SANJIANG JTQ-BM-925TE User manual

版本号:301900AB180704
1
Instruction Manual of JTQ-BM-925TE Combustible gas detector
------ Please read this Manual carefully before installing and using the product. -----
1. Product overview
JTQ-BM-925TE, Point type Combustible gas detector, (hereinafter referred to as the detector),which
measurement range is 0~100% LEL, is with a new type thick film metal oxide semiconductor, screen printed
gas sensor, provides accurate and continuous monitoring of combustible gases in household , industrial,
hotels,apartments, etc. It can also access the Sanjiang fire alarm control system.
2.Product Features
With the semiconductor gas sensor and excellent performance of MCU, The detector is stable, long-life
and easy to install.
3.Technical Parameters
3.1 Operating Volt:DC24V,limited voltage range:12~28V
3.2 Operating Current:Monitoring status, ≤35mA @DC24V;Alarm status, ≤40mA @DC24V.
3. 3 Two Bus system:Non polarity two-wire system, current <400µA
3.4 Operating environment: Temperature: 0℃~ 55℃; relative humidity: ≤95%, without condensation.
3.5 Alarm Level: Natural gas 10%LEL(±30%)
3.6 Response timing:≤30 Seconds, reset automatically
3.7 Working life:>5 years(clear air condition)
3.8 Power on(or reset):The indicator blinks twice quickly when power on or reset, then it blinks in the
sequence of green, red, and yellow, along with the warning sound of buzzer.
3.9 The indicator: Warming up status, green indicator blink quickly ( about twice per second);
Monitoring status, green indicator blinks once per around 12 seconds (once per minute when there’s no input
signal of two bus system); Alarm status, red indicator blink quickly (twice per second); Fault status of sensor,
yellow indicator blink once per 3 seconds.
3.10 Buzzer: Alarm status, it sounds twice per second; Fault status,it sounds once per 3 seconds.
3.11 Self-inspection button: Press the button, the indicator blinks in the sequence of green, red, yellow in
circles along with the the warning sound of buzzer.
3.12 Dimensions: Ø104mm x 48 mm. Material of enclosure: ABS ( anti-flaming VO)
3.13 Installation: DZ-925T Base mounted. Surface mount or ceiling mount
3.14 Comply with standards: GB 15322.1-2003
4. Configuration and connection
4.1 Appearance of the detector
2
4.2 Back side of detector
4.3 Connector of base
Note: A. Points of 1 and 3: input of bus wire ( non polarity)
B. Points of 2 and 4: input of DC24V ( non polarity)
5. Installation / Usage instruction
5.1 Wire with the power wire, bus wire, and the base of DZ-925T firstly, after all the decoration work in the
application site is done, ( Note! Don’t make your detectors appealing during the decoration process,
otherwise the sensor will be damaged.), then connect the base with the detector.
Power on the detector, the indicator blinks twice quickly, then it blinks in the sequence of green, red, and
yellow along with the warning sound of buzzer.
Preheating, green indicator blinks quickly; After preheating, green indicator blinks slowly for around 20
seconds, then it comes to monitoring state, green indicator blinks once per around 12 seconds (once per
minute when there’s no connection of two bus system).
5.2 Location of mounted
Decision of location (as shown below) should follow the below instructions, and make a detail analysis
according to the reality of fuel gas and cookware, to decide the location.
5.2.1 Detector should be installed in the same room with stoves or gas fires.
5.2.2 The base of detector shall be between the stove and the source of gas, horizontal distance between 1.5
and 4 meters.
5.2.3 Decide the vertical height according the type of gas
--For LPG.
Detection of petroleum gas should be installed 0.3m from the ground( because of the
gas is heavier than the air)
--Gas detection : should be installed above the stove or any other gas source at vertical distance
Mounted
p
lates
L
abe
l
L1
GND
24V
L2
3
of 0.5m and 0.3m from the ceiling
( because of the gas is lighter than the air)
5.2.4 Diagram of installation location.
5.2.5 Locations to avoid
a Steam, cooking fume, ventilation are present directly.
b Close to air blowing heavily like doors, windows, exhaust fan and air inlet.
c Close to shower room, plenty of steam, and power cut at night likely.
d Explosion Proof place
e Outdoor or where the temperature is below 0℃or above 55℃
f Object separates the detector from the gas appliances.
5.3 Wiring requirements
For 24V power cable, we suggest of wires which cross-sectional area is equal to or more than 2.5mm2, bv
type line;
Bus can be RVs flame-retardant copper core wires which cross-sectional area is more than or equal to 1.0
mm2.
5.4 Once combustible gas in the air reaches the set alarming level, the detector starts alarming, red
indicator flashes and rings a buzzer (twice per second); When the gas concentration is restored lower than the
set alarm, the detector can be reset automatically; Detectors accessing to the alarming system, in about 15
seconds alarms will be informed to the controller.If the detector alarm fails to reset in 30 seconds, please
immediately cut off the gas source, open the window, it is strictly prohibited to turn on or off any electrical
appliances, and ask the qualify people to come to check and solve the leakage.
5.5 If the detector is flashing yellow light and ringing a buzzer(approximately every 3 seconds ),and the
detector can not be returned to the normal monitoring state after the self inspection button is pressed, it
indicates that the detector is faulty (sensor fault).This detector has no longer function of detecting leakage,
please contact the dealer;If the detector is connected to the controller, the detector will report the fault
information to the controller.
5.6 Operation buttons: Being pressed the self inspection button, the detector will be tested by itself (in the
sequence of lighting green, red, yellow, and accompany with a buzzer sound),it will enter to the monitoring
state after the end of the self inspection test.
≥50cm
<30cm
Ceiling
Range hood
Gas stove
Floor
Detector (natural gas)
1.5m<L<4m
Detector (LPG)
4
6. Failure analysis and troubleshooting
Failure Reason analysis Troubleshooting method Remarks
1
Alarm once
powered on.
Detecto
r
is
p
owered fo
r
t
h
e
fi
rst t
i
me o
r
p
owe
r
i
s
cut o
ff
f
o
r
a
l
on
g
t
i
me.
Detecto
r
can
b
erese
t
o
r
p
owere
d
a
g
a
i
na
f
te
r
o
p
erat
i
n
g
f
o
r
aw
hil
e.
2
Detector cannot
be encoded
The addressable
b
ase is
not
p
ro
p
er
ly
connecte
d
to t
h
e DC24V
p
owe
r
su
pply
o
r
two
b
us w
i
re.
Please
p
lu
g
in the addressable
b
ase w
i
t
h
wor
k
a
bl
e5core
pl
u
g
,t
h
en enco
d
e
i
t.
7. Repair and Maintenance
In case of failure, please do not take apart the detector without permission, and notify the company or the
local office, we will serve you as soon as possible.
8. Dos and Dont
8.1 Same address can’t be used twice in the same loop , otherwise the system will be reported code failure.
8.2 This product shall not be stored or used in the environment containing corrosive gases (such as chlorine,
etc.)
8.3 Do not allow the detector to be exposed in the decoration environment, please wait to complete the
decoration of the site , then the detector can be installed.
8.4 Please do not use the non calibrated concentration of the gas to test the product, ultra-high concentration
of gas will affect the lifetime of the detector, also endanger human health.
8.5 Please avoid long time for hard drinking or use heavily perfume, hair gel, moss, pesticides, gasoline,
alcohol, thinner, banana oil, paint and other volatile organic compounds to affect the normal monitoring of
the detector.
8.6 Do not cut off the power supply at will.
8.7 If the detector is out of power for a long time, it needs more than 5 hours to reset to normal application.
8.8 For your safety, please contact the dealer / service provider / manufacturer,it will conduct an inspection
according the specified gas sample and consentration once a year.
9.Special notification
9.1 Please replace it timely when the product of the sensor exceeds the service life (5 years).
9.2 Our company does not undertake any responsibility for the warranty when one of the following
circumstances occurs:
9.2.1 Failure to install or use the product in accordance with the requirements of this specification;
9.2.2 Damage due to excessive power grid voltage or opening the housing without permission;
9.2.3 Damage due to the use under drench, strong external force or in the environment which is not in
conformity with the specification of environmental temperature ,humidity, or high dust;
9.2.4 Any other damages caused by improper use.
Address: 3/F., Guangcai Xintiandi Mansion, Nanshan Road, Nanshan District, Shenzhen, Guangdong, 518054, China
Tel :+86(755)86226969 Fax:+86(755)86223939 Http://www.sanjiang-security.com

Other SANJIANG Gas Detector manuals

SANJIANG F161 User manual

SANJIANG

SANJIANG F161 User manual

SANJIANG JTQ-BF-06TLLoRa User manual

SANJIANG

SANJIANG JTQ-BF-06TLLoRa User manual

SANJIANG F162 User manual

SANJIANG

SANJIANG F162 User manual

Popular Gas Detector manuals by other brands

Silent Call Communications CO5-MCUS Installation and operation manual

Silent Call Communications

Silent Call Communications CO5-MCUS Installation and operation manual

Bosean Electronic Technology BH-90a user manual

Bosean Electronic Technology

Bosean Electronic Technology BH-90a user manual

Critical Environment Technologies CGAS-A installation manual

Critical Environment Technologies

Critical Environment Technologies CGAS-A installation manual

isweek AS8900 manual

isweek

isweek AS8900 manual

Coster RGS 328 instructions

Coster

Coster RGS 328 instructions

TESTO 316-1-EX instruction manual

TESTO

TESTO 316-1-EX instruction manual

BRUEL & KJAER 1306 instruction manual

BRUEL & KJAER

BRUEL & KJAER 1306 instruction manual

Vighnaharta AGDS -32 user manual

Vighnaharta

Vighnaharta AGDS -32 user manual

Co2meter CM-501 operating instructions

Co2meter

Co2meter CM-501 operating instructions

Besantek BST-MG03 user manual

Besantek

Besantek BST-MG03 user manual

RKI Instruments M2A Operator's manual

RKI Instruments

RKI Instruments M2A Operator's manual

BEP Marine 600-GD Installation and operating instructions

BEP Marine

BEP Marine 600-GD Installation and operating instructions

Figaro TGS2611 Application notes

Figaro

Figaro TGS2611 Application notes

Helio MAP 50 operating manual

Helio

Helio MAP 50 operating manual

Madur IRMA manual

Madur

Madur IRMA manual

CPVan CP-WG01W user guide

CPVan

CPVan CP-WG01W user guide

GEV FMG 1275 user manual

GEV

GEV FMG 1275 user manual

Bühler technologies GAS 222.35 AMEX Brief instructions

Bühler technologies

Bühler technologies GAS 222.35 AMEX Brief instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.