Samson 4747 Service manual

Translation of original instructions
EB 4747 EN
Edition January 2019
Type4747 Limit Switch

Note on these mounting and operating instructions
These mounting and operating instructions assist you in mounting and operating the device
safely. The instructions are binding for handling SAMSON devices.
ÎFor the safe and proper use of these instructions, read them carefully and keep them for
later reference.
ÎIf you have any questions about these instructions, contact SAMSON‘s After-sales Service
Department (aftersalesser[email protected]).
The mounting and operating instructions for the devices are included in
the scope of delivery. The latest documentation is available on our website
at www.samson.de > Service & Support > Downloads > Documentation.
Denition of signal words
Hazardous situations which, if not avoided,
will result in death or serious injury
Hazardous situations which, if not avoided,
could result in death or serious injury
Property damage message or malfunction
Additional information
Recommended action
DANGER
!
WARNING
!
NOTICE
!
Note
Tip
2 EB 4747 EN

Contents
EB 4747 EN 3
1 Safety instructions and measures ...................................................................5
1.1 Notes on possible severe personal injury .........................................................7
1.2 Notes on possible personal injury ...................................................................8
1.3 Notes on possible property damage................................................................8
2 Markings on the device .................................................................................9
2.1 Nameplate ....................................................................................................9
2.2 Article code.................................................................................................10
3 Design and principle of operation ................................................................12
3.1 Type4747-xxx01InductiveLimitSwitch.........................................................12
3.2 Type4747-xxx1xElectricLimitSwitch............................................................12
3.3 Accessories .................................................................................................14
3.4 Traveltables ................................................................................................15
3.5 Technical data .............................................................................................16
3.6 Summaryofexplosionprotectionapprovals...................................................18
3.7 Dimensions in mm........................................................................................19
4 Measures for preparation............................................................................20
4.1 Unpacking ..................................................................................................20
4.2 Transporting ................................................................................................20
4.3 Storage.......................................................................................................20
5 Mounting ....................................................................................................20
5.1 Mounting position........................................................................................21
5.2 Leverandpinposition ..................................................................................21
5.3 DirectattachmenttoType3277andType3277-5Actuators............................22
5.4 AttachmentaccordingtoIEC60534-6(NAMURrib) ......................................24
5.5 AttachmenttoType3510Micro-owValve ....................................................26
5.6 AttachmentaccordingtoVDI/VDE3845torotaryactuators ...........................28
5.6.1 Lightversion ................................................................................................28
5.6.2 Heavy-duty version ......................................................................................30

Contents
4 EB 4747 EN
6 Electrical connections...................................................................................32
6.1 ElectricalconnectionfortypeofprotectionExd..............................................32
6.2 ElectricalconnectionfortypeofprotectionExia .............................................33
6.3 EquipmentwithtypeofprotectionExt ...........................................................34
6.4 Equipmentforuseinzone2/22 ...................................................................34
6.5 Cableentry .................................................................................................34
6.6 Switchingamplier ......................................................................................35
7 Operation...................................................................................................36
7.1 Adjusting the switching point ........................................................................36
8 Servicing.....................................................................................................37
8.1 Servicingexplosion-protecteddevices............................................................37
8.2 Preparation for return shipment.....................................................................38
9 Malfunctions ...............................................................................................39
9.1 Emergency action ........................................................................................40
10 Decommissioning and removal ....................................................................40
10.1 Decommissioning.........................................................................................40
10.2 Removingthelimitswitch..............................................................................40
10.3 Disposal......................................................................................................40
11 Appendix....................................................................................................41
11.1 After-sales service........................................................................................41

EB 4747 EN 5
Safety instructions and measures
1 Safety instructions and measures
Intended use
TheSAMSONType4747LimitSwitchissuesanelectricsignalwhenthevalvetravelexceeds
or falls below an adjusted limit. The signal is suitable for switching control signals, issuing
visual and audible alarms or for connection to central control or alarm systems. The device is
designedtooperateunderexactlydenedconditions(e.g.temperature).Therefore,operators
must ensure that the limit switch is only used in applications where the operating conditions
correspond to the technical data. In case operators intend to use the limit switch in other
applicationsorconditionsthanspecied,contactSAMSON.
SAMSON does not assume any liability for damage resulting from the failure to use the de-
viceforitsintendedpurposeorfordamagecausedbyexternalforcesoranyotherexternal
factors.
ÎRefertothetechnicaldataforlimitsandeldsofapplicationaswellaspossibleuses.
Reasonably foreseeable misuse
TheType4747LimitSwitchisnot suitable for the following applications:
−Useoutsidethelimitsdenedduringsizingandbythetechnicaldata
Furthermore, the following activities do not comply with the intended use:
−Useofnon-originalspareparts
−PerformingmaintenanceactivitiesnotspeciedbySAMSON
Qualications of operating personnel
Thelimitswitchmustbemounted,startedupandservicedbyfullytrainedandqualied
personnel only; the accepted industry codes and practices are to be observed. According to
these mounting and operating instructions, trained personnel is referred to as individuals
whoareabletojudgetheworktheyareassignedtoandrecognizepossibledangersdueto
theirspecializedtraining,theirknowledgeandexperienceaswellastheirknowledgeofthe
applicable standards.
Explosion-protectedversionsofthisdevicemustbeoperatedonlybypersonnelwhohasun-
dergonespecialtrainingorinstructionsorwhoisauthorizedtoworkonexplosion-protected
devicesinhazardousareas.

6 EB 4747 EN
Safety instructions and measures
Personal protective equipment
No personal protective equipment is required for the direct handling of the limit switch. Work
on the control valve may be necessary when mounting or removing the device.
ÎObservetherequirementsforpersonalprotectiveequipmentspeciedinthevalvedocu-
mentation.
ÎCheckwiththeplantoperatorfordetailsonfurtherprotectiveequipment.
Revisions and other modications
Revisions,conversionsorothermodicationsoftheproductarenotauthorizedbySAMSON.
Theyareperformedattheuser'sownriskandmayleadtosafetyhazards,forexample.
Furthermore, the product may no longer meet the requirements for its intended use.
Warning against residual hazards
To avoid personal injury or property damage, plant operators and operating personnel must
preventhazardsthatcouldbecausedinthecontrolvalvebytheprocessmedium,the
operating pressure, the signal pressure or by moving parts by taking appropriate
precautions.Theymustobserveallhazardstatements,warningandcautionnotesinthese
mounting and operating instructions, especially for installation, start-up and service work.
If inadmissible motions or forces are produced in the pneumatic actuator as a result of the
supply pressure, it must be restricted using a suitable supply pressure reducing station.
Responsibilities of the operator
The operator is responsible for proper operation and compliance with the safety regulations.
Operators are obliged to provide these mounting and operating instructions to the operating
personnel and to instruct them in proper operation. Furthermore, the operator must ensure
thatoperatingpersonnelorthirdpersonsarenotexposedtoanydanger.
Responsibilities of operating personnel
Operating personnel must read and understand these mounting and operating instructions as
wellasthespeciedhazardstatements,warningandcautionnotes.Furthermore,theoperat-
ing personnel must be familiar with the applicable health, safety and accident prevention
regulations and comply with them.
Referenced standards and regulations
DeviceswithaCEmarkingfullltherequirementsoftheDirectives2014/30/EUand
2014/34/EUforexplosion-protectedapplications.ThisEUdeclarationofconformityisin-
cludedintheAppendixoftheseinstructions.

EB 4747 EN 7
Safety instructions and measures
Referenced documentation
The following documents apply in addition to these mounting and operating instructions:
−The mounting and operating instructions of the components on which the limit switch is
mounted (valve, actuator, valve accessories etc.).
1.1 Notes on possible severe personal injury
DANGER
!
Risk of fatal injury due to the formation of an explosive atmosphere.
Incorrectinstallation,operationormaintenanceofthelimitswitchinpotentiallyexplo-
sive atmospheres may lead to ignition of the atmosphere and cause death, even with a
harmless supply voltage.
ÎFormountingandelectricalinstallationinhazardousareas,observetheexplosion
protection approvals as well as the relevant electrotechnical regulations and the ac-
cidentpreventionregulationsthatapplyinthecountryofuse.EN60079-14applies
in Europe.
ÎDo not connect the supply voltage before mounting is completed.
ÎInstallation, operation or maintenance of the limit switch must only performed by
personnelwithqualicationsaccordingtoClause4.5ofIEC60079-14whohasun-
dergonespecialtrainingorinstructionsorwhoisauthorizedtoworkonexplo-
sion-protecteddevicesinhazardousareas.
ÎDonotopendeviceswithameproofenclosureswhentheelectricalpowersupplyis
connected.
Risk of fatal injury as a result of electrostatic discharge at the device.
An electric spark generated by electrostatic discharge may lead to ignition of a poten-
tiallyexplosiveatmosphereandcausedeath.
ÎInhazardousareas(withtypeofprotectionExt),mountthedeviceinsuchaway
that electrostatic charging cannot take place.

8 EB 4747 EN
Safety instructions and measures
1.2 Notes on possible personal injury
WARNING
!
Crush hazard arising from moving parts on the valve and actuator.
The control valves contain moving parts (actuator and plug stems), which can injure
handsorngersifinsertedintothevalve.
ÎDo not touch any moving valve parts while the control valve is in operation.
ÎWhile performing any mounting or installation on the valve or actuator, disconnect
and lock the pneumatic air supply as well as the control signal.
1.3 Notes on possible property damage
NOTICE
!
An incorrect electrical power supply will damage the limit switch.
TheType4747LimitSwitchisdesignedtooperateunderexactlydenedelectricalcon-
ditions.
ÎOnly connect the limit switch to a suitable power supply after mounting is complet-
ed.
Risk of malfunction due to incorrect mounting parts/accessories or incorrect assign-
ment of lever and pin position.
ÎOnlyusemountingparts/accessorieslistedinthesemountingandoperatinginstruc-
tions to mount the limit switch.
ÎObserve the type of attachment.
ÎObserve the assignment between lever and pin position.

EB 4747 EN 9
Markings on the device
2 Markings on the device
2.1 Nameplate
SAMSON AG D-60314 Frankfurt Made in Germany
Var.-ID Serial no.
Model 4747-
SAMSON 4747
Limit switch, inductive
* See EU Type Examination Certificate for further values
WARNING-POTENTIAL ELECTROSTATIC CHARGING HAZARD*
3
2
4 5
1
6
SAMSON AG D-60314 Frankfurt Made in Germany
Var.-ID Serial no.
Model 4747-
SAMSON 4747
Reed magnetic switch
* See EU Type Examination Certificate for further values
WARNING-POTENTIAL ELECTROSTATIC CHARGING HAZARD*
3
2
4 5
1
1Typeofprotectionforexplosion-protecteddevices
2Temperaturelimitsinthetestcerticatesfortheexplosion-protecteddevices
3 Model no.
4 CongurationID
5 Serial number
6CEmarking

10 EB 4747 EN
Safety instructions and measures
2.2 Article code
Limit Switch Type4747 - x x x x x x x x x x 0xxxxx
Type of protection
Without 000
ATEX II2GExiaIICT6Gb
II2DExtbIIICT85°CDbIP66 110
EAC 1ExiaIICT6/T5/T4Gb
ExtbIIICT85°CDb 113
ATEX II2GExdIICT6/T5/T4
II2DExtDA21IP66T80°C 210
IECEx ExdIICT6,T5,rep.T4
ExtDA21IP66T80°C 211
NEPSI ExdIICT4~T6Gb
DIPA21Ta,T4~T6 212
EAC 1ExdIICT6/T5/T4GbX
ExtbIIICT80°CDbX 213
STCC II2GExdIICT6
II2DExtbIIICT80°C 216
FM AExdIICT6 230
ATEX II3GExnAcIIT6Gc
II3DExtcIIICT85°CDcIP66 810
EAC 2ExnAIICT6/T5/T4Gc
ExtcIIICT85°CDc 813
Limit contact
InductiveproximitysensorNCB2-V3-N0
(–25to+80°C) 0 1
InductiveproximitysensorNBB3-V3-Z5
(–25to+70°C) 1 0
Microswitches with silver contacts
(–40to+80°C) 1 1
Microswitches with gold contacts
(–40to+80°C) 1 2

EB 4747 EN 11
Safety instructions and measures
Limit Switch Type4747 - x x x x x x x x x x 0xxxxx
Number of contacts
11
22
Switching angle
<100°adjustable 0
Electrical connection
M20x1.5 1
½ NPT 2
Degree of protection
IP66 0
Ambient temperature 1)
–25to+80°C(+65°CinT6) 0
–40to+80°C(+65°CinT6) 1
–25to+70°C(+65°CinT6) 2
Material
Aluminum 0
Stainless steel 1
Safety approval
Without 0
SIL 1
Special version
Without 000
1) Themaximumpermissibleambienttemperatureofthelimitswitchdependsonthepermissibleambienttemperature
of the components, type of protection and temperature class.

12 EB 4747 EN
Design and principle of operation
3 Design and principle of oper-
ation
Thelimitswitchisequippedwithamaximum
oftwoinductiveproximityswitchesortwo
electric microswitches. For most applications
the contacts are adjusted to issue a signal
when the actuator has reached one of its
end positions. The switching point can be
adjusted to any position within the opening
angleortravelrangetosignalizeintermedi-
atepositions.Theshaft(4)ofthelimitswitch
is connected to the actuator by a follower
pin.Theshafthasamaximumoftwometal
tags or cam disks (3).
3.1 Type4747-xxx01 Induc-
tive Limit Switch
A NAMUR signal is required to control the
inductive contacts (see section 6.6).
The limit switch has adjustable metal tags (3)
ontheshaft(4).Whenthetag(3)isinside
themagneticeldoftheNAMURproximity
switch,theproximityswitchisattenuated
and the output has a high impedance
(switchingfunction“Contactopen”).When
thetag(3)leavesthemagneticeld,the
NAMURproximityswitchisunattenuated
and the output has a low impedance
(switchingfunction"Contactclosed").The
tag (3) can be adjusted to a switching point
between0and100°attheadjustmentscrew
(2).
3.2 Type4747-xxx1x Electric
Limit Switch
Thelimitswitchhasamaximumoftwoad-
justable metal cam disks (3) on the shaft (1).
The cam disk (3) activates the electric mi-
croswitch over the roller on the switch lever.
The cam disks (3) can be adjusted to a
switchingpointbetween0and100°atthe
adjustment screws (2).
Note

EB 4747 EN 13
Design and principle of operation
2
3
4
1
1 Terminal block
2 Adjustment screw
3Camdiskormetaltag
4Shaft
Fig.1: Type4747 Limit Switch

14 EB 4747 EN
Design and principle of operation
3.3 Accessories
Table1: Cable glands
Order no. Designation
8808-0200 M20x1.5Exdcablegland,madeofbrass,withO-ring,fornon-armoredcable(6.5to14mm
cable diameter)
8808-2010 ½NPTExdcablegland,madeofbrass,withO-ring,fornon-armoredcable(6.5to14mmcable
diameter)
8808-0178 1) M20x1.5Exe cable gland, made of polyamide (black), with O-ring
1890-4875 1) M20x1.5cablegland,madeofbrass,withO-ring
1890-4876 1) M20x1.5cablegland,madeofbrass(blue),withO-ring
8808-1011 1) M20x1.5cablegland,madeofpolyamide(black),withoutO-ring
8808-1012 1) M20x1.5cablegland,madeofpolyamide(blue),withoutO-ring
8421-0067 O-ring18x2
1) The cable gland is notsuitableforExdinstrumentation.
Table2: Mounting kits
Order no. Designation
1400-9974 AttachmentaccordingtoVDI/VDE3845,level2,heavy-dutyversion
1400-7473 AttachmentaccordingtoVDI/VDE3845,level1,lightversion(AA1toAA4size)
1400-9384 AttachmentaccordingtoVDI/VDE3845,level1,heavy-dutyversion(AA1toAA4size)
1400-9992 AttachmentaccordingtoVDI/VDE3845,level1,heavy-dutyversion(AA5size)
1400-9385 AttachmentforVETECS160/R,heavy-dutyversion
1400-7471 MountingkitforType3277LinearActuators(240,350,700cm²)
1400-7472 MountingkitforType3271LinearActuators(120cm²)
1402-1093
1400-7472 Mounting kit for SED diaphragm valves (both mounting kits are required)
1400-7468 MountingkitforcontrolvalveswithNAMURriborattachmenttovalveswithrod-typeyokes
accordingtoIEC60534-6(20to35mmroddiameter)
1402-0479 MountingkitforType3510Micro-owValvewith60or120cm²actuatorarea

EB 4747 EN 15
Design and principle of operation
3.4 Travel tables
The M lever is included in the scope of delivery.
S, L, XL levers for attachment according to IEC60534-6 (NAMUR rib) are available as ac-
cessories in the mounting kits.
Direct attachment to Type3277-5 and Type3277 Actuators
Actuator area Rated travel Required
lever
Assigned pin
position
[cm²] [mm]
120 7.5 M 25
120/175/240/350 15 M 35
355/700/750 30 M 50
Attachment according to IEC60534-6 (NAMUR rib)
SAMSON valves with Type3271
Actuator
Other control
valves
Required
lever
Assigned pin
position
Actuator area Rated travel Max. travel
[cm²] [mm] [mm]
60 and 120 with
Type3510Valve
7.5 17 S 17
120 7.5 25 M 25
120/175/240/350
15 35 M 35
700/750 7.5 35 M 35
355/700/750 15 and 30 50 M 50
1000/1400/2800 30 70 L70
60 100 L100
1400/2800 120 200 XL 200
Attachment according to VDI/VDE3845 to rotary actuators
Opening angle Required le-
ver
Assigned pin posi-
tion
0to100° M90°
Note

16 EB 4747 EN
Design and principle of operation
3.5 Technical data
Type4747-xxx0 Inductive Limit Switch
The technical data for the explosion-protected devices may be restricted by the limits specied in the test
certicates.
ÎRefer to test certicates in the appendix.
Controlcircuit Switchingamplieraccordingto
EN60947-5-6:2000
5to60VDC
(Pmax≤4W)
Inductiveproximitysensor NCB2-V3-NO NBB3-V3-Z5
Switching element NAMURNCcontact NCcontact
Contacts 1 or 2
Permissible ambient temperature –25to+80°C –25to+70°C
Electrical connection M20x1.5or½NPT
Degree of protection IP66
Weight Approx.0.65kg
Type4747-xxx1 Electric Limit Switch · Specications apply to silver and gold-plated contacts
Switching element Electriclimitswitch:changeovercontact/SPDT(single-pole/double-throwtype)
Permissible load ACvoltage DCvoltage
250V/10A 125V/0.5A
24V/10A
Contacts 2
Permissible ambient temperature 1) –40to+80°C
Electrical connection M20x1.5or½NPT
Degree of protection IP66
Weight Approx.0.65kg
Materials
Enclosure and cover Aluminum,powdercoated,graybeigeRAL1019orstainlesssteel1.4409
Externalparts Stainlesssteel1.4301/1.4310/1.4409
Compliance ·

EB 4747 EN 17
Design and principle of operation
Electric data for connection to intrinsically safe current circuits (Exia)
The listed technical data may be restricted by the limits specied in the test certicates.
ÎRefer to test certicates in the appendix.
Limitswitch Type4747-11x01
Limitcontacts Inductive
Output voltage 1) Ui16V 16V
Output current 1) Ii25mA 52mA
Power dissipation 1) Pi64mW 169mW
Outer capacitance 1) Ci100nF
Outer inductance 1) Li100μH
Permissible ambient temperature –25to+80°C –25to+80°C
1) Permissiblemaximumvalueswhenconnectedtoacertiedintrinsicallysafecircuit.

18 EB 4747 EN
Design and principle of operation
3.6 Summary of explosion protection approvals
Type Certication Type of protection/comments
4747-xxx01 SIL Number P+F02/4-13R008 Certicationforsafety-instrumented
systemsaccordingtoIEC61508
Date 2002-12-09
4747-110 ATEX Number PTB12ATEX2020 II2GExiaIICT6Gb
II2DExtbIIICT85°CDbIP66
Date 2013-04-26
4747-113 EAC Number RUC-DE.08.B.00117 1ExiaIICT6/T5/T4Gb
ExtbIIICT85°CDb
Date 2013-11-15
4747-210 ATEX Number PTB09ATEX1113X II2GExdIICT6/T5/T4,
II2DExtDA21IP66T80°C
Date 2009-11-20
4747-211 IECEx Number IECExPTB09.0060X ExdIICT6,T5,rep.T4,
ExtDA21IP66T80°C
Date 2009-11-25
4747-212 NEPSI Number GYJ14.1065X ExdIICT4~T6Gb
DIPA21Ta,T4~T6
Date 2014-02-24
4747-213 EAC Number RUC-DE.08.B.00117 1ExdIICT6/T5/T4GbX
ExtbIIICT85°CDbX
Date 2013-11-15
4747-216 STCC Number ZETC/25/2018 II2GExdIICT6,T5,T4
II2DExtDA21IP66T80°C
Date 2018-04-27
4747-230 FM
Number 3037212 XP/I/1/ABCD/T6
DIP/II,III/EFG/T6
I/1/AExd/IIC/T6Type4X,IP66
Date 2011-03-08
4747-810 ATEX
Number PTB12ATEX2020 II3GExnAcIIT6Gc
II3DExtcIIICT85°CDcIP66
Date 2013-04-26
4747-813 EAC Number RUC-DE.08.B.00117 2ExnAIICT6/T5/T4Gc
ExtcIIICT85°CDc
Date 2013-11-15

EB 4747 EN 19
Design and principle of operation
3.7 Dimensions in mm
94
77
40
99
80
30

20 EB 4747 EN
Measures for preparation
4 Measures for preparation
After receiving the shipment, proceed as fol-
lows:
1. Checkthescopeofdelivery.Compare
the shipment received with the delivery
note.
2. Checktheshipmentfortransportation
damage.Reportanytransportationdam-
age.
4.1 Unpacking
Do not remove the packaging if the limit
switch is to be transported to another loca-
tion or kept in storage.
Beforemountingthelimitswitch,proceedas
follows:
1. Removethepackagingfromthelimit
switch.
2. Dispose of the packaging in accordance
with the valid regulations.
4.2 Transporting
−Protectthelimitswitchagainstexternal
inuences(e.g.impact).
−Protect the limit switch against moisture
and dirt.
−Observe transport temperature depend-
ing on the permissible ambient tempera-
ture(seetechnicaldatainsection3.5).
4.3 Storage
Risk of damage to the limit switch due to im-
proper storage.
Observe storage instructions. Contact
SAMSON, if need be.
Storage instructions
−Protectthelimitswitchagainstexternal
inuences(e.g.impact,shocks,vibra-
tion).
−Do not damage the corrosion protection
(coating).
−Protect the limit switch against moisture
and dirt. In damp spaces, prevent con-
densation. If necessary, use a drying
agent or heating.
−Observe storage temperature depending
on the permissible ambient temperature
(seetechnicaldatainsection3.5).
5 Mounting
The limit switch is suitable for the following
types of attachment:
−Direct attachment to SAMSON
Type3277Actuator
−Attachment to actuators according to
IEC60534-6(NAMURrib)
−AttachmenttoType3510Micro-ow
Valve
−AttachmentaccordingtoVDI/VDE3845
to rotary actuators
Note
NOTICE
!
Other manuals for 4747
1
Table of contents
Other Samson Switch manuals

Samson
Samson 3738-50 Service manual

Samson
Samson 3738-20 Service manual

Samson
Samson EB 3773 Series Service manual

Samson
Samson 4746 Service manual

Samson
Samson 4740 Service manual

Samson
Samson 4747 Service manual

Samson
Samson 3738-50 Instruction sheet

Samson
Samson 3768 Service manual

Samson
Samson 4746 Service manual

Samson
Samson 3776 Service manual
Popular Switch manuals by other brands

Renkforce
Renkforce 2497596 operating instructions

Sigtronics
Sigtronics SRS-M Installation and operating instructions

CTC Union
CTC Union ITP-1204GTM-12PHE Quick installation guide

NETGEAR
NETGEAR ProSAFE JGS516PE installation guide

Dell
Dell PowerConnect PC7024 Technical white paper

Renkforce
Renkforce 2621177 operating instructions