COILCLEAN IL INSTALLATION MANUALVersion 08/2017QUESTIONS ON INSTALLATION?CALL SANUVOX AT 1-888-726-8869JIKLA. High-intensity UVC germicidal lampB. Anodized aluminum parabolic reflectorC. Clamp assemblyD. 3/4" support rodE. Mounting flange (2)F.Gaynor lamp plugG. UV lamp bootH. Teflon wire set (20 feet)I.Ballast boxAlso includes:J.CouplerK. Cotton gloves & hardwareL. UV caution decalABCDEFGHSAFETY CONSIDERATIONSSELECTING THE APPROPRIATE LOCATIONInstallation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.Untrained personnel can perform basic maintenance functions such as changing lamps. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit or accessory, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves.Refer to your customized Sanuvox sizing & placement proposal as to where the CoilClean ILs are to be installed. IL's can be installed on the upstream or downstream side of the coil. If you do not have the Sanuvox sizing & placement proposal, call 1-888-726-8869 where Sanuvox will provide one at no-charge.Before installing or performing maintenance or service on the unit, turn off unit and disconnect from power source. Electrical shock can cause injury or death. There may be more than one disconnect switch.________________________________________________________________________________________________________Never expose eyes or skin to ultraviolet light from any source. The unit MUST be DISCONNECTED from power source before performing maintenance or service. Personal injury may result.Do not touch lamp glass without gloves. Reduced performance of lamp may result. Clean lamp after handling.The UV lamp contains a small quantity of mercury. If a lamp breaks, clean and dispose of with care.Use only specified replacement lamps with your unit. Use of an incorrect lamp can result in damage to the unit and/or lamp.
WARNING
IMPORTANT NOTICE
The whole assembly must be field-installed inside the air handling unit, either horizontally to the side panels, or on the coil frame, using field-mounted brackets or vertically, to floor and ceiling of AHU. Make sure that the site can be supplied with the necessary power requirements. Power consumption is 1.0 amp for 40'' lamps, 1.25 amps for 50” lamps and 1.5 amps for 60” lamps. Ensure that there is adequate clearance for service. If a humidifier is present, the ideal location for the germicidal coil cleaner is in the air stream before the humidifier. If space does not permit, the germicidal coil cleaner may be installed after the humidifier. The operating temperature range is 50 to 115 F. Operating outside of this range will result in decreased performance.NOTE: The CoilClean IL is NOT waterproof. If installed outdoors, CoilClean IL fixture and ballast boxes must be installed in a watertight and ventilated enclosure.MAINTENANCECERTIFICATIONS
UNDERSTANDING BALLAST LED DISPLAY & DRY CONTACTS
UV SYSTEM ‘ON’ : The system is functioning normallyUV LAMP TO BE REPLACED : Notifies the user that the lamphas reached the end of its serviceable life (24 months of real-time operation) and must be replacedUV LAMP FAILURE :powered ON with no UV lamp installedFlashes if lamp has failed or the unit is NO POWER (LED OFF) : There is no power being delivered to the system or defective power supplyThe CoilClean IL incorporates unique features into the ballast control box. These include LED status display as well two pairs of dry contacts designed to communicate with building automation systems.LED status displayThe ballast box may have one or two ballasts incorporated into the box depending on how many units were ordered. If only one ballast is incorporated into the ballast box, you will notice only one wire set incorporated into the box and a black button covering where a second LED would be. If the ballast box incorporates two ballasts there will be two LEDs that corresponding to each UV lamp. A reset button is located under the LED (when cover is removed) allowing the user to “Reset” the timer back to zero. To be performed after UV lamp replacement.Dry contacts for building automation integrationEach CoilClean IL system includes a pair of dry contacts (NO & NC). Dry contacts make it possible for the CoilClean ILs to be easily tied to a building automation system. Maximum voltage to be provided to
common is 30VDC.
(Green)(Yellow)(Red)(LED OFF)ResetLEDNO: normally openNC: normally closed CoilClean IL replacement UV lampsLMPHGS120: T6 High-Intensity Germicidal (UVC) 12” Straight UV Lamp for IL12
LMPHGS180: T6 High-Intensity Germicidal (UVC) 18” Straight UV Lamp for IL18
LMPHGS240: T6 High-Intensity Germicidal (UVC) 24” Straight UV Lamp for IL24
LMPHGS300: T6 High-Intensity Germicidal (UVC) 30” Straight UV Lamp for IL30
LMPHGS400: T6 High-Intensity Germicidal (UVC) 40” Straight UV Lamp for IL40
LMPHGS500: T6 High-Intensity Germicidal (UVC) 50” Straight UV Lamp for IL50
LMPHGS600: T6 High-Intensity Germicidal (UVC) 60” Straight UV Lamp for IL60CoilClean IL replacement ballastMulti voltage BST120/277SHS for IL12, IL18, IL24 IL30, IL40, IL50, IL60Others
FLANGE part# MSC9FLANGE ADAPTOR part# MSCCON19LIMIT SWITCH part# MSCSWC14
PART NUMBERSLamp Change-Out: 17,000 hours (2 years) Disconnect all power before performing any maintenance or service. UV lamps need periodic replacement to maintain design specifications. Replace UV lamps after 17,000 hours of operation. Use caution when removing and inserting UV lamps from the metal spring clamps. Then press on the reset button for resetting timer to zero. Use only specified Sanuvox UV lamps with this UV system. Other UV lamps may plug into the connector, but they should not be used. The use of an incorrect lamp can result in damage to the system or UV lamp and void the warranty.NO: normally openNC: normally closedCommon
DRY CONTACTS
UV lamp can be disposed/recycle after use as for any other fluorescent bulb. CoilClean ILs are designed for continous operation. Do not cycle the system through a relay connected to the fan blower.__________________________CSAC22.2 113#Issue: 2015/05/01 Fans and ventilationUL 507 Issued: 1999/12/13 Ed: 9 Rev. 2012/06/18 Electric Fans
Marking : cETLusWARRANTYLamp Warranty: 2 yearsElectronics: 1 yearBallast Warranty: 15 yearsSIGNAL READING
NO NC
Same as
common10V2
0V2Same as
common1
1 or 2 lamps
are OFF
Lamps are
ON
1circuit is opened 2circuit is closed
To mount Refer to “Using the COUPLER to joinmultiple 3/4" support rods” on the bottom of page 3.Coupler tube: In the event that the AHU side panels (that support the fixture) are wider than the included support rod or the installation requires multiple CoilClean ILs, the coupler tube can be inserted between two or more support rods or 3/4 EMT conduit allowing the support rods to be extended to desired lengths. Refer to “using the COUPLER to join multiple 3/4" support rods” on the bottom of page 3.To mount the aluminum reflector to the support rod6.Attach the clamps to the back of the aluminum reflector using the supplied Phillips screws and lock washer.The holes in the parabolic reflector are pre-drilled and pre threaded.7. a) Attach the parabolic reflector to the support rod tightening the clamp securing the assembly in place.b) While wearing the included cotton gloves, carefully “clip” the UV lamp using the metal spring clips into the parabolic reflector.NOTE: For ease of operation, the lamp end with the four pins should be pointing in the direction of the ballast box.Limit switch installation8. To protect users from direct exposure to the ultraviolet rays, use a limit switch. The limit switch will shut down operation to the UVsystem should the access door be opened. A limit switch is available from Sanuvox (part# MSCSWC14).3/4" support rod to the mounting flanges4. Measure and cut the rod to desired lenght. Insert the 3/4" support rod into the two mounting flanges and tighten the two Phillipsscrews on either mounting flange.If using more than one CoilClean IL fixture, multiple support rodsmay be joined together by using the included coupler. 5. The CoilClean IL fixture is to be installed with the UV lamp facing the coil. The mounting flanges attachdirectly to the unit’s side panel, or to the coil frame. NOTE: If it is not possible to attach the flanges directly to the unit’s panels orto the coil frame, a bracket (field-supplied) is required or vertical installation.-
INSTALLATION
Perform the following procedure to assemble the CoilClean IL1. Turn OFF all power to HVAC equipment.2. Remove the CoilClean IL from its packaging. Use care in handling the aluminum reflector/shield, as the lamp is fragile.3. Unpack the ballast box.NOTE: Post can be installed horizontally or vertically. For that later option, more posts are needed and flanges. Descriptionafterward is for horizontal install.The UV lamp end with the four pins should be pointing in the direction of the ballast box.Ballast box installation9. Remove the 4 x Phillips head screws from the ballast box cover. Mount the ballast box on a wallor other hard surface, attached using the 2 holes in the center of the ballast box.Be careful not to damage the wiring.Wiring ballast box to the UV lamp(s)10. Depending on configuration, there may be one or two ballasts incorporated into theballast box (depending on how many units were ordered). The wire harness comeswith 20 feet of Teflon wire set per ballast.11. In order to facilitate running the wire set from the ballast to the UV lamp, the Gaynor plugand lamp boot are made to be installed after the wires have been run. To install: first slide thefour (4) lamp wires through the UV lamp boot and then push each of the four (4) wires into theyellow Gaynor plug. As per the underneath example. Blue wire always in the dark side.12.Carefully secure the white Gaynor plug to the end of the UV lamp. NOTE: The Gaynor plug fits on two of four ways. If theplug does not fit, just rotate the plug 1/4 turn left or right. The UV lamp boot is designed to seal the connection between theplug and the UV lamp as to reduce the possibility of moisture penetrating to the connection. NOTE: The UV lamp boot doesnot cover the entire end- cap (approx. 3/4").Wiring to POWER13. The CoilClean IL is powered by a multi voltage ballast 120/240v.With cover removed, pull the white (neutral) and black (hot) from theround knock-out at the bottom of the ballast box. CONNECT TOPOWER using the included yellow quick connect.Using the COUPLER to join multiple 3/4" support rodsThe coupler tube can be inserted between two or more support rods or 3/4" EMT conduit allowing the support rods to be extended to desired lengths.1.Insert inner tube halfway inside one support rod.2. Using a 1/4" hexagon drill, screw one self tapingscrew. The hole in the support rod is pre-drilled.3. Insert the other half of the inner tube into theother support rod and follow the instructions in step 2.4. The completed assembly with the inner tube coupler joining two support rods.
INSTALLATION - continued
UV LAMP 2UV LAMP 1
CoverRemovedFigure A.
BallastMountedto the wallFigure B.
UV lamp 4 pin endCONNECTIONS TO GAYNOR PLUGOrientation of Gaynor plug is criticalUV lamp bootWire setfrom ballast

Other Sanuvox Ultrasonic Jewelry Cleaner manuals

Sanuvox SABER PRO WIRELESS 24V User manual

Sanuvox

Sanuvox SABER PRO WIRELESS 24V User manual

Sanuvox IL COIL CLEAN User manual

Sanuvox

Sanuvox IL COIL CLEAN User manual

Sanuvox SABER MAGNET 24V User manual

Sanuvox

Sanuvox SABER MAGNET 24V User manual

Popular Ultrasonic Jewelry Cleaner manuals by other brands

HydraMaster TREADMASTER 100-100-001 owner's guide

HydraMaster

HydraMaster TREADMASTER 100-100-001 owner's guide

Carson C6 Series manual

Carson

Carson C6 Series manual

LG VB-9000WH owner's manual

LG

LG VB-9000WH owner's manual

Pattfield Ergo Tools PE-EFR 1410 Translation of the original instructions

Pattfield Ergo Tools

Pattfield Ergo Tools PE-EFR 1410 Translation of the original instructions

Force of Nature FON-BUNDLE-003-B quick start guide

Force of Nature

Force of Nature FON-BUNDLE-003-B quick start guide

Tineco CARPET ONE SPOT Series user manual

Tineco

Tineco CARPET ONE SPOT Series user manual

Sol SOL-ONE user guide

Sol

Sol SOL-ONE user guide

Makita CL107FD instruction manual

Makita

Makita CL107FD instruction manual

Kärcher WV 60 operating instructions

Kärcher

Kärcher WV 60 operating instructions

Ukoke 3800 S/T instruction manual

Ukoke

Ukoke 3800 S/T instruction manual

Milestone HistosMATE Operator's manual

Milestone

Milestone HistosMATE Operator's manual

ECOVACS ROBOTICS WINBOT X instruction manual

ECOVACS ROBOTICS

ECOVACS ROBOTICS WINBOT X instruction manual

Palax Roller user manual

Palax

Palax Roller user manual

Salonserve SEQ343 user manual

Salonserve

Salonserve SEQ343 user manual

Clean + Care TKCUS45-450 quick start guide

Clean + Care

Clean + Care TKCUS45-450 quick start guide

Bissell CROSSWAVE HARD FLOOR EXPERT 3831 Series quick start guide

Bissell

Bissell CROSSWAVE HARD FLOOR EXPERT 3831 Series quick start guide

POSTPROCESS CENTI quick start guide

POSTPROCESS

POSTPROCESS CENTI quick start guide

Polaris P280 Instructions for installation and use

Polaris

Polaris P280 Instructions for installation and use

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.