18
COMMISSIONING
At the time of commissioning, please ensure all relevant sections of the Benchmark Checklist, (Pages 26 and 27) of this
document are completed.
FILLING THE UNIT WITH WATER
• Check expansion vessel pre-charge pressure. The vessel is supplied precharged to 3.5 bar to match the control pressure
of the pressure reducing valve. The precharge pressure is checked using a car tyre gauge by unscrewing the plastic cap
opposite the water connection.
• Check all connections for tightness including the immersion heater(s). An immersion heater key spanner is supplied for
this purpose.
• Ensure the drain cock is CLOSED.
• Open a hot tap furthest from the PremierPlus SystemFit cylinder.
• Open the PremierPlus SystemFit stop cock to ll the unit. When water ows from the tap, allow to run for a few minutes
to thoroughly ush through any residue, dirt or swarf, then close the tap.
• Open successive hot taps to purge the system of air.
SYSTEM CHECKS
• Check all water connections for leaks and rectify as necessary.
• Turn off PremierPlus SystemFit water supply.
• Remove the pressure reducing valve head work to access the strainer mesh, clean and re-t.
• Manually open, for a few seconds, each relief valve in turn, checking that water is discharged and runs freely through
the tundish and out at the discharge point.
• Ensure that the valve(s) reseat satisfactorily.
INDIRECT (PRIMARY) CIRCUIT
Fill the indirect (primary) circuit following the boiler manufacturer’s commissioning instructions. To ensure the primary
heating system is correctly lled the 2-port motorised valves should be manually opened by moving the lever on the motor
housings to the MANUAL OPEN setting. When the primary circuit is full return the levers to the AUTO position. Vent any
trapped air. Check the primary system for leaks and rectify as necessary. Flush the primary system in accordance with the
boiler manufacturers instructions and add a suitable inhibitor when re-lling.
Switch on the electrical supply to the PremierPlus SystemFit indirect controls and the boiler. Programme the PremierPlus
SystemFit controller as detailed in the tting and user instruction leaet supplied with the controller. Set the controller for
hot water operation only (the +1HR ON Hot Water over-ride button can be used if the time is during a hot water OFF period).
Check that the heating 2-port motorised valve is closed and that the hot water 2-port motorised valve opens. The pump
should run and the boiler re (tap symbol appears in controller display). The primary ow to the PremierPlus SystemFit
should become hot, if it does not, check for a wiring or piping error.
Allow the PremierPlus SystemFit unit to heat up and check that the hot water thermostat and 2-port motorised valve operate
correctly. A storage temperature of approx. 60°C is recommended (see Fig 7, page 16 for adjustment details). If necessary
the temperature can be adjusted by inserting a at bladed screwdriver in the adjustment knob and rotating. The minimum
thermostat setting is 10°C. The adjustment range on the spindle represents a temperature range of 10° to 72°C.
Select the heating only function on the controller. NOTE: The room temperature is set at the controller, no adjustment is
possible at the room sensor unit. Check that the heating 2-port motorised valve opens and that the hot water 2-port motorised
valve is closed. The pump should run and the boiler re (a ame symbol appears in the controller display). The primary ow
to the PremierPlus SystemFit and the radiator circuit should become hot, if it does not check for a wiring or piping error.
If a second CH zone is tted, adjust the programmable room thermostat so that it is calling for heat. Check that the second
CH zone valve opens. The pump should run and the boiler re. The primary ow to the second CH zone should become
hot, if it does not check for a wiring or piping error.
Select the heating and hot water control function on the controller. Check that the heating 2-port motorised valve and the
hot water 2-port motorised valve open.
The minimum thermostatic setting is 10 °C. The maximum thermostatic setting is 72 °C.