SAJ 8000m Series User manual

8000m Series Compact AC Drive
User Manual
Version Code :8000m-E-602000600-1705

8000mSeries
- 1 -
Preface
First of all, thank you for purchasing 8000m Series Compact AC Drive!
This user manual introduces how to use 8000m series variable frequency drives
(VFDs) properly. Please read this user manual carefully before carrying out works
such as installation, commissioning, maintenance, etc.
Improper usage of VFDs would result in unpredictable accident, please deliver this
user manual to your end user. At the same time, please use VFDs until completely
understands safety instructions.
Attentions:
Illustrations in this user manual are for the convenience of understanding by user,
and it might be a bit different to the product you have purchased. As most of the
illustrations are showing the condition of VFD product with cover or safety guard
removed, please note that cover or safety guard must be installed back as required,
then operate strictly according to this user manual.
SAJ always continually improve the products, all technical parameters are subject to
change without notice. It would be possible that the old version manual is
inconformity to the new products you received. Please always use the user manual
which is included in the same package of product. If the user manual is lost or
incomplete, or there are problems or doubts, please ring the hotline of service center
of SAJ Company on 400-159-0088.

8000mSeries
- 2 -
CONTENTS
Preface ................................................................................................... - 1 -
SAFETY INSTRUCTION ................................................................... - 5 -
Manual Conventions ............................................................................ - 9 -
Chapter 1 Introduction to the 8000m series VFD ........................ - 10 -
1.1 Model Description...................................................................... - 10 -
1.2 Namplate Example ..................................................................... - 10 -
1.3 Model Table................................................................................ - 11 -
1.4 Specifications ............................................................................. - 11 -
1.5 Dimensions and Sizes ................................................................ - 14 -
1.6 Keypad Tray Dimensions........................................................... - 15 -
1.7 RS485 Interface.......................................................................... - 16 -
1.8 Braking Resistor Selection Table ............................................... - 16 -
Chapter 2 Installation and Wiring................................................. - 17 -
2.1 Installation.................................................................................. - 17 -
2.2 Wiring......................................................................................... - 22 -
Chapter 3 Keypad Operation............................................................ - 26 -
3.1 Keypad Operation ...................................................................... - 26 -
3.2 Operation Details ....................................................................... - 27 -
Chapter 4 Function Parameter Table ............................................... - 30 -
4.1 Symbol Conventions: ................................................................. - 30 -
4.2 Function Parameter Table........................................................... - 30 -

8000mSeries
- 3 -
Chapter 5 Function Parameter Description..................................... - 56 -
5.1 F0 Group—Basic Function ........................................................ - 56 -
5.2 F1 Group: Start and Stop Parameters......................................... - 66 -
5.3 F2 Group: Motor Parameters ..................................................... - 70 -
5.4 F3 Group: Vector Control Parameters........................................ - 73 -
5.5 F4 Group: V/F Control Parameters ............................................ - 76 -
5.6 F5 Group Input Terminals Parameters ....................................... - 81 -
5.7 F6 Group Output Terminals Parameters..................................... - 92 -
5.8 F7 Group Display Interface Parameters..................................... - 98 -
5.9 F8 Group Auxiliary Function Parameters ................................ - 101 -
5.10 F9 Group PID Control Parameters......................................... - 108 -
5.11 FA Group Protection Parameters and Fault Records.............. - 115 -
5.12 FB Group Swing Frequency and Counting Meter Parameters- 121 -
5.13 FC Group RS485 Communication Parameters ...................... - 124 -
5.14 FD Group Multi-step Speed and Simple PLC Parameters..... - 127 -
Chapter 6 Trouble Shooting ............................................................ - 130 -
6.1 Fault and Trouble Shooting...................................................... - 130 -
6.2 Common Faults and Solutions ................................................. - 134 -
Chapter 7 EMC ................................................................................ - 135 -
7.1 Definition ................................................................................. - 135 -
7.2 Introduction to EMC Standard ................................................. - 135 -
7.3 EMC Guideline ........................................................................ - 135 -
Chapter 8 Communication Protocol............................................... - 139 -
8.1 Communication Interface......................................................... - 139 -
8.2 Communication Modes ............................................................ - 139 -

8000mSeries
- 4 -
8.3 Frame Format ........................................................................... - 139 -
8.4 Protocol Function ..................................................................... - 141 -
8.5 Note.......................................................................................... - 145 -
8.6 CRC Checksum........................................................................ - 146 -
8.7 Example.................................................................................... - 147 -
8.8 Data Address Table of Function Code...................................... - 149 -

8000mSeries
- 5 -
SAFETY INSTRUCTION
Read this user manual thoroughly before installation, operation, maintenance or
inspection of the variable frequency drive (VFD). In this manual, safety instructions
are classified as “WARNING” or “CAUTION”.
WARNING: Indicate a potentially dangerous situation which, if not avoided,
can result in death or serious injury to personnel.
CAUTION: Indicate a potentially dangerous situation which, if not avoided, can
result in minor or moderate injury and damage to equipment. It may also be used for
warning against unsafe practices.
Even items described as ( CAUTION) may result in a vital accident in some
situations. Please follow these important notes:
■Checking Before installation
◎Do not install or operate any VFD that is damaged or has missing parts. Failing to follow
this rule can result in facility damage or severe injury.
■Installation
◎When installing or handling the VFD, please hold the bottom of the product otherwise its case only,
thus prevent its falling and being damaged.
◎Install the VFD on nonflammable material like metal, and keep away from flammable or
explsive object, heat source, and such environment. Otherwise it may cause a fire.
◎Make sure that the mounting environment free of metal dust. Otherwise it may cause damage
to the VFD.
◎When VFDs is installed inside an electrical cabinet or other kind of enclosure, please install
fans or other cooling devices, and keep ventilation well enough to ensure the enclosure
temperature below 40℃, or the VFD may be damaged due to extreme high rise of temperature.

8000mSeries
- 6 -
■Wiring
◎Ensure only qualified electrical engineering personnel for wiring work . Otherwise it
can cause an electrical shock or damage to the VFD.
◎Make sure VFD is isolated from power supply by the circuit breaker. Otherwise it may
cause electrical shock or a fire.
◎Make sure that the ground terminal is grounded correctly. Otherwise it may cause
an electrical shock.
◎Do not touch the main circuit terminals, and keep the wiring of VFD main terminals
from contacting to the enclosure, or it can cause electrical shock.
◎Terminals for brake resistor are (+) and PB. Do not wire to other terminals, otherwise
will cause a fire.
◎Before wiring, ensure the VFD’s rated input voltage and phases is compatible to the
input power source, or it can cause a fire or personal injury.
◎Never connect the AC power supply to output terminals U, V and W. Otherwise the
VFD will be damaged and the guarantee is voided.
◎Never carry out withstand voltage test to the VFD, for example by a megohm meter.
Otherwise it may cause damage to the VFD.
◎VFD’s main circuit wiring and control circuit wiring should be separated, or run
vertically from each other. Otherwise it may cause interference to the control signals.
◎Main circuit wiring cable leads should be crimped with cable lugs in insulated sleeve.
◎If the cable length between the VFD and the motor is greater than 50 meters, it is
recommended to use an output reactor to protect the VFD and the motor.

8000mSeries
- 7 -
■Operating
◎It is only allowed to power on the VFD after the wirng is finished and its cover is
reinstalled. It is strictly prohibit to remove the cover of VFD while power is on, otherwise
it may cause electric shock.
◎Before programming a VFD with fault auto reset or restart option after power off, the
mechanical device need to be implemented with safety measures first, otherwise it can lead
to personal injury.
◎”STOP/RESET” key may become invalid as a result of some function setting. It is
recommended to install an independent emergency circuit breaker for the VFD control
system, otherwise it may result in personal injury.
◎When the power is on, the VFD’s terminals may have electricity also even if it is in stop
mode. Do not touch U, V, W terminals and motor connection terminals. Otherwise it may
cause an electrical shock.
◎Do not use a magnetic contactor to control the start and stop of the VFD. Otherwise it
may cause the VFD to be damaged.
◎Before starting, please make sure that the motor and mechanical device can be run with
the VFD’s accelerating time setting in their safe range. Otherwise may result in device
damage.
◎Do not touch the heat sink or braking resistor. Otherwise it may cause harmful burns to
the body.
◎Never modify the parameters casually in unnecessary conditions, as the VFD’s default
parameter setting has already meet the requirements of most mechanical devices. Even if
some devices have special requirements, it is only needed to modify some necessary
parameters. Otherwise, it may cause device damage by improper parameter modification.

8000mSeries
- 8 -
■Maintenance
◎Never touch the VFD the connection terminals when power is on. Otherwise it may
cause an electrical shock.
◎Only qualified electrical engineering personnal can be authorized to do the jobs of
maintenance, checking, or parts replacement.
◎After the power supply is OFF, make sure the charge LED is OFF , the residual voltage
is not exist, or wait at least 10 minutes, before carrying out maintenance or inspection.
Otherwise it may cause damage or injury.
◎PCB has CMOS integrated circuit parts, never touch with bare hand, or static electricity
may cause damage to the PCB.
■Other
◎Modification to the VFD without permission is strictly prohibited, otherwise can cause
severe injury. Arbitrarily modification of VFD will result in service guarantee voided.

8000mSeries
- 9 -
Manual Conventions
In this manual we refer to 8000m Series Variable Frequency Drives as: drive,
inverter, VFD, 8000m, 8000m drive, AC drive or 8000m Series Compact AC Drive.

8000mSeries
- 10 -
Chapter 1 Introduction to the 8000m series VFD
1.1 Model Description
1.2 Namplate Example

8000mSeries
- 11 -
1.3 Model Table
1.4 Specifications
Control Characteristics
Control Mode V/F control
Starting Torque 0.5Hz 100%
Speed Control Range 1:20
Precision of Speed
Regulation ±1.0%
Overload Capacities Model G: 60 seconds at 150% rated current; one second at 180%
rated current.
V/F Curve Options Three options: Linear, Square and Multipoint.
DC Injection Braking
Function
Braking start frequency: 0.00~Max. frequency limit;
Braking time:0.1~50.0s;
Braking current:0 ~150% of rated current(model G);
Braking start waiting time:0.0~50.0s.
Jog Operation Jog frequency range: 0.00-max.frequency;
Accel./Decel. time of jog operation:0.1~3600s.
Accel./Decel. Time Accel./Decel. time range:0.1~3600s
Torque Boosting Manual setting:0.1~30.0%; Automatic setting:0.0%
Drive Model Rated Output
Power kW
Rated Input
Current A
Rated Output
Current A
Motor Power
kW
Single-phase 220V±15%
8000m-2SR4GH 0.4 4.5 2.4 0.4
8000m-2SR75GH 0.75 8.2 4.5 0.75
8000m-2S1R5GH 1.5 14.2 7 1.5
8000m-2S2R2GH 2.2 23 10 2.2
Three-phase 380V±15%
8000m-4TR75GH 0.75 3.4 2.5 0.75
8000m-4T1R5GH 1.5 5 3.7 1.5
8000m-4T2R2GH 2.2 5.8 5.0 2.2

8000mSeries
- 12 -
Input & Output Characteristics
Start Frequency 0.01~10Hz
Rated Input Voltage 220V/380V ±15%
Rated Input
Frequency 50/60Hz,fluctuation range:±5%
Frequency Reference
Resolution Analog signals: max. frequency ×0.1%; Digital setting:0.01Hz
Output Voltage 0: rated input voltage
Output Frequency
Range 0.00~600Hz
Peripheral I/O Characteristics
Digital Input
Terminals 4 inputs (programmable)
Analog Input
Terminals AVI: 0~10V or 0/4~20mA (Jumper 10)
Relay Output 1 relay output (programmable)
Open Collector
Output 1 channel (programmable)
Analog Output FM: 0~10V; 0/4~20mA (Jumper 12)
Basic Functions
Operating Command
Channels
Three channels: keyboard, control input terminals, serial
communication interface. These channels can be switched by
several methods.
Frequency
References
7 references including panel potential meter, UP/DOWN key digital
setting, communication and PID control, etc.
Auxiliary Frequency
Reference
1 auxiliary frequency references, can be used in frequency
combination or adjustment.
Multi-step speed &
Simple PLC Function
14 steps multi-step speed control can be carried out by control input
terminals or built-in simple PLC function.
Built-in PID Function
Closed loop control of system variables such as pressure, speed or
temperature can be carried out by a built-in Proportional + Integral
+ Derivative (PID) controller.

8000mSeries
- 13 -
Swing Frequency
Function
Suitable for some textile and chemical fiber machines by
programmable controlling of the triangular frequency references.
AVR Function Automatic Voltage Regulation (AVR), automatically keep the
output voltage constant when power supply is not stable.
Stall Prevention
Stall Prevention automatically control the decelerating procedure
by monitoring the bus voltage and prevent overvoltage fault caused
by high inertia or rapid deceleration.
Communication
Function RS485 communication with standard modbus protocol.
Automatic Energy
Saving Control
Automatic decrease output voltage while in the situation of light
load, to achieve efficient energy saving.
Fault Protection
Function
Over- current , over voltage, under- voltage, over temperature, lack
of phase, etc.
Personalized function
LED Display 16 parameters can by displayed including running frequency, DC
bus voltage, output voltage, output current, etc.
Password Setting Four-digit non-zero password can be set and become effective after
exit the password programming mode and wait 1 minute.
Parameter Lock
Function
This function can be used to lock the parameter when running or
stop in order to avoid wrong operation.
Application Environment
Efficiency
At rated power
≥93% as 45kW and below;
≥95% as 55kW and above。
Location Indoor away from sunlight, dust, corrosive gas, oil fog, driping
water or condensation.
Elevation 1000m or less
Ambient Temperature -10℃~+40℃
Humidity 95% RH or less
Vibration < 5.9 m/s2 (0.6G)

8000mSeries
- 14 -
1.5 Dimensions and Sizes
Dimensions Drawing
Single phase 220V 1.5-2.2kW and 3-phase380V 0.75kW-2.2kW
Single phase 220V 0.4-0.75kW

8000mSeries
- 15 -
1.6 Keypad Tray Dimensions
Voltage
Class Drive Model
Dimensions(mm) Diameter of
installation
hole(mm0
W W1 H H1 D
Single
Phase
220V
8000m-2SR4GH 81.3 67.4 151.3 133 132.8
Φ5
8000m-2SR75GH
8000m-2S1R5GH
99.3 86.8 164.7 147.4 152
8000m-2S2R2GH
Three
Phase
380V
8000m-4TR75GH
8000m-4T1R5GH
8000m-4T2R2GH

8000mSeries
- 16 -
1.7 RS485 Interface
Terminal Symbol Function Specifications
S+ Positive pole of differential signal
Standard
RS485
interface
S- Negative pole of differential signal
+5V Positive pole of extension power (+5V)
GND Negative pole of extension power
1.8 Braking Resistor Selection Table
Inverter Model Recommended Power
of Brake Resistor
Recommended
Resistance Value of
Brake Resistor
Brake Unit
8000m-2SR4GH 50W ≥150Ω
Standard
Accessory Inside
8000m-2SR75GH 80W ≥150Ω
8000m-2S1R5GH 100W ≥100Ω
8000m-2S2R2GH 100W ≥70Ω
8000m-4TR75GH 150W ≥300Ω
8000m-4T1R5GH 150W ≥220Ω
8000m-4T2R2GH 250W ≥200Ω

8000mSeries
- 17 -
Chapter 2 Installation and Wiring
2.1 Installation
2.1.1 Installation Environment
◎The ambient temperature exerts great influences on the service life of the VFDs
and is not allowed to exceed the specified temperature range (-10℃ to 40℃ ).
◎A VFD is easy to generate large amount of heat during operation. Thus VFDs
should be mounted vertically with screws on the surface of incombustible objects,
with sufficient spaces nearby for heat sinking.
◎VFDs should be mounted in the place without vibration or with vibration of less
than 0.6G, especially away from those kinds or machine such as punch.
◎The inverter should be mounted in locations away from direct sunlight, high
humidity, condensate, corrosive gas, explosive gas, oil dirt, dust, and metal powder
etc.
2.1.2Installation Orientation & Clearance
Single Drive & multi drives (Side by Side) Installation

8000mSeries
- 18 -
Multi Drive (up and down) Installation
When take up and down installation, air deflector should be installed between upper
and lower VFD, as illustrated below.

8000mSeries
- 19 -
2.1.4 Electric Elements and Material
Peripheral Electric Elements
Connection Diagram
This manual suits for next models
7
Table of contents
Other SAJ Controllers manuals
Popular Controllers manuals by other brands

Sentera
Sentera MTV-1/010-NA Mounting and operating instructions

Revolution Electronics
Revolution Electronics 12003 Installation instructions manual

GE
GE b30 Communications manual

Malossi
Malossi FORCE MASTER 2.1 Assembly instructions

OBL
OBL Z Series operating manual

GRAUPNER
GRAUPNER PS 5,9V operating manual