac on terminal Y2-I
COOL Y2-OUT OFF ON/OFF Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT terminal).
MA TEMP _ _._ºF -40 to 150ºF Displays value of measured mixed air from MAT sensor.
Displays -.- if not connected, short, or out-of-range.
DA TEMP _ _._ºF -40 to 150ºF
Displays when Discharge Air Sylk Bus sensor is connected and displays measured discharge
air temperature. Displays -.-°F if sensor sends invalid value, if not connected, short or
out-of-range.
OA TEMP _ _._ ºF -40 to 140ºF Displays measured value of outdoor air temperature. Displays -°F if sensor sends invalid value,
if not connected, short or out-of-range.
OA HUM _ _% 0 to 100% Displays measured value of outdoor humidity. Displays -% if not connected, short, or
out-of-range.
RA TEMP _ _._ºF 0 to 140ºF If field installed Dual Enthalpy sensor is connected, displays measured value of return air tem-
perature. Displays -°F if sensor sends invalid value, if not connected, short or out-of-range.
RA HUM _ _% 0 to 100% If field installed Dual Enthalpy sensor is connected, displays measured value of return air hu-
midity. Displays -% if sensor sends invalid value, if not connected, short or out-of-range.
IN CO2_ _ _ ppm "0 to 2000
(3500) ppm"
If field installed CO2sensor is connected, displays value of measured CO2. Invalid if not con-
nected, short or out-of-range. May be adjusted in Advanced menu by Zero offset and Span.
DCV STATUS n/a n/a If field installed CO2sensor is connected, displays ON if above setpoint and OFF if below
setpoint.
DAMPER OUT _ _% 0 to 100% Displays output position to the damper actuator. When used with Honeywell communicating ac-
tuator the damper out is in XX.X%
ACT POS. n/a 0 to 100% Displays actual position of actuator.
ACT COUNT n/a 1 to 65,535 Displays number of times actuator has cycled. 1 Cycle equals 180° of movement in any direc-
tion.
ACTUATOR n/a OK/Alarm Displays Error on ALARM MENU if voltage or torque is below actuator range.
EXH1 OUT OFF ON/OFF Output of EXH1 terminal. - ON = relay closed; OFF = relay open.
EXH2 OUT OFF ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = EXH2
ERV OFF ON/OFF Output of AUX1 O terminal; displays only if AUX1 O = ERV
"MECH COOL ON
HEAT STGS ON" 00, 1, or 2 Displays stage of mechanical cooling that is active. Displays the stage of heat pump heating
that is active.
FAN SPEED n/a LOW/HIGH Displays speed of fan on a 2-speed fan unit
W (HEAT IN) n/a ON/OFF Displays status of heat on a 2-speed fan unit.
STATUS MENU

8
SETPOINTS MENU
Parameter
Parameter
Default
Value
Parameter
Range and
IncrementaNotes
MAT SET 53ºF 38 to 70ºF;
increment by 1
Setpoint determines where the economizer will modulate the OA damper to maintain the mixed
air temperature.
LOW T LOCK 32ºF -45 to 80ºF;
increment by 1
Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on.
Commonly referred to as the Compressor lockout.
DRYBLB SET 63ºF 48 to 80ºF;
increment by 1
Setpoint determines where the economizer will assume outdoor air temperature is good for free
cooling; e.g.; at 63ºF unit will economizer at 62ºF and below and not economize at 64ºF and
above. There is a 2ºF deadband.
ENTH CURVE ES3 ES1, ES2, ES3,
ES4, or ES5
Does not display if a field installed Dual Enthalpy kit is connected. Enthalpy boundary "curves"
for economizing using single enthalpy comparison between outdoor air enthalpy and setpoint.
DCV SET 1100 ppm 500 to 2000 ppm
increment by 100
Displays ONLY if field installed CO2sensor is connected. Setpoint for Demand Control Ventila-
tion of space. Above the setpoint, the OA dampers will modulate open to bring in additional OA
to maintain a space ppm level below the setpoint.
MIN POS 2.8 V 2 to 10 Vdc
Displays ONLY if a CO2sensor is NOT connected.
With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) set-
tings are required. Default for MIN POS L is 3.2V and MIN POS H is 2.8V
VENTMAX 2.8 V
2 to 10 Vdc
Displays only if a field installed CO2sensor is connected. Used for Vbz (ventilation max cfm)
setpoint. VENTMAX is the same setting as MIN POS would be if you did not have the CO2sen-
sor.
100 to 9990 cfm
increment by 10
If OA, MA, RA and CO2sensors are connected and DCV CAL ENABLE is set to AUTO mode,
the OA dampers are controlled by CFM and displays from 100 to 9990 cfm.
2 to 10 Vdc With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H (high speed fan)
settings are required. Default for VENTMAX L is 3.2V and VENTMAX H is 2.8V.
VENTMIN 2.25 V
2 to 10 Vdc Displays only if field installed CO2sensor is connected. Used for Va (ventilation min cfm)
setpoint. This is the ventilation requirement for less than maximum occupancy of the space.
100 to 9990 cfm
increment by 10
If OA, MA, RA and CO2sensors are connected and DCV CAL ENABLE is set to AUTO mode,
the OA dampers are controlled by CFM and displays from 100 to 9990 cfm.
2 to 10 Vdc With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H (high speed fan) set-
tings are required. Default for VENTMIN L is 2.5V and VENTMIN H is 2.25V.
ERV OAT SP 32ºF 0 to 50ºF;
increment by 1 Only when AUX1 O = ERV
EXH1 SET 50% 0 to 100%;
increment by 1
Setpoint for OA damper position when exhaust fan 1 is powered by the economizer. With
2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are required.
Default for Exh1 L is 65% and Exh1 H is 50%.
EXH2 SET 75% 0 to 100%;
increment by 1
Setpoint for OA damper position when exhaust fan 2 is powered by the economizer. Only used
when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) settings are re-
quired. Default for Exh2 L is 80% and Exh2 H is 75%.

9
SYSTEM SETUP MENU
Parameter
Parameter
Default
Value
Parameter
Range and
IncrementaNotes
INSTALL 01/01/2011 Display order = MM/DD/YY. Setting order = DD, MM, then YY.
UNITS DEG ºF ºF or ºC Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT HP O/B CONV
HP O/B
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump ("B" – signal) input from
thermostat.
CONV = conventional.
AUX2 I HP(B)
Shutdown (SD)
Heat (W1)
HP(O)
HP(B)
In HP O/B mode: HP(O) = energize heat pump on Cool; HP(B) = energize heat pump on
Heat.
In CONV mode: SD = Enables configuration of shutdown; W = Informs controller that system
is in heating mode. NOTE: If using 2-speed fan mode, you must program CONV mode for W.
Shutdown is not available in the two speed fan mode.
FAN TYPE 1 speed 1 speed/
2 speed
Sets economizer controller for operation of 1 speed or 2 speed supply fan NOTE: 2-speed
fan option also needs Heat (W1) programmed in AUX 2 In.
FAN CFM 5000cfm
100 to 15000
cfm;
increment by
100
This is the airflow capacity of the rooftop unit or air handler. The value is found in the unit
I&O manual or specification sheet. The cfm of the indoor fan is only used with the DCVCAL
ENA parameter set in the AUTO mode.
AUX1 OUT EXH2
NONE
ERV
EXH2
SYS
lNONE = not configured (output is not used)
lERV= Energy Recovery Ventilator
lEXH2 = second damper position relay closure for second exhaust fan.
lSYS = use output as an alarm signal
OCC INPUT INPUT or
ALWAYS
The indoor fan "G" or "ON" Signal. Can also be used with a setback thermostat with occu-
pancy out (24 Vac), where the 24 Vac is input "INPUT" to the OCC terminal. If no occupancy
output from the thermostat then change program to "ALWAYS".
FACTORY
DEFAULT NO NO or YES Resets all set points to factory defaults when set to YES. LCD will briefly flash YES and
change to NO but all parameters will change to factory default values.

10
Parameter
Parameter
Default
Value
Parameter
Range and
IncrementaNotes
MA LO SET 45ºF 35 to 55ºF
increment by 1º Temp to activate Freeze Protection (close damper and alarm if temp falls below setup value)
FREEZE POS CLO CLO
MIN Damper position when freeze protection is active (closed or MIN POS).
CO2ZERO 0 ppm 0 to 500 ppm
increment by 10
Displays only if field installed CO2sensor is connected. CO2ppm level to match CO2sensor
start level.
CO2SPAN 2000 ppm
1000 to 3000
ppm;
increment by 50
Displays only if field installed CO2sensor is connected. CO2ppm span to match CO2sensor.
STG3 DLY 2.0h
0 min, 5 min, 15
min, then 15
min intervals.
Up to 4h or OFF
Delay after stage 2 for cool has been active. Turns on 2nd stage of cooling when economizer
is 1st stage and mechanical cooling is 2nd stage. Allows three stages of cooling, 1
economizer and 2 mechanical. OFF = no Stage 3 cooling.
SD DMPR POS CLO CLO
OPN
Indicates shutdown signal from space thermostat. When controller receives 24 Vac input on
the SD terminal in conventional mode, the OA damper will open if programmed for OPN and
OA damper will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc.
will shut off.
DCVCAL ENA MAN MAN (manual)
AUTO
Displays only if all sensors (RA, OA, MA and CO2) are connected. Turns on the DCV auto-
matic control of the dampers. Resets ventilation based on the RA, OA and MA sensor condi-
tions.
This operation is not operable with a 2-speed fan unit.
MAT T CAL 0.0 F° +/-2.5F° Allows for the operator to adjust for an out of calibration mixed air temperature sensor.
OAS T CAL 0.0F° +/-2.5F° Allows for the operator to adjust for an out of calibration outdoor air temperature sensor.
OAS H CAL 0% RH +/-10% RH Allows for the operator to adjust for an out of calibration outdoor air humidity sensor.
RA T CAL 0.0F° +/-2.5F° If field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an out
of calibration temperature sensor.
RA H CAL 0% RH +/-10% RH If field installed Dual Enthalpy sensor is connected, allows for the operator to adjust for an out
of calibration humidity sensor.
DA T CAL 0.0 F° +/-2.5F° Allows for the operator to adjust for an out of calibration Discharge Air Sylk Bus temperature
sensor.
2SP FAN DELAY 5 Minutes
0 to 20 minutes
in 1 minute
increments.
When in economizing mode this is the delay for the high speed fan to try to satisfy the call for
second stage cooling before the first stage mechanical cooling is enabled.
ADVANCE SETUP MENU

11
CHECKOUT MENU
Parameter Parameter
Default Value
Parameter Range
and IncrementaNotes
DAMPER VMIN-HS n/a n/a Positions damper to VMIN position
DAMPER VMAX-HS n/a n/a Positions damper to VMAX position.
DAMPER VMAX-LS With 2-speed fan units the damper will position to VMAX low speed fan.
DAMPER OPEN n/a n/a Positions outside air damper to the full open position.
DAMPER CLOSE n/a n/a Positions outside air damper to the fully closed position.
CONNECT Y1-O n/a n/a Closes the Y1-O relay (Y1-O); energizes 1st stage compressor.
CONNECT Y2-O n/a n/a Closes the Y2-O relay (Y2-O); energizes 2nd stage compressor.
CONNECT EXH1 n/a n/a Closes the power exhaust fan 1 relay (EXH1)
CONNECT EXH2 n/a n/a
Energizes the EXH2 output. The EXH2-O can be replaced by:
lERV
lEXH2
lSYS.
lAUX1 O
Based on AUX1 O switch settings or is not available if AUX1 O is set to NONE
Checkout Tests
Use the Checkout menu to test the damper operation and any configured outputs. Only items that are configured are
shown in the Checkout menu.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the pand qbuttons.
2. Press the 8button to select the item.
3. RUN? appears on the display.
4. Press the 8button to start the test.
5. The unit pauses and then displays TEST RUNNING.
6. Press the button Ó(Menu up) to end the test (e.g. turn off the relay). Test stops automatically after 10 minutes without
a command or mode change, and will resume normal operation.
The checkout tests can all be performed at the time of installation or any time during the operation of the system as a test
that the system is operable.
NOTE: Be sure to allow for enough time for compressor startup and shutdown between checkout tests so that you do not
short-cycle the compressors and damage them from extreme short-cycling.

12
Test of Outdoor Air Enthalpy Sensor
Outdoor air enthalpy sensors with a date code after 1301
can simulate an outdoor air temperature/humidity
condition that forces the W7220A economizer controller
into free cooling mode. If the sensor is from prior to date
code 1301, it can be temporarily replaced with a newer
sensor (Note: There will be a sideways 2 following the part
number on the label as shown in the image below). To
force the controller into economizing mode:
1. Apply power to the unit.
2. Check the STATUS screen on the W7220A for actual
outdoor air (OA) temperature and OA humidity
readings.
3. With power applied to the unit and the C7400S sensor
connected, change the sensor’s 3-position DIP switch
in the order shown below without delay between steps
(from OFF, OFF, OFF to the ON, ON, ON position and
immediately back to OFF, OFF, OFF position). A
stickpin or some other small tool is necessary to move
the DIP switches.
4. The output of the C7400S to the W7220A will be 40°F
and 40% RH which will allow the economizer to go into
free cooling mode (economizing available).
5. By energizing the “G” terminal and “Y1” terminal on the
unit thermostat strip a call for cooling is established
and the economizer response can be observed.
6. After 15 minutes the C7400S sensor will change back
to the actual OA temperature and humidity.

13
ALARM MENU
Parameter Parameter Default
Value
Parameter Range
and IncrementaNotes
MA T SENS ERR n/a n/a
Alarms display only when they are active. The menu title “ALARMS (_)”includes the
number of active alarms in parenthesis ().
CO2SENS ERR n/a n/a
OA T SENS ERR n/a n/a
DA ENTHL ERR n/a n/a
SYS ALARM n/a n/a When AUX1 O is set to SYS and there is any alarm (e.g., failed sensors, etc.), the
AUX1 O terminal has 24 Vac out.
ACT UNDER V n/a n/a Voltage received by Actuator is above expected range
ACT OVER V n/a n/a Voltage received by Actuator is below expected range
Alarms
The Economizer module provides alarm messages that display on the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before checking for alarms. This allows time for all the
configured devices (e.g. sensors, actuator) to become operational. The exception is the MA sensor which
will alarm immediately.
If one or more alarms are present and there has been no keypad activity for at least 5 minutes, the Alarms menu displays
and cycles through the active alarms. You can also navigate to the Alarms menu at any time.
Clearing Alarms
Once the alarm has been identified and the cause has been removed (e.g. replaced faulty sensor), the alarm can be
cleared from the display. To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the 8button.
3. ERASE? displays.
4. Press the 8button.
5. ALARM ERASED displays.
6. Press the button Ó(MenuUp/Exit) to complete the action and return to the previous menu.
NOTE: If an alarm still exists after you clear it, it redisplays within 5 seconds.

14
TYPICAL ADJUSTMENTS
1. Economizer ENTH CURVE Setpoint
a. Only the coolest, driest outside air is used for
economizer operation when parameter “ES5" is
selected on the SETPOINT MENU. Select
parameter “ES1” on the SETPOINT MENU for the
greatest energy savings.
b. Adjustments are ES1, ES2, ES3, ES4, ES5.
c. “ES3” is the default setting.
d. Economizer ENTH CURVE Setpoint can be
adjusted at any time and may need adjustment for
jobsite conditions.
JADE™ECONOMIZER MODULE
Single Enthalpy and Dual Enthalpy High Limit Curves
Enthalpy
Curve
Temp.
Dry-Bulb (°F)
Temp.
Dewpoint (°F)
Enthalpy
(btu/lb/da)
Point P1 Point P2
Temp. °F Humidity %RH Temp. °F Humidity %RH
ES1 80.0 60.0 28.0 80.0 36.8 66.3 80.1
ES2 75.0 57.0 26.0 75.0 39.6 63.3 80.0
ES3 70.0 54.0 24.0 70.0 42.3 59.7 81.4
ES4 65.0 51.0 22.0 65.0 44.8 55.7 84.2
ES5 60.0 48.0 20.0 60.0 46.9 51.3 88.5
HL 86.0 66.0 32.4 86.0 38.9 72.4 80.3
2. EXH1 SET - Adjustments for (optional) power exhaust.
a. The outside air damper position at which the
power exhaust fan(s) will engage.
b. With 2-speed indoor fan units EXH1 L (low speed
fan) and EXH1 H (high speed fan) settings are
required.
c. Default for EXH1 L is 65% and EXH1 H is 50%.
d. After the outside air damper output command
DAMPER OUT (not ACT POS.) reaches the
power exhaust setpoint, the power exhaust output
EXH1 is energized after a 45 second delay.
e. Range of adjustment is from 0-100% outside air.
e. Single enthalpy strategy: If outdoor air enthalpy is
lower than the ENTH CURVE setpoint, then free
cooling is available.
f. Dual enthalpy strategy: ENTH CURVE Setpoint is
not used. If outdoor air enthalpy is lower than
return air enthalpy, then free cooling is available.
There is also a high limit boundary for dual
enthalpy. The high limit boundary is “ES1” when
there are no stages of mechanical cooling
energized and "HL" when a compressor stage is
energized.
3. EXH2 SET - Adjustments for (optional) 2 speed power
exhaust.
a. The outside air damper position at which the 2nd
speed of the power exhaust fan(s) will engage.
b. With 2-speed indoor fan units EXH2 L (low speed
fan) and EXH2 H (high speed fan) settings are
required.
c. Default for EXH2 L is 80% and EXH2 H is 75%.
d. After the outside air damper output command
DAMPER OUT (not ACT POS.) reaches the
power exhaust setpoint, the power exhaust output
EXH2 is energized after a 45 second delay to
allow the damper to reach the appropriate
position.
e. Range of adjustment is from 0-100% outside air.

15
4. MIN POS - Outside Air Damper minimum position
a. Displays ONLY if a CO2sensor is NOT connected.
With 2-speed fan units MIN POS L (low speed fan)
and MIN POS H (high speed fan) settings are
required. Default for MIN POS L is 3.2V and MIN
POS H is 2.8V.
b. Adjust MIN POS to allow the minimum amount of
outdoor air, as required by local codes, to enter the
building.
c. Range of adjustment is from 0-100% (2-10V); in
most applications MIN POS is adjusted to allow
10% to 25% outside air to enter the system.
d. MIN POS can be adjusted at any time.
e. Whenever the “G” (supply fan) signal is present,
the damper will open to this minimum position
unless the mixed air sensor falls below the MA LO
SET (Freeze Protect Mode Setpoint).
5. VENTMAX - Demand Control Ventilation (DCV)
Maximum Setpoint
a. Displays only if a CO2sensor is connected.
b. VENTMAX allows the installer to limit the amount
of outdoor airflow into the building when DCV
overrides the mixed air temperature sensor
setpoint. It is normally equal to the minimum
amount of outdoor air under maximum
occupancy, as required by local codes, to enter
the building.
c. VENTMAX can be adjusted at any time.
6. VENTMIN - Demand Control Ventilation (DCV)
Setpoint
a. Displays only if a CO2sensor is connected.
b. Is the ventilation requirement for less than
maximum occupancy of the space.
c. Compatible CO2sensors will have a 2-10Vdc
output for a 0-2000 ppm CO2input.
d. DCV modulates the outdoor damper between the
VENTMIN and VENTMAX settings to provide
ventilation based on occupancy. The carbon
dioxide (CO2) sensor is used to indirectly monitor
occupancy level.
e. No cooling signal (e.g.Y1, Y2) is required for DCV
to override the outdoor air damper when
ventilation requires outdoor air.
f. The controller must receive a “G” (supply fan)
signal to open the damper.
g. Range of adjustment is from 2 Volts to 10 Volts.
h. VENTMIN can be adjusted at any time.
I. The controller compares the CO2sensor input to
VENT MIN to determine the damper minimum
position.
I. If the actual CO2level is below the setpoint,
then the damper minimum position is
determined by the damper minimum position
(VENTMIN) setting.
ii. If the actual CO2level rises above the
setpoint, then the damper minimum position is
overridden proportionally more open up to the
VENTMAX setting.
iii. If the mixed air temperature drops below 45°F
(MA LO SET - Freeze Protect Mode Setpoint),
the DCV input will be overridden and the
damper may not open.
j. Ensure proper polarity of the sensor wires when
connecting to the economizer controller. Incorrect
polarity negates the sensor signal.
NORMAL OPERATION
1. Fan Only (G)
a. Damper will go to minimum position (in 90
seconds or less) whenever the “G” (supply fan)
signal is present.
b. When “G” signal is removed, the outside air
damper closes against blade seals for tight shutoff
of outside air.
c. If the mixed air temperature drops below 45°F (MA
LO SET Setpoint), then the control will override
the minimum position setting and will modulate the
outside air damper closed.
2. Call for First Stage of Cooling (Y1)
a. Economizer Unavailable (warm outdoor air):
Closes the Y1-O relay (Y1-O) which energizes 1st
stage compressor.
b. Economizer Available (free cooling): The
controller tries to maintain a mixed air temperature
of 53°F ± 5 (MAT SET Setpoint) by modulating the
outside air damper position.
3. Call for Second Stage of Cooling (Y2)
a. Economizer Unavailable (warm outdoor air):
Closes the Y2-O relay (Y2-O) which energizes
2nd stage compressor.
b. Economizer Available (free cooling): Closes the
Y1-O relay (Y1-O) which energizes 1st stage
compressor. The controller tries to maintain a
mixed air temperature of 53°F ± 5 (MAT SET
Setpoint) by modulating the outside air damper
position. After a time period of 2 hours of
simultaneous economizer operation and first
stage compressor operation, the economizer
closes the Y2-O relay (Y2-O) which energizes 2nd
stage compressor.
4. Call for Heat
a. Standard Air Conditioner with electric or gas heat.
(W1 & W2)
I. The Thermostat controls the stages of heating
directly.
ii. If the control detects that the supply fan is on
(through its “G” input), then the control will
open the damper to minimum position.
iii. If the mixed air temperature drops below 45°F
(MA LO SET Setpoint), then the control will
override the minimum position setting and will
modulate the outdoor damper closed.
b. Heat Pump Operation (B)
I. The “B” signal from the Thermostat allows
operation of the compressors to provide
heating without delay.
ii. If the control detects that the supply fan is on
(through its “G” input), then the control can
open the damper to minimum position.
iii. If the mixed air temperature drops below 45°F
(MA LO SET Setpoint), then the control will
override the minimum position setting and will
modulate the outdoor damper closed.

16
NOTES
1. This economizer requires a two-stage thermostat.
2. When diagnosing the system, the best results are
obtained by first putting the fan setting on the
Thermostat to the “Continuous Fan” mode.
3. Operation of the optional power exhaust only depends
upon the supply fan running and the damper position
(it is possible to set the minimum position high enough
to engage the power exhaust in the heating mode).
Table of Inputs and Output Response with and without a CO2Sensor (DCV)
Inputs to Controller Outputs from Controller
DCV Free Cooling
Available? Y1-I Y2-I AUX2-I FAN Y1-O Y2-O OA Damper position
None
NO
OFF OFF OFF OFF OFF OFF CLOSED
OFF OFF OFF ON OFF OFF MIN POS
ON OFF OFF ON ON OFF MIN POS
ON ON OFF ON ON ON MIN POS
ON OFF ONdON ON OFF MIN POS
ON ON ONdON ON ON MIN POS
YES
OFF OFF OFF ON OFF OFF MIN POS
ON OFF OFF ON OFF OFF MIN POS to 100%
ON ON OFF ON ON OFFbMIN POS to 100%
ON OFF ONdON ON OFF MIN POS
ON ON ONdON ON ON MIN POS
Below
Setpoint
NO
OFF OFF OFF ON OFF OFF VENTMIN
ON OFF OFF ON ON OFF VENTMIN
ON ON OFF ON ON ON VENTMIN
ON OFF ONdON ON OFF VENTMIN
ON ON ONdON ON ON VENTMIN
YES
OFF OFF OFF ON OFF OFF VENTMIN
ON OFF OFF ON OFF OFF VENTMIN to 100%
ON ON OFF ON ON OFFbVENTMIN to 100%
ON OFF ONdON ON OFF VENTMIN
ON ON ONdON ON ON VENTMIN
Above
Setpoint
NO
OFF OFF OFF ONcOFF OFF VENTMIN to VENTMAX
ON OFF OFF ON ON OFF VENTMIN to VENTMAX
ON ON OFF ON ON ON VENTMIN to VENTMAX
ON OFF ONdON ON OFF VENTMIN to VENTMAX
ON ON ONdON ON ON VENTMIN to VENTMAX
YES
OFF OFF OFF ONcOFF OFF VENTMIN to VENTMAX
ON OFF OFF ON OFF OFF VENTMIN to 100%
ON ON OFF ON ON OFFbVENTMIN to 100%
ON OFF ONdON ON OFF VENTMIN TO VENTMAX
ON ON ONdON ON ON VENTMIN TO VENTMAX
b With STG3 DLY in ADVANCED SETUP MENU at 2.0 hours, the 2nd stage of mechanical cooling Y2-O can be energized after a 2 hour delay if the call
for Y1-I and Y2-I have not been satisfied.
cThe CO2sensor has a relay output that is active when the CO2level is above 1200ppm that can be used to energize the indoor fan through the “G”
thermostat input of the unit even if there is not a call for fan, cooling or heating by the room thermostat. Additional field wiring is required to enable this
option.
dAUX2-I is used only on heat pump models to indicate unit is in heat pump (heating) mode.
4. Upon loss of power to the unit or economizer, the
outside air damper will spring close shut in about 5
seconds.
5. The mist eliminator (Permanent Outdoor Air Filter) is of
aluminum mesh construction and should be cleaned
by flushing regularly with warm soapy water. The
replacement mist eliminator size is listed on the first
page of these instructions.
6. Compressor Time Delays, Compressor Interstage
Delays are not provided by the economizer controller.

17
Table of Inputs and Output Response with and without a CO2Sensor (DCV) for Unoccupied Mode
Inputs to Controller Outputs from Controller
DCV Free Cooling
Available? Y1-I Y2-I AUX2-I FAN Y1-O Y2-O OA Damper position
(Unoccupied)e
None
NO
OFF OFF OFF OFF OFF OFF CLOSED
OFF OFF OFF ON OFF OFF CLOSED
ON OFF OFF ON ON OFF CLOSED
ON ON OFF ON ON ON CLOSED
ON OFF ONdON ON OFF CLOSED
ON ON ONdON ON ON CLOSED
YES
OFF OFF OFF ON OFF OFF CLOSED
ON OFF OFF ON OFF OFF CLOSED to 100%
ON ON OFF ON ON OFFbCLOSED to 100%
ON OFF ONdON ON OFF CLOSED
ON ON ONdON ON ON CLOSED
Below Setpoint
NO
OFF OFF OFF ON OFF OFF CLOSED
ON OFF OFF ON ON OFF CLOSED
ON ON OFF ON ON ON CLOSED
ON OFF ONdON ON OFF CLOSED
ON ON ONdON ON ON CLOSED
YES
OFF OFF OFF ON OFF OFF CLOSED
ON OFF OFF ON OFF OFF CLOSED to 100%
ON ON OFF ON ON OFFbCLOSED to 100%
ON OFF ONdON ON OFF CLOSED
ON ON ONdON ON ON CLOSED
Above Setpoint
NO
OFF OFF OFF ONcOFF OFF CLOSED
ON OFF OFF ON ON OFF CLOSED
ON ON OFF ON ON ON CLOSED
ON OFF ONdON ON OFF CLOSED
ON ON ONdON ON ON CLOSED
YES
OFF OFF OFF ONc OFF OFF CLOSED
ON OFF OFF ON OFF OFF CLOSED to 100%
ON ON OFF ON ON OFFbCLOSED to 100%
ON OFF ONdON ON OFF CLOSED
ON ON ONdON ON ON CLOSED
eUnoccupied Mode is only available by field wiring a normally open (NO) relay in the “G” signal wiring between the unit and economizer. A thermostat
with an occupied output is required which energizes the relay when the space is occupied. The relay interrupts the 24 volt “G” signal from the unit
indoor fan when the space is unoccupied.
Mixed Air / Discharge Air Temperature vs.

Low Leak Horizontal Gear Economizer
RKKB / RLKB 090-150
Notes:
1. Unit wiring shown as reference only. Check unit wiring for actual unit wiring.
WIRE COLOR CODE
BLK Black BLU Blue
BRN Brown GRN Green
GRY Gray ORG Orange
RED Red TAN Tan
VIO Violet WHT White
YEL Yellow
COMPONENT CODE Revision Change Date
HARNESS ENDS AT PL20
10J1H Mixed Air Sensor
C7400S Fresh Air Sensor
J2 Power Exhaust Cap
MS3110J Damper Actuator 24v
PL6 Male Interface Unit Plug
PL7 RTU Factory Adaptor
PL20 Female Economizer Cap
PL21 Smoke Detector Male Plug
PL22 Smoke Detector Harness (Optional)
W7220A Logic Module
A
Date: April 15, 2015
Supersedes:
Drawn by: MGL
Unit #: 60-396-13C
Diagram#: 6039613CW
Approved by:
Table of contents