Satec C191HM User manual

C191HM
Powermeter
and
Harmonic
Manager
Installation
and Operation
Manual
BG0280Rev. A4

C191HM Powermeter &
Harmonic Manager
Installation and Operation
Manual


i
LIMITED WARRANTY
The manufacturer offers the customer an 24-month functional warranty on the
instrument for faulty workmanship or parts from date of dispatch from the
distributor. In all cases, this warranty is valid for 36 months from the date of
production. This warranty is on a return to factory basis.
The manufacturer does not accept liability for any damage caused by instrument
malfunction. The manufacturer accepts no responsibility for the suitability of the
instrument to the application for which it was purchased.
Failure to install, set up or operate the instrument according to the instructions
herein will void the warranty.
Your instrument may be opened only by a duly authorized representative of the
manufacturer. The unit should only be opened in a fully anti-static environment.
Failure to do so may damage the electronic components and will void the
warranty.
NOTE
The greatest care has been taken to manufacture and calibrate your instrument.
However, these instructions do not cover all possible contingencies that may
arise during installation, operation or maintenance, and all details and variations
of this equipment are not covered by these instructions.
For additional information regarding installation, operation or maintenance of this
instrument, contact the manufacturer or your local representative or distributor.
IMPORTANT
Please read the instructions this manual before performing installation,
and take note of the following precautions:
Ensure that all incoming AC power and other power sources are
turned OFF before performing any work on the instrument. Failure to
do so may result in serious or even fatal injury and/or equipment
damage.
Before connecting the instrument to the power source, check the labels on
the side of the instrument to ensure that your instrument is equipped with
the appropriate power supply voltage, input voltages, currents and
communication protocol for your application.
Under no circumstances should the instrument be connected to a
power source if it is damaged.
To prevent potential fire or shock hazard, do not expose the
instrument to rain or moisture.

ii
The secondary of an external current transformer must never be allowed
to be open circuit when the primary is energized. An open circuit can cause
high voltages, possibly resulting in equipment damage, fire and even
serious or fatal injury. Ensure that the current transformer wiring is made
through shorting switches and is secured using an external strain relief to
reduce mechanical strain on the screw terminals, if necessary.
Setup procedures must be performed only by qualified personnel
familiar with the instrument and its associated electrical equipment.
DO NOT open the instrument under any circumstances.
Modbus is a trademark of Modicon, Inc.
Read this manual thoroughly before connecting the meter to the current
carrying circuits. During operation of the meter, hazardous voltages are
present on input terminals. Failure to observe precautions can result in
serious or even fatal injury or damage to equipment.
BG0280 Rev. A4

iii
Table of Contents
Quick Start ........................................................................................ iv
Chapter 1 Introduction.................................................................... 1
1.1 About This Manual.................................................................................. 1
1.2 About The C191HM.................................................................................1
Chapter 2 Installation...................................................................... 7
2.1 Mechanical Installation ..........................................................................7
2.2 Electrical Installation..............................................................................8
Chapter 3 Using The Menus ........................................................... 18
Chapter 4 Setup Menus................................................................... 20
4.1 Basic Setup Menu...................................................................................20
4.2 Communications Port Setup Menu.......................................................22
4.3 Digital Input Setup Menu........................................................................ 23
4.4 Analog Output Setup Menu.................................................................... 24
4.5 Pulsing Output Setup Menu...................................................................26
4.6 Alarm/Event Setpoints Setup Menu ......................................................27
4.7 Relay Operation Control Menu.............................................................. 32
4.8 Display Setup Menu................................................................................33
4.9 User Selectable Options Menu.............................................................. 35
4.10 Access Control Menu............................................................................. 37
4.11 Reset/Synchronization Menu.................................................................38
Chapter 5 Data Display ................................................................... 39
5.1 Navigating in the Display Mode.............................................................39
5.2 Data Display Formats............................................................................. 42
5.3 Self-Test Diagnostics Display................................................................ 46
Chapter 6 Viewing Status Information........................................... 47
6.1 The Status Information Menu ................................................................47
6.2 Status Display Formats.......................................................................... 47
Appendix: Technical Specifications.............................................. 49
Index.................................................................................................. 54

iv
Quick Start
TYPICAL INSTALLATION
Wiring Mode 4LL3 (see Section 2.2.4 for full instructions)
120-
230V AC
RELAYS
LOAD
120-
230VAC
FUSE
10-15A
N
V
11
8
222120 23 24 25
1
N
V
3
2345
120-
230V AC
NN N
33
INPUT
STATUS
2927 28
26 30 31 32
678
12
10
9
SW2
LINE AC
N
5A
L
N
LOAD
KL
ANALOG OUTPUT
V
5
2
V
2
1
+
16
24V
+-
191817
-
N
LINE
LINE
3(C)
2(B)
(PLC)
LOAD
24V
RS-485
+ _
SW1
1A PC
I1
6
3
I7
2
I4
3
RS-232
RS-485
Tx
+
13
xRx
14
-15
1
Powermeter
UP TO 31
DEVICES
Switches
+
_
Shorting
KL
LINE 1(A) KL

v
SETUP (see Chapter 4 for full instructions)
Setups can be performed directly on the front panel
or via PComTest communication software.
Press .
Press to activate middle window.
Press ⇑⇓to scroll to desired option.
Press to activate lower window.
Press ⇑⇓to scroll to desired value.
Press to save selected value.
Basic and Communications Default Setups
Code Parameter Options Description
ConF Wiring mode 4Ln3 4-wire Wye using 3 PTs (3 element), line to
neutral voltage readings
Pt PT ratio 1.0 The phase potential transformer ratio
Ct CT primary current 5 The primary rating of the phase current
transformer, A
d.P Power demand
period 15 The length of the demand period for power
demand calculations, in minutes. E = external
synchronization
n.dp Number of power
demand periods 1 The number of demand periods to be averaged
for sliding window demands
1 = block interval demand calculation
A.dP Ampere/Volt
demand period 900 The length of the demand period for
volt/ampere demand calculations, in seconds
0 = measuring peak current
buF Averaging buffer
size 8 The number of measurements for RMS sliding
averaging
rSt Reset
enable/disable diS Protects all reset functions, both via the front
panel or communications.
Freq Nominal frequency 50/, 60 The nominal power utility frequency, Hz
LoAd Maximum demand
load current 0 The maximum demand load current used in
TDD calculations (0 = CT primary current)
Prot Communications
protocol ASCII
ASCII protocol
Addr Address 0 (ASCII) Powermeter address
bAud Baud rate 9600 9600 bps
dAtA Data format 8n 8 bits, no parity
CPtb ASCII compatibility
mode diS Disables ASCII compatibility mode (For more
information, see ASCII Communications
Protocol Reference Guide)
Port
ASCII
Prot
men
u
option
value
bASc
4L-n
ConF
men
u
option
value
SELECT CH
G
ENTER
SELECT
SELECT
ENTER


Chapter 1 Introduction 1
Chapter 1 Introduction
1.
1.1 About This Manual
This manual is intended for the user of the C191HM Powermeter. This
Powermeter is a microprocessor-based instrument used for the measurement,
monitoring, and management of electrical parameters.
This chapter gives an overview of this manual and an introduction to the
C191HM.
Chapter 2, Installation, provides instructions for mechanical and electrical
installation.
Chapter 3, Using the Menus, presents the structure of menus for setup and
status viewing.
Chapter 4, Setup Menus, provides instructions for performing parameter setup
via the front panel.
Chapter 5, Data Display, guides you through the display pages.
Chapter 6, Viewing Status Information, tells you how to access additional status
information on the instrument. This information may be useful during installation.
Chapter 7 contains Technical Specifications for the C191HM.
1.2 About The C191HM
The C191HM is a compact panel mounted three-phase AC Powermeter and
Harmonic Manager, specially designed to meet the requirements of users
ranging from electrical panel builders to substation operators. The C191HM
provides basic voltage, current, frequency, power, power factor and energy
measurements, plus total harmonic distortion (THD, TDD and K-Factor) and
individual harmonic measurements.
The C191HM is suitable for mounting on 136x136mm square cut-outs.
Features
Harmonic Measurements
• Individual voltage and current harmonics with harmonic angles up to
order 40.
• Harmonic power direction (through PAS software)
• Synthesized voltage and current waveforms (through PAS software)
Display
The front panel features bright LED displays (three windows, up to 45 pages)
with adjustable display update time. Display auto scroll is available on the main

2 Chapter 1 Introduction
screen with a programmable scroll interval of 2 to 15 seconds. Automatic return
to the main screen is available after 30 seconds of uninterrupted use. The front
panel also includes:
• bar graph showing percentage load with respect to user-definable nominal
(100%) load current
• alarm LED providing a local indication when a predefined alarm condition
appears. The alarm LED is shut off manually (by pressing on both up and
down keys more than 5 sec)
• RXD/TXD LEDs showing communications receive/transmit status
Setup is menu driven, with optional password protection. 16 programmable
setups are provided for alarm and control functions (for programmable
parameters, see ‘Measured Parameters’ below).
Communications are available using an RS-232 or RS-485 standard (factory
set), with ASCII/Modbus (and optional DNP3.0) protocols. 120 user assignable
registers are available in ASCII/Modbus protocols.
Eight relays are provided for energy pulsing (KYZ) or alarm and remote control.
Contacts of six relays may switch loads up to 250V, 5A AC and are
recommended for alarm and remote control; contacts of two relays may switch
loads up to 250V, 3A AC and may be used for energy pulsing.
One optically isolated analog output is provided for remote monitoring or
control. Current loop options are 0-20 and 4-20 mA. The analog output must be
used with an external power supply.
Four counters are provided for counting user-defined events or their duration.
These can be used for counting total operation time of generators or overload
time of transformers or power lines. The counters are operated and released by
user-defined triggers.
One digital input can be used as a status input for monitoring external contacts
or as an external synchronization input for power demand interval
synchronization. When no external synchronization pulse is provided, the power
demand interval can be synchronized through communications.
Three user-selectable options are provided:
Power calculation mode
Energy rollover value
This option specifies the point at which the energy value rolls over to zero.
Phase energy calculations mode
This option is used to enable or disable phase energy calculations.

Chapter 1 Introduction 3
Measured Parameters
Note: Real-time values are measured over 1 cycle of fundamental frequency; Average
values are of 8, 16 or 32 real-time values
Parameter Dis- Output
play Com Analog Pulse Alarm
Average Amps, Volts, Frequency $ = setup via PC
#
= setup via panel
Average RMS voltage per phase L-N √√#$ #$
Average RMS voltage per phase L-L √√
Average RMS current per phase √√#$ #$
Average frequency √√#$ #$
Average neutral current √√#$ #$
Voltage & current unbalance √√
Amps & Volt Demand Parameters
Ampere demand per phase √#$
Volt demand per phase √#$
Ampere maximum demand per phase √√
Voltage maximum demand per phase √√
Average Power Values
Average active power per phase √√
Average reactive power per phase √√
Average apparent power per phase √√
Average total active power √√#$ #$
Average total reactive power √√#$ #$
Average total apparent power √√#$ #$
Average power factor per phase √√
Average total power factor √√#$ #$
Power Demand Parameters
Active power accumulated demand √#$ #$
Apparent power accumulated demand √#$ #$
Active power demand √#$
Active power sliding demand √#$
Apparent power demand √#$
Apparent power sliding demand √#$
Active power predicted demand √#$
Apparent power predicted demand √#$
Active power maximum demand √√
Apparent power maximum demand √√
Energy Per Phase
Active energy import per phase √√
Reactive energy import per phase √√
Apparent energy per phase √√
Total Energy
Total active energy import √√#$

4 Chapter 1 Introduction
Parameter Dis- Output
play Com Analog Pulse Alarm
Total active energy export √√#$
Total reactive energy import √√#$
Total reactive energy export √√#$
Total reactive energy net √
Total reactive energy absolute #$
Total apparent energy √√#$
Min/Max Log
Min/Max volts √√
Min/Max amps, neutral current √√
Min/Max frequency √√
Min/Max kW, kvar, kVA, PF √√
Real-time Amps, Volts, Frequency
RT RMS voltage per phase L-N √#$ #$
RT RMS voltage per phase L-L √
RT RMS current per phase √#$ #$
RT frequency √#$ #$
RT neutral current √
Real-time Power Values
RT active power per phase √
RT reactive power per phase √
RT apparent power per phase √
RT total active power √#$
RT total reactive power √#$
RT total apparent power √#$
RT power factor per phase √
RT total power factor √#$
Real-time Harmonic Values
RT voltage THD per phase √#$
RT current THD per phase √#$
RT current TDD per phase √#$
RT K-Factor per phase √#$
Average Harmonic Values
Average Voltage THD per phase √√
Average Current THD per phase √√
Average Current TDD per phase √√
Average K-Factor per phase √√
Fundamental Frequency Values (H01)
Voltage & current per phase √
kW, PF per phase √√
kvar, kVA per phase √
Total kW, PF √√
Total kvar, kVA √

Chapter 1 Introduction 5
Parameter Dis- Output
play Com Analog Pulse Alarm
Individual Harmonic Distortion
Voltage harmonics 1-40 per phase √
Current harmonics 1-40 per phase √
Odd voltage harmonics 3-39 per phase √
Odd current harmonics 3-39 per phase √
High odd voltage harmonics 3-39 triggers #$
High odd current harmonics 3-39 triggers #$
Voltage harmonics angles 1-40 per phase √
Current harmonics angles 1-40 per phase √
Phase Rotation √#$
Counters √√
Status Input √√#$
Relay Status √√
Remote Relay Control √
Alarm Trigger Status √#$
Self-Diagnostic Tests √√
For 4Ln3 and 3Ln3 wiring configurations line to line and line to neutral voltages are
displayed and transmitted via communication simultaneously; analog output and set points
use line to neutral voltages. For other configurations only line to line voltages are used.

6 Chapter 1 Introduction
Instrument Dimensions
Figure 1-1 C191HM Dimensions
8
4
ALARM
RXD
144mm
MAX
MIN
ESC
SELECT
K
5
K
6
KK
7
86mm
144mm
TXD
LOAD%
K
1
K
2
K
K
3
C191HM
Aneutral
c9
9
-10021
/
2
kvar
ENTER
ENERGY
A3
kW
V3
,V3-1
Hz
A2
PF
V2
/V2-3
kVA
V1
,V2-2
A1

Chapter 2 Installation 7
Chapter 2 Installation
2.
2.1 Mechanical Installation
Prepare the panel cut-out, 136 x 136 mm, prior to mounting.
STEP 1: Place the instrument through the cut-out.
STEP 2: Assemble the latches onto the outer wall of the enclosure.
STEP 3: Tighten the screws.
Figure 2-1 Mounting the C191HM
STEP3
STEP2
C191HM
136.0
136.0
+1.0
STEP1
c99-09046/2
+1.0

Chapter 2 Installation
8
2.2 Electrical Installation
Before installation ensure that all incoming power sources are shut
OFF. Failure to observe this practice can result in serious or even fatal
injury and damage to equipment.
2.2.1 Power Supply Connection
The power supply can be dedicated-fused, or from a monitored voltage if it is
within the instrument’s power supply range. Use an external circuit breaker or
switch.
AC power supply: line to terminal 12; neutral to terminal 10.
DC power supply: positive to terminal 12; negative to terminal 10.
2.2.2 Current Inputs
Connect the instrument to the current transformer as shown in Figures 2-2
through 2-8.
2.2.3 Ground
Connect the chassis ground C191HM terminal to the switchgear earth ground
using dedicated wire of greater than 2.5 mm2/13 AWG.
2.2.4 Voltage Inputs
Input of 690V (Standard): Use any of the seven wiring configurations shown in
Figures 2-2 through 2-8.
Input of 120V (Option U): 120V input usually implies use of a potential
transformer (PT). The PT requires use of any of the four wiring configurations
shown in Figures 2-4 through 2-7.

Chapter 2 Installation 9
Wiring Configuration Wiring
(See parameter setup instructions in Section 4.1) Setup Mode Connection
3-wire direct connection using 2 CTs (2-element) 3dir2 Figure 2-2
4-wire WYE direct connection using 3 CTs (3-element) 4Ln3 or 4LL3 Figure 2-3
4-wire WYE connection using 3 PTs, 3 CTs (3-element) 4Ln3 or 4LL3 Figure 2-4
3-wire open delta connection using 2 PTs, 2 CTs (2-element) 3OP2 Figure 2-5
3-wire open delta connection using 2 PTs, 3 CTs (2½-element) 3OP3 Figure 2-6
4-wire WYE connection using 2 PTs, 3 CTs (2½-element) 3Ln3 or3LL3 Figure 2-7
4-wire delta direct connection using 3 CTs (3-element) 4Ln3 or 4LL3 Figure 2-8
11
8
5
2
LINE 1
(C)
(B)
(A)
+
K
1
c99-09042
7
10
12
+
9
4
-
6
+
3
+-
-
-
-
L
K
LOAD
Shorting
Switches
L
LINE 2
LINE 3
Voltages Currents
Figure 2-2
Three Wire Direct
Connection Using 2
CTs (2-element)
Wiring Mode = 3dir2

Chapter 2 Installation
10
c99-09036
LINE 1 (A)
(C)
N
(B)
K
+
-
+
-
+
K
LLOAD
-
L
KL
LINE 2
LINE 3
N
V
3
V
V
2
V
1
Shorting
Switches
Voltages
1
7
10
12
+
9
4
6
+
+
3
-
-
-
Currents
(A)
(C)
N
(B) K
KL
+-+
K
LLOAD
-
L
c99-09037
+
+
+
+
+
+
-
-
-
-
-
-
LINE 3
LINE 2
LINE 1
V
N
V
3
V
2
V
1
11
8
5
2
Shorting
Switches
Voltages
1
7
10
12
+
+
9
4
-
6
+
3
-
-
Currents
Figure 2-3
Four Wire WYE Direct
Connection Using 3
CTs (3-element)
Wiring Mode = 4LL3
or 4Ln3
Figure 2-4
Four Wire WYE
Connection Using 3
PTs, 3 CTs (3-
element)
Wiring Mode = 4LL3
or 4Ln3

Chapter 2 Installation 11
(C)
(B)
(A)
-
-
-
-
+
L
K
+
+
+
+
+
-
K
-
LOAD
L
12
10
11
c99-09038
8
5
2
7
9
6
3
4
1
LINE 3
LINE 2
LINE 1
V
N
V
3
V
2
V
1
I
1
I
3
2
I
Shorting
Switches
Voltages
+
-
+
-
Currents
(A)
(C)
(B) K
KL
+-+
K
LLOAD
-
L
c99-09039
+
+
+
+
-
-
-
-
LINE 3
LINE 2
LINE 1
V
N
V
3
V
2
V
1
11
8
5
2
Shorting
Switches
Voltages
1
7
10
12
+
+
9
4
-
6
+
3
-
-
Currents
Figure 2-5
Three Wire Open
Delta Connection
Using 2 PTs, 2 CTs
(2-element)
Wiring Mode = 3OP2
Figure 2-6
Three Wire Open
Delta Connection
Using 2 PTs, 3 CTs
(2½-element)
Wiring Mode = 3OP3
Table of contents
Other Satec Measuring Instrument manuals

Satec
Satec PM172P User manual

Satec
Satec PM172P User manual

Satec
Satec EM133 User manual

Satec
Satec PM172EH Series User manual

Satec
Satec PRO PM335 Instruction manual

Satec
Satec System 295 User manual

Satec
Satec PM130 PLUS User manual

Satec
Satec PM290 User manual

Satec
Satec expertmeter EM720 User manual

Satec
Satec PM130 series User manual

Satec
Satec PM130P User manual

Satec
Satec PM130P User manual

Satec
Satec PM172 Series User manual

Satec
Satec PM174 Series User manual

Satec
Satec expertmeter EM720 User manual

Satec
Satec PRO EM235 Instruction manual

Satec
Satec PM175 Series User manual

Satec
Satec PM175 Series User manual

Satec
Satec EM132 User manual

Satec
Satec Expertmeter PM180 User manual