Intrinsically Safe Sounder Type DA132
Description
The DA132 Sounder is a lightweight warning Sounder, certified to Ex II 1G Ex ia IIC T4 (Ta –20
o
C to 55°C) with
32 user-selectable tones, and an output level of over 100dB. The Sounder enclosure is also rated to IP65.
The DA132 can be connected to the DA135 to create a single point annunciator, from a single zener barrier or
galvanic isolator.
Connection Details
(1)
2nd
TONE
(2)
0V
(4)
+V
DA135
(3)
+V
To generate the second tone connect the –ve supply to
terminal 1 or short to terminal 2.
NOTE: Sounder must be powered via a suitable
Zener barrier or Galvanic Isolator to prevent
damage to the sounder
Installation
Mounting
The Sounder should be mounted using the two
available fixing holes in the base. It is recommended
that stainless steel nuts and bolts be used if the
environment is corrosive.
Removing and Replacing the cover
If required the mechanism for locking the Sounder to
the base can be activated by removing the thin section
of plastic shown in Fig 1 with side cutters or a similar
tool. To open a locked head, remove the small black
bung from the hole on the side of the sounder, insert a
thin wire/pointer to depress the clip whilst twisting the
head.
Weatherproof Installation
The O-ring and bung must be fitted and suitable cable
glands used to achieve an IP65 rating. In order to avoid
collection of moisture in the speaker horn, the Sounder
should not be installed with the grille facing directly
upwards.
Wiring
Cable termination should be in accordance with
specifications application of the installation.
The base has three knockouts, two on the side and one
on the base, to accommodate a 20mm conduit or M20
cable glands.
Ensure that only the correct glands are used to maintain
the IP rating of the final assembly
Recommended Cable
0.5 to 2.5mm
2
with earthed screen and insulating
sheath. Cable parameters are determined by the output
parameters of the interface selected.
Sound Level
The sound level for each of the individual tones are
shown in Table 2. This is assuming the DA132 set at full
volume, driven from a suitable IS interface as shown in
Table 1. A single turn potentiometer is provided to
reduce the volume level by a minimum of 15dB.
Fig.1 Remove
tab to lock
sounder

RTK Instruments Limited
St James Business Park,
Knaresborough, North Yorkshire,
England. HG5 8PJ
Telephone: +44 (0)1423 580500
Facsimile: +44 (0)1423 580501
Web: www.rtkinstruments.com
Email: enquiry
@
rtkinstruments.com
Page 2 of 5
DA-132 Rev 0
Manufacturers of
Alarm Annunciators and Systems | Sequential Event
Recorders | Display Facias | Hazardous Area Interface,
Alarm and Display Products | Signal Conditioning &
Trip Amplifiers | Process Instrumentation
ISO 9001
FM 14290
Labelling
The sounder is shipped with the following labels:-
•A label marking with the appropriate Serial No. and
manufacturing date on the bottom of the enclosure.
•A Certification Label as shown in Fig 2 showing all
relevant certification information.
INSTRUMENTS
KNARESBOROUGH
HG5 8PJ, UK
Ui=28V Ii=300mA Pi=1.2W
WARNING: POTENTIAL
ELECTROSTATIC DISCHARGING
HAZARD - SEE INSTRUCTIONS
1180
IS SOUNDER TYPE:DA-132
CERTIFICATE No: IECEx BAS 07.0026X
CERTIFICATE No: Baseefa07ATEX0120X
II 1 G Ex ia IIC T4 -20°C <T
a
< +55°C
Fig 2
EMC Compliance
Immunity to EN61000-6-2 : 2005
Emissions to EN6100-6-4 : 2007
Environment
Operating temperature : -20°C to +55°C
Storage temperature: -20°C to +80°C
Humidity: 0-95% RH, non condensing
Protection
IP65
Construction
High impact, flame retardant polycarbonate
Cable Entry
The base has three knockouts, two on the side and
one on the base, to accommodate a 20mm conduit
or M20 cable glands.
Connections
For conductors up to 2.5mm
2
Recommended IS Interfaces
Nominal Supply Barriers/Isolators
24V MTL7728P+, MTL7728+,
(MTL7729P+ for IIB only)
MTL5521
12V MTL7715P+
Specification
Standards: ATEX certified to EN 60079-0:2004 and
EN60079-11:2007
IECEx certified to IEC60079-0:2004 and
IEC60079-11:2006
Approved for II 1G Ex ia IIC T4 (Ta –20
o
C to
+55°C)
Location
Zone 0, 1 or 2. Gas Group, IIC, IIB or IIA,
Temp Class up to T4
Certificate No’s
Baseefa07ATEX0120X
IECEx BAS 07.0026X
Safety Parameters
Vi = 28V
Ii = 300mA
Pi = 1.2W
Ci = Li = 0
Please refer to EC Type Examination certificates for full
details on suitable interface devices
Supply
12 to 24VDC +/-20%
Max current, 44mA @24V, max 40mA @ 12V
Table 1
Special Conditions for use
The certificate number has an ‘X’ suffix, which indicates that the certificate contains one of more special conditions
for safe use. These are below:
Electrostatic Risk: The equipment shall not be directly installed in any process where its enclosure might be
electro-statically charged by the rapid flow of a nonconductive media. Care must be taken when cleaning, and if
this is necessary it must be done with a damp cloth.

RTK Instruments Limited
St James Business Park,
Knaresborough, North Yorkshire,
England. HG5 8PJ
Telephone: +44 (0)1423 580500
Facsimile: +44 (0)1423 580501
Web: www.rtkinstruments.com
Email: enquiry
@
rtkinstruments.com
Page 3 of 5
DA-132 Rev 0
Manufacturers of
Alarm Annunciators and Systems | Sequential Event
Recorders | Display Facias | Hazardous Area Interface,
Alarm and Display Products | Signal Conditioning &
Trip Amplifiers | Process Instrumentation
ISO 9001
FM 14290
Operating Instructions
Fig 3
Tone Selection
The required tone should be selected by referring to Table 2 below. The first 5 DIL switches of the DIL switch on
the PCB should then be set to the code as shown (1 = ON, 0 = OFF).
Mode Selection
The Sounder has two modes Normal Mode for standard use at 12 or 24VDC using a suitable interface device and
DA135 Mode when used in conjunction with the DA135 IS Beacon as shown below. To select use DIL switch 6,
ON for Normal Mode and OFF for DA135 Mode
Sound Level
The output sound level shown is Table 2 is for a Sounder powered from a suitable barrier or isolator (listed in
Table 1), fed by 24VDC. To reduce the sound output, by up to 15dB turn the potentiometer in the anti-clockwise
direction.
Connection with the DA135
The DA132 can be connected directly to the DA135 Intrinsically Safe Beacon to create a single point annunciator.
To be used in this Mode the Sounder must be in DA135 Mode by putting DIL switch 6 into the OFF position.
Fig 4
Tone Table
HAZARDOUS AREA SAFE AREA
1-2 3-4 5-6 7-8 9-10 11-12 13-14
+24V DC
SUPPLY
BARRIER OR
IS INTERFACE
UNIT
12-40V FROM
AN IS SYSTEM
++++
+
ACK/RESET
+-
+
-

RTK Instruments Limited
St James Business Park,
Knaresborough, North Yorkshire,
England. HG5 8PJ
Telephone: +44 (0)1423 580500
Facsimile: +44 (0)1423 580501
Web: www.rtkinstruments.com
Email: enquiry
@
rtkinstruments.com
Page 4 of 5
DA-132 Rev 0
Manufacturers of
Alarm Annunciators and Systems | Sequential Event
Recorders | Display Facias | Hazardous Area Interface,
Alarm and Display Products | Signal Conditioning &
Trip Amplifiers | Process Instrumentation
ISO 9001
FM 14290
TONE TONE
TYPE TONE DESCRIPTION/ APPLICATION DIP SWITCH
1_2_3_4_5
2ND
STAGE
TONE
PEAK
SOUND
LEVEL
(dBA @
1m)
1. 970Hz (BS5839-1:2002) O-O-O-O-O 18 95.7
2. 800Hz/970Hz @ 2Hz (BS5839-1:2002) O-O-O-O-I 1 95.5
3. 800Hz – 970Hz @ 1Hz (BS5839-1:2002) O-O-O-I-O 1 96.6
4. 970Hz 1s OFF/1s ON (Apollo Fire Systems Alert Tone,
BS5839-1:2002) O-O-O-I-I 5 95.6
5. 970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate
Tone, BS5839-1:2002) O-O-I-O-O 1 95.5
6. 554Hz, 0.1s/ 440Hz, 0.4s (France – AFNOR NF S 32
001 ) O-O-I-O-I 1 93.2
7. 500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN
2575:2000) O-O-I-I-O 1 95.7
8. 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert
tone) O-O-I-I-I 9 92.9
9. 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia
AS1670 Evacuation tone) O-I-O-O-O 1 94.4
10. 550Hz/440Hz @ 0.5Hz O-I-O-O-I 19 94.4
11. 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low
tone) O-I-O-I-O 1 95.6
12. 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High
tone) O-I-O-I-I 1 92.5
13. 1200Hz – 500Hz @ 1Hz (DIN 33 404) O-I-I-O-O 1 95.5
14. 400Hz O-I-I-O-I 18 91.3
15. 550Hz, 0.7s/1000Hz, 0.33s O-I-I-I-O 1 96.2
16. 1500Hz – 2700Hz @ 3Hz (Vandal Alarm) O-I-I-I-I 1 101.2
17. 750Hz I-O-O-O-O 1 92.9
18. 2400Hz I-O-O-O-I 1 99.8
19. 660Hz I-O-O-I-O 18 92.7
20. 660Hz 1.8s ON/1.8s OFF I-O-O-I-I 19 92.7
21. 660Hz 0.15s ON/0.15s OFF I-O-I-O-O 19 92.3
22. 510Hz, 0.25s/ 610Hz, 0.25s I-O-I-O-I 1 93.4
23. 800/1000Hz 0.5s each (1Hz) I-O-I-I-O 1 94.6
24. 250Hz – 1200Hz @ 12Hz I-O-I-I-I 1 91.8
25. 500Hz – 1200Hz @ 0.33Hz I-I-O-O-O 1 95.7
26. 2400Hz – 2900Hz @ 9Hz I-I-O-O-I 18 94.5
27. 2400Hz – 2900Hz @ 3Hz I-I-O-I-O 18 93.9
28. 800Hz – 970Hz @ 100Hz I-I-O-I-I 1 96.6
29. 800Hz – 970Hz @ 9Hz I-I-I-O-O 1 96.7
30. 800Hz – 970Hz @ 3Hz I-I-I-O-I 1 96.8
31. 800Hz, 0.25s ON/1s OFF I-I-I-I-O 1 94.4
32. 500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220) I-I-I-I-I 8 95.7
Table 2

RTK Instruments Limited
St James Business Park,
Knaresborough, North Yorkshire,
England. HG5 8PJ
Telephone: +44 (0)1423 580500
Facsimile: +44 (0)1423 580501
Web: www.rtkinstruments.com
Email: enquiry
@
rtkinstruments.com
Page 5 of 5
DA-132 Rev 0
Manufacturers of
Alarm Annunciators and Systems | Sequential Event
Recorders | Display Facias | Hazardous Area Interface,
Alarm and Display Products | Signal Conditioning &
Trip Amplifiers | Process Instrumentation
ISO 9001
FM 14290
Maintenance
During the life of the sounder, it should require little or no maintenance. However, if abnormal or unusual
environmental conditions occur or due to plant damage or accident etc, then a visual inspection is recommended.
Faulty Units
If a fault is found faulty units should be returned to RTK for investigation and possible replacement.
EC DECLARATION OF CONFORMITY
This is to certify that the DA132 Intrinsically Safe Sounder
Manufactured by:-
RTK INSTRUMENTS LTD
ST JAMES BUSINESS PARK
KNARESBOROUGH
NORTH YORKSHIRE
HG5 8PJ
Conforms to the protection requirements of the following directives:
•Council directive 89/336/EEC (EMC Directive) to BS EN 61000-6-4 and BS EN
61000-6-2
•Council Directive 94/9/EC (ATEX Directive) to EN60079-0 and EN60079-11
The product is certified to:
II 1G Ex ia IIC T4 (Ta –20
o
C to +55°C)
Certificate Nos:
Baseefa07ATEX0120X
IECEx BAS 07.0026X
The Quality System is certified and monitored by Baseefa Ltd, Rockhead Business Park,
Staden Lane, Buxton, Derbyshire, SK17 9RZ
.............................................................
PAUL HARTLEY - MANAGING DIRECTOR
Date: 12
th
March 2008
Due to our policy of continuous product development, we reserve the right to amend these specifications without notice.
Table of contents
Popular Marine Equipment manuals by other brands

MasterCraft
MasterCraft HV700 owner's manual

Bosch
Bosch FNM-320-SRD installation guide

Raymarine
Raymarine i60 wind Installation & operation instructions

urmet domus
urmet domus 1043 installation manual

Zeta Alarm Limited
Zeta Alarm Limited MKII-AXTB/R installation manual

Webasto
Webasto BlueSky operating instructions