Fernco or similar
rubber flow
restriction end cap
When Installing Interceptor Inside
If your dishwashing sink(s)
discharges into a floor
drain/sink (drain), you must
regulate the flow into the
drain to avoid an overflow
of water onto the kitchen
floor. This can be done by
installing a valve or flow
restriction cap on the sink
piping that discharges into
the drain. See drawing
for guidance. For detailed
guidance on indirect connections, go to:
webtools.schierproducts.com/Technical_Data/Indirect_Connections.pdf
SPECIAL PRECAUTIONS
For Schier Grease Interceptor Installations - Failure to follow this guidance voids your warranty
Fully Support Base of Unit
Install unit on solid, level surface in
contact with the entire footprint of
unit base; for suspended
installations design trapeze to
support the wet weight of the unit.
Do not partially support unit or
suspend unit using metal
U-channel to create a trapeze
Installation Instructions
Installation instructions and additional
components are included with the
interceptor. Read all instructions prior to
installation. This interceptor is intended
to be installed by a licensed plumber in
conformance with all local codes.
Support Inlet and Outlet Piping
For above grade installations ensure
heavy inlet and outlet piping (such as
cast iron or long runs) is properly
supported or suspended during the
entire installation process to prevent
connection failure or damage to
bulkhead fittings.
High Temperature Kitchen Water
If water is entering the interceptor at excessive temperature (over
140º F), a drain water tempering valve (DTV) and approved backflow
prevention assembly must be installed. Most state and local plumbing
codes prohibit water above 140º F being discharged into the sanitary
sewer. Water above 140º F will weaken or deform PVC Schedule 40
pipe, poly drainage fixtures like interceptors and erode the coating of
cast iron (leading to eventual failure).
pipe supports
Interceptor
Interceptor
Interceptor
Interceptor
concrete floor
suspended installation
Interceptor
Interceptor
Interceptor
Interceptor
cold water supply line
high temperature effluent ( > 140º F)
approved backflow prevention assembly
DTV (drain water tempering valve)
directly connected indirectly connected
Do not install this unit in any manner
except as described in these instructions.
Doing so may result in property damage, personal injury or death.
DO NOT AIR TEST UNIT OR RISER SYSTEM!
Flush-to-Grade Burials
Flush-to-Grade buried installations
(without a riser) are not recommended
for heavy foot traffic areas without the
use of an internal gusset support kit
SGK2 (for GB2) or SGK3 (for GB3).
installation
instructions
inside
Page 2 of 9
GB3-CT Installation Guide