Page 2 of 9
GB-500-500HF Installation Guide
When Installing Interceptor Inside
If your dishwashing sink(s)
discharges into a floor
drain/sink (drain), you must
regulate the flow into the
drain to avoid an overflow
of water onto the kitchen
floor. This can be done by
installing a valve or flow
restriction cap on the sink
piping that discharges into
the drain. See drawing
for guidance. For detailed
guidance on indirect connections, go to:
webtools.schierproducts.com/Technical_Data/Indirect_Connections.pdf
Fernco or similar
rubber flow
restriction end cap
SPECIAL PRECAUTIONS
For Schier Grease Interceptor Installations - Failure to follow this guidance voids your warranty
High Water Table Installations
Interceptors and risers are not designed
to withstand water table height in excess
of the top of the unit when buried (see
figure). If it is possible for this to occur,
install the interceptor and risers in a
water-tight concrete vault or backfill with
concrete or flowable fill (wet concrete
and flowable backfill should be poured in
stages to avoid crushing the interceptor).
At risk areas include but are not limited to
tidal surge areas, floodplains and areas
that receive storm water. Great Basin™
models that are direct buried in high
water table scenarios must be installed
with an anchor kit. Models GB-50, GB-75,
and GB-250 use model AK1 anchor kit.
Model GB-500 uses model AK2 anchor kit for use with deadmen anchors.
Fully Support Base of Unit
Install unit on solid, level surface in
contact with the entire footprint of
unit base; for suspended
installations design trapeze to
support the wet weight of the unit.
Do not partially support unit or
suspend unit using metal
U-channel to create a trapeze
Installation Instructions
Installation instructions and additional
components are included with the
interceptor. Read all instructions prior to
installation. This interceptor is intended
to be installed by a licensed plumber in
conformance with all local codes.
Hydrostatic Slabs
(or Pressure Slabs)
When installed under a
hydrostatic slab (slab
designed to withstand
upward lift, usually
caused by hydrostatic
pressure) interceptor
must be enclosed in a
watertight concrete vault.
Support Inlet and Outlet Piping
For above grade installations ensure
heavy inlet and outlet piping (such as
cast iron or long runs) is properly
supported or suspended during the
entire installation process to prevent
connection failure or damage to
bulkhead fittings.
High Temperature Kitchen Water
If water is entering the interceptor at excessive temperature (over
150º F), a drain water tempering valve (DTV) and approved backflow
prevention assembly must be installed. Most state and local plumbing
codes prohibit water above 150º F being discharged into the sanitary
sewer. Water above 150º F will weaken or deform PVC Schedule 40
pipe, poly drainage fixtures like interceptors and erode the coating of
cast iron (leading to eventual failure).
pipe supports
InterceptorInterceptor
concrete slab subject to hydrostatic pressure
watertight
concrete
vault
InterceptorInterceptor
concrete floor
suspended installation
InterceptorInterceptor
max water table height
for direct burial
deadman anchor
nylon strap
turnbuckle
InterceptorInterceptor
Do not install this unit in any manner
except as described in these instructions.
Doing so may result in property damage, personal injury or death.
installation
instructions
AGS2
Above Grade Installation Support
(for Model GB-500 Only)
The wet weight of the interceptor combined
with high temperature kitchen water
creates the potential for tank deformation
when installed above grade. Model GB-500
installed above grade must be installed
with Above Grade Support Kit model AGS2
to maintain structural integrity
DO NOT
COMPACT
BACKFILL
DO NOT AIR TEST UNIT OR RISER SYSTEM!