
EB 5757 EN 19
Mounting and start-up
5 Mounting and start-up
Risk of malfunction due to incorrectly per-
formed start-up.
Perform start-up following the described
sequence.
5.1 Mounting the actuator onto
the valve
Risk of actuator damage due to excessively
high tightening torques.
Observe the specied tightening torques.
The actuator has a force-locking connection
tothevalveinde-energizedstate.
ÎTurnthehandwheel(2,Fig.1on
page11)counterclockwisetoretract
the actuator stem as far as it will go.
ÎPlace the actuator on the valve con-
nection and tighten the coupling nut
(Fig.1onpage11)(tighteningtorque
20Nm).
5.2 Installing the control valve
into the pipeline
Degree of protection not achieved due to in-
correct mounting position.
Do not install the valve with the actuator
suspended downwards.
ÎInstall the valve into the pipeline accord-
ingthespecicationsinthemounting
and operating instructions of the valve.
5.3 Electrical connections
Risk of electric shock.
−Upon installation of the electric cables, you
are required to observe the regulations
concerning low-voltage installations ac-
cording to DINVDE0100 as well as the
regulations of your local power supplier.
−Use a suitable power supply which guar-
antees that no dangerous voltages reach
the device in normal operation or in the
event of a fault in the system or any other
system parts.
−Connect the actuator to the electrical net-
work only after the power supply is rst
switched off. Make sure the power cannot
be switched on unintentionally.
The actuator requires a fast-response
Pt1000temperaturesensortobeconnected
for it to function.
The binary input can be used to change be-
tween the two set points W1 and W2.
Alternatively,insteadofthePt1000sensor,
thecurrentinput0/4to20mAcanbeused
for control purposes.
Inaddition,awaterowsensororaow
switchcanbeconnectedtoquicklyrecognize
when hot water is being tapped.
Connect the ends of both connecting leads
asshowninFig.5andFig.6.
NOTICE
!
NOTICE
!
NOTICE
!
DANGER
!