EX-AZ 415
Operating instructions
Safety switch
1
EN
EN Operating instructions...................... pages 1 to 4
Translation of the original operating instructions
FR
Vous trouverez la version
actuelle du mode d’emploi
dans votre langue nationale
ofcielle sur l’Internet,
www.schmersal.net.
ES
Encontrará el manual de
instrucciones actual en su
idioma ocial de la UE en
nuestra página de Internet
www.schmersal.net.
NL
U vindt de huidige versie van
de gebruikshandleiding in
uw ofciële landstaal op het
Internet, www.schmersal.net.
IT
Il manuale d‘istruzioni
aggiornato nella vostra lingua
(lingua ufciale UE) è scarica-
bile in Internet all‘indirizzo
www.schmersal.net.
JP
EU公用語で書かれた最新の
取扱説明書は、インターネッ
(www.schmersal.net)からダウ
ンロードできます。
1 About this document
1.1 Function
This operating instructions manual provides all the information you
need for the mounting, set-up and commissioning to ensure the safe
operation and disassembly of the safety switchgear. The operating
instructions must be available in a legible condition and a complete
version in the vicinity of the device.
1.2 Target group: authorised qualied personnel
All operations described in this operating instructions manual must
be carried out by trained specialist personnel, authorised by the plant
operator only.
Please make sure that you have read and understood these operat-
ing instructions and that you know all applicable legislations regarding
occupational safety and accident prevention prior to installation and
putting the component into operation.
The machine builder must carefully select the harmonised standards to
be complied with as well as other technical specications for the selec-
tion, mounting and integration of the components.
1.3 Explanation of the symbols used
Information, hint, note:
This symbol is used for identifying useful additional information.
Caution: Failure to comply with this warning notice could
lead to failures or malfunctions.
Warning: Failure to comply with this warning notice could
lead to physical injury and/or damage to the machine.
1.4 Appropriate use
The products described in these operating instructions are developed to
execute safety-related functions as part of an entire plant or machine. It
is the responsibility of the manufacturer of a machine or plant to ensure
the proper functionality of the entire machinery or plant.
The safety switchgear must be exclusively used in accordance with the
versions listed below or for the applications authorised by the manufac-
turer. Detailed information regarding the range of applications can be
found in the chapter “Product description”.
1.5 General safety instructions
The user must observe the safety instructions in this operating instruc-
tions manual, the country-specic installation standards as well as all
prevailing safety regulations and accident prevention rules.
Further technical information can be found in the Schmersal
catalogues or in the online catalogue on the Internet:
www.schmersal.net.
The information contained in this operating instructions manual is
provided without liability and is subject to technical modications.
If multiple safety components are wired in series, the Perfor-
mance Level to EN ISO 13849-1 will be reduced due to the
restricted error detection under certain circumstances. The
entire concept of the control system, in which the safety com-
ponent is integrated, must be validated to EN ISO 13849-2.
There are no residual risks, provided that the safety instructions as well
as the instructions regarding mounting, commissioning, operation and
maintenance are observed.
Inhalt
1 About this document
1.1 Function..............................................1
1.2 Target group: authorised qualied personnel..................1
1.3 Explanationofthesymbolsused...........................1
1.4 Appropriateuse........................................1
1.5 General safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.6 Warningaboutmisuse...................................2
1.7 Exclusionofliability.....................................2
2 Product description
2.1 Orderingcode .........................................2
2.2 Specialversions........................................2
2.3 Destinationanduse.....................................2
2.4 Technicaldata.........................................2
2.5 Safety classication .....................................2
3 Mounting
3.1 Generalmountinginstructions.............................2
3.2 Dimensions ...........................................3
4 Electrical connection
4.1 General information for electrical connection. . . . . . . . . . . . . . . . . .3
4.2 Contactvariants........................................3
5 Set-up and maintenance
5.1 Functionaltesting.......................................3
5.2 Maintenance ..........................................3
6 Disassembly and disposal
6.1 Disassembly...........................................3
6.2 Disposal..............................................3
7 Appendix
7.1 ECDeclarationofconformity..............................4
x.000 / v.A. / 12.2009 / BZ-Nr. 50153-23V900 / Teile-Nr. 1187092-EN / Ausgabe E
2
Operating instructions
Safety switch EX-AZ 415
EN
1.6 Warning about misuse
In case of inadequate or improper use or manipulations of the
safety switchgear, personal hazards or damage to machinery
or plant components cannot be excluded. The relevant requi-
rements of the standard EN 1088 must be observed.
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages result-
ing from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary repairs,
conversions and modications to the device are strictly forbidden; the
manufacturer shall accept no liability for damages resulting from such
invasive work, arbitrary repairs, conversions and/or modications to the
device.
2 Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
EX-AZ 415-➀ZPK-➁-3D
No. Option Description
➀
S1 / S2
11/11 1 NO 1 NC / 1 NO 1 NC contact
02/11 2NC / 1NO 1NC contact
02/20 2 NC / 2 NO contacts
02/02 2NC / 2NC contacts
➁
1637 Gold-plated contacts
Only if the information described in this operating instruc-
tions manual are realised correctly, the safety function and
therefore the compliance with the Machinery Directive and
the Explosion Protection Directive is maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specications apply accordingly, provided that they correspond
to the standard version.
2.3 Destination and use
The safety switch has been designed to prevent, in conjunction with the
control part of a machine, movable safety guards from being opened
before hazardous conditions have been eliminated.
The components can be used in explosion-endangered areas of Zone
22 equipment category 3 GD. The installation and maintenance require-
ments to the standard series EN 61241 must be met.
The user must evaluate and design the safety chain in accor-
dance with the relevant standards and the required safety level.
The safety-technical data and features according to the appli-
cable CE test certicate (or possible other approvals) are
mentioned in the technical data.
Conditions for safe operation
Due to their specic impact energy, the components must be tted
with a protection against mechanical stresses. The specic ambient
temperature range must be observed.
2.4 Technical data
Equipment category
L
II 3D
Explosion protection Ex tD A22 IP67 T60°C X
Standards: EN 60947-5-1, EN 61241-0,
EN 61241-1, BG-GS-ET-15
Enclosure: light-alloy diecast, paint nish
Actuator: Zinc-plated brass / aluminium
Max. impact energy: 4 J
Actuating speed: max. 1 m/s
Protection class: IP 67 to EN 60529
Contact material: Silver
Contact types: Change-over contact with double
break, type Zb or 2 NC contacts, with
galvanically separated contact bridges
Switching system:
A
EN 60947-5-1, slow action,
positive break NC contact
Termination: Screw connection
Cable section: min. 0.75 mm2, max. 1.5 mm2,
(including conductor ferrules)
Cable entry: 2 x M20 x 1.5
Uimp:4 kV
Ui: 250 V
Ithe:6 A
Utilisation category: AC-15 / DC-13
Ie/Ue: 4 A / 230 VAC 4 A / 24 VDC
Max. fuse rating: 6 A gG D-fuse
Positive break travel: 3.8 mm
Positive break force min. 31 N
Ambient temperature: – 10 ºC … + 50 °C
Mechanical life: max. 1 million operations
Latching force: 80 - 400 N (adjustable)
Cable cross-section of the
cable glands:
min. Ø 7 mm; max. Ø 12 mm
L
II 2GD
Tightening torque: Covers screws: min. 0.6 Nm
Bottom cover screws: min. 0.7 Nm
Cable gland: min. 8 Nm
Screw plug: min. 8 Nm
2.5 Safety classication
Standards: EN ISO 13849-1
B10d (NC contact): 2,000,000
B10d (NO contact) at 1
0% ohmic contact load:
1,000,000
Service life: 20 years
MTTF
B d x x
hs/h3600
d
10d op op
op
n
0,1 x nop tcycle
(Specications can vary depending on the application-specic parameters
hop, dop and tcycle as well as the load.)
3 Mounting
3.1 General mounting instructions
Fitting is only authorised in a de-energised condition
The mounting holes are accessible after removal of the cover.The use
of a protective ground wire is imperative.The switch enclosure must
not be used as end stop.Any mounting position.The mounting position
however must be chosen so that the ingression of dirt and soiling in the
used opening is avoided.
3
EX-AZ 415
Operating instructions
Safety switch
EN
Please observe the recommendations regarding maximum
impact energy, actuating speed and tightening torque in the
technical data.
Mounting of the actuators: See mounting instructions actuators
Please observe the remarks of the standards
EN ISO 12100, EN 953 and EN 1088.
3.2 Dimensions
All measurements in mm.
10,1 22,3
20
8
M20
8,8
28 A
88
84,6
46,5
103,6
26,8
4 Electrical connection
4.1 General information for electrical connection
The electrical connection may only be carried out
by authorised personnel in a de-energised condition.
The contact labelling can be found in the wiring compartment of the switch.
At least one magnetic contact with positive break
A must be integrated in the safety circuit.
Cable glands (included in delivery) are only authorised for permanent
cables. The constructor must provide for the necessary strain relief. After
wiring, dust and soiling must be removed from the wiring compartment.
The conductors of the connecting cables must not obstruct the move-
ment of the switching lever. Unused openings must be sealed with
EX-certied locking screws (included in delivery).
Note
The distance between the actuator ange and the switch enclosure
must be < 3 mm when the actuator is inserted.
4.2 Contact variants
Contacts shown in de-energised condition and with the actuator
inserted.
S1 1 NO contact / 1 NC contact
S2 1 NO contact / 1 NC contact
S1 2 NC contacts
S2 1 NO contact / 1 NC contact
21
13
21
13
22
14
22
14
S2
S1
21
13
11
21
22
14
12
22
S2
S1
EX-AZ 415-11/11ZPK-3D EX-AZ 415-02/11ZPK-3D
S1 2 NC contacts
S2 2 NO contacts
S1 2 NC contacts
S2 2 NC contacts
13
23
11
21
14
24
12
22
S2
S1
11
21
11
21
12
22
12
22
S2
S1
EX-AZ 415-02/20ZPK-3D EX-AZ 415-02/02ZPK-3D
Legend:
A positive break
P actuated
Q not actuated
5 Set-up and maintenance
5.1 Functional testing
The safety function of the safety components must be tested. The following
conditions must be previously checked and met:
• The installation is executed according to the instructions.
• The connection is executed correctly.
• The cable is correctly executed and connected.
• Check the free movement of the actuating element.
• The safety component is not damaged
• Remove particles of dust and soiling
• Check cable entry and connections in de-energised condition
5.2 Maintenance
In case of correct installation in accordance with the above-described
instructions, the component requires little maintenance. Under rough
operating conditions, a regular check including the following steps is
recommended:
1. Check the corrrect xing of the actuator and the safety switchgear
2. Remove particles of dust and soiling
3. Check cable entry and connections in de-energised condition
Do not open the enclosure in live condition.
Damaged or defective components must be replaced.
For explosion protection reasons, the component must be
exchanged after max. 1 million operations.
6 Disassembly and disposal
6.1 Disassembly
The safety switchgear must be disassembled in a de-energised condi-
tion only.
6.2 Disposal
The safety switchgear must be disposed of in an appropriate manner in
accordance with the national prescriptions and legislations.
4
Operating instructions
Safety switch EX-AZ 415
EN
EX-AZ 415-B-EN
K. A. Schmersal GmbH
Industrielle Sicherheitsschaltsysteme
Möddinghofe 30, D - 42279 Wuppertal
Postfach 24 02 63, D - 42232 Wuppertal
Telefon +49 - (0)2 02 - 64 74 - 0
Telefax +49 - (0)2 02 - 64 74 - 1 00
E-Mail: [email protected]
Internet: http://www.schmersal.com
7 Appendix
7.1 EC Declaration of conformity
Note
The currently valid declaration of conformity can be
downloaded from the internet at www.schmersal.net.
EC Declaration of conformity
Translation of the original declaration of conformity K.A. Schmersal GmbH
Industrielle Sicherheitsschaltsysteme
Möddinghofe 30 ▪ 42279 Wuppertal
Germany
Internet: www.schmersal.com
We hereby certify that the hereafter described products both in their basic design and construction
conform to the applicable European Directives.
Place and date of issue: Wuppertal, January 11, 2010
Authorised signature
Heinz Schmersal
Managing Director
Name of the component / type: EX-AZ 415
L
II 3D
L
Ex tD A22 IP67 T60°C X
Description of the component: Positive break position switch with
separate actuator for safety functions
Harmonised EC-Directives: 2006/42/EC EC-Machinery Directive
94/9/EC EC-Explosion Protection Directive
(ATEX)
Person authorized for the compilation
of the technical documentation:
Ulrich Loss
Möddinghofe 30
42279 Wuppertal

Other schmersal Switch manuals

schmersal AZM300Z-I2-STSD2P User manual

schmersal

schmersal AZM300Z-I2-STSD2P User manual

schmersal ZSD1 User manual

schmersal

schmersal ZSD1 User manual

schmersal EX-TV.S 335 User manual

schmersal

schmersal EX-TV.S 335 User manual

schmersal AZM300B-ST-1P2P-DU User manual

schmersal

schmersal AZM300B-ST-1P2P-DU User manual

schmersal SHGV User manual

schmersal

schmersal SHGV User manual

schmersal AZM300B-ST-1P2P-A-DU User manual

schmersal

schmersal AZM300B-ST-1P2P-A-DU User manual

schmersal AZ 200 AS User manual

schmersal

schmersal AZ 200 AS User manual

schmersal T3Z 068 Series User manual

schmersal

schmersal T3Z 068 Series User manual

schmersal BN 80 Series User manual

schmersal

schmersal BN 80 Series User manual

schmersal MZM 120 User manual

schmersal

schmersal MZM 120 User manual

schmersal TESK-S Series User manual

schmersal

schmersal TESK-S Series User manual

schmersal AZM201Z-SK-T-SD2P-DU Service manual

schmersal

schmersal AZM201Z-SK-T-SD2P-DU Service manual

schmersal TV8S 521 User manual

schmersal

schmersal TV8S 521 User manual

schmersal BN 325-R User manual

schmersal

schmersal BN 325-R User manual

schmersal EX-AZ 16-12ZV(R)K-3D User manual

schmersal

schmersal EX-AZ 16-12ZV(R)K-3D User manual

schmersal ZQ 700-11 User manual

schmersal

schmersal ZQ 700-11 User manual

schmersal AZM300Z-ST-SD2P-T-DU User manual

schmersal

schmersal AZM300Z-ST-SD2P-T-DU User manual

schmersal AZM300B-ST-1P2P User manual

schmersal

schmersal AZM300B-ST-1P2P User manual

schmersal AZM300B-I2-ST-SD2P-A User manual

schmersal

schmersal AZM300B-I2-ST-SD2P-A User manual

schmersal EX-AZ 16 User manual

schmersal

schmersal EX-AZ 16 User manual

schmersal EX-Z 355 Series User manual

schmersal

schmersal EX-Z 355 Series User manual

schmersal TESK Series User manual

schmersal

schmersal TESK Series User manual

schmersal EX-BN 20 series User manual

schmersal

schmersal EX-BN 20 series User manual

schmersal RSS 36-D-ST5 User manual

schmersal

schmersal RSS 36-D-ST5 User manual

Popular Switch manuals by other brands

Kramer VS-21DVI user manual

Kramer

Kramer VS-21DVI user manual

steute Ex T 356 Mounting and wiring instructions

steute

steute Ex T 356 Mounting and wiring instructions

Rose electronics UltraView Installation and operation manual

Rose electronics

Rose electronics UltraView Installation and operation manual

Inline 33271N user manual

Inline

Inline 33271N user manual

Siemens 3LD3.10 Series operating instructions

Siemens

Siemens 3LD3.10 Series operating instructions

Shure AD651B user guide

Shure

Shure AD651B user guide

SWEEX SC016 manual

SWEEX

SWEEX SC016 manual

Interlogix NS3562-8P-2S Quick installation guide

Interlogix

Interlogix NS3562-8P-2S Quick installation guide

ABB FIP2002 Installation instruction

ABB

ABB FIP2002 Installation instruction

Rose electronics Vista KVL-4PCA Installation and operation manual

Rose electronics

Rose electronics Vista KVL-4PCA Installation and operation manual

HP 2530-24 Installation and getting started guide

HP

HP 2530-24 Installation and getting started guide

BLAUBERG SGR-3/1 Operation manual

BLAUBERG

BLAUBERG SGR-3/1 Operation manual

Intermatic FM1D20A installation instructions

Intermatic

Intermatic FM1D20A installation instructions

Fracarro SWP524TS operating instructions

Fracarro

Fracarro SWP524TS operating instructions

H3C S7500 Series installation manual

H3C

H3C S7500 Series installation manual

Rose electronics SuperSwitch SS-9 features and benefits

Rose electronics

Rose electronics SuperSwitch SS-9 features and benefits

ACS KAK Technical manual

ACS

ACS KAK Technical manual

resideo 269SN Installation and setup guide

resideo

resideo 269SN Installation and setup guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.