13
Troubleshooting
ΙΙΙ
1 Items to be checked first
1) The input voltage should be voltage rating within ±10% range.
The air conditioner may not operate properly if the voltage is out of this range.
2) Is the connection cable linking the indoor unit and the outdoor unit properly?
The indoor unit and the outdoor unit shall be linked by six cables.
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
Otherwise the air conditioner may not operate properly.
3) When a problem occurs due to the contents illustrated in the table below it is a symptom not related to
the malfunction of the air conditioner.
4) Indoor unit observes operation condition of the air conditioner, and displays self diagnosis details
on the display panel.
No.
Operation of air conditioner
The STD operation indicator, LED blinks when a
power plug of the indoor unit is plugged in at first.
1
It indicates power is on. The LED stops blinking if the
operation On/Off button on the remote control is pushed.
In the Cool mode, the compressor does not operate
at a room temperature higher than the setting
temperature while the indoor fan operates.
In the Heat mode, the compressor does not operate
at a room temperature lower than the setting
temperature that the indoor fan should operate.
2
3
4
5
6
It happens after three minutes when the compressor is
reoperated. The same phenomenon occurs when a power
is on. As a phenomenon that the compressor is reoperated after
three minutes, the indoor fan is adjusted automatically with
reference to a temperature of the air.
The Fan speed is not allowed in the Auto or
Dry mode.
The speed of the indoor fan is set to LL in the Dry mode. The Fan
speed is five steps are selected automatically in the Auto mode.
Compressor stops operating intermittently
in the Dry mode.
Compressor operation is controlled automatically in the Dry
mode depending on the room temperature and humidity.
Compressor of the outdoor unit is operating
although it is turned off in a Heat mode.
When the unit is turned off while de-ice is activated,
the compressor continues operating for up to 9 minutes
(maximum) until the deice is completed.
Only timer LED of the indoor unit lights up and the
air conditioner does not operate.
The Timer is being activated and the unit is in the ready mode.
The unit operates normally if the timer operation is cancelled.
Explanation
No. Display
STD LED blinking (1Hz)
TIMER LED blinking (1Hz)
STD and TIMER LED blinking (1Hz)
NATURE LED blinking (1Hz)
ALL LED blinking (1Hz)
1
2
3
4
5
Restore from power failure (input initial power)
Indoor unit Room sensor Error (open or short)
Indoor unit heat exchanger temperature sensor Error (open or short)
Indoor fan malfunctioning (for speed is below 450rpm)
Option Error
Self Diagnosis
7
8
The compressor and indoor fan stop intermittently
in the Heat mode.
The compressor and indoor fan stop intermittently if room
temperature exceeds a setting temperature in order to protect
the compressor from overheated air in a HEAT mode.
Indoor fan and outdoor fan stop operating
intermittently in the Heat mode.
The compressor operates in a reverse cycle to remove exterior
ice in the Heat mode, and indoor fan and outdoor fan do not
operate intermittently for within 20% of the total heater operation
9
The compressor stops intermittently in the Cool
mode or Dry mode and the fan speed of the indoor
unit decreases.
The compressor stops intermittently or the fan speed of the
indoor unit decreases to prevent inside/outside air from
freezing depending on the inside/outside air temperature.