2
Operating instructions
Position switches EX-Z/T 355
EN
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages resul-
ting from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modifications to the device are strictly forbidden;
the manufacturer shall accept no liability for damages resulting from
such invasive work, arbitrary repairs, conversions and/or modifications
to the device.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
EX-➀➁ 355-➂Z➃-➄-➅-➆-3G/D
No. Option Description
➀
ZSnap action A
T Slow action A
➁
Actuator selection, refer to catalogue
➂
11 1 NO Contact / 1 NC contact
02 2 NC contacts
20 2 NO
01/01 1 NC contact to the left / 1 NC contact to the right
12 1 NO contacts / 2 NC contacts
03 3 NC
➃
H Slow action with staggered contacts
UE Slow action with overlapping contacts
➄
1297 Enclosure with transverse slotted holes
➅
2138 Roller lever 7H for safety applications
➆
1637 Gold-plated contacts
In accordance with the Machinery Directive, the type plate of
safety components is type plate is labelled "safety component".
Only if the information described in this operating instructions
manual are realised correctly, the safety function and therefore
the compliance with the Machinery Directive and the Explosion
Protection Directive is maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specifications apply accordingly, provided that they correspond to
the standard version.
2.3 Destination and use
The position switches are suitable for sliding and hinged guards in
explosive atmospheres of Zone 2 and 22, category 3GD, which need
to be closed in order to provide for the necessary operational safety.
The installation and maintenance requirements to the standard series
EN 60079 must be met.
The user must evaluate and design the safety chain in ac-
cordance with the relevant standards and the required safety
level.
Conditions for safe operation
Due to the specific impact energy, the components must be fitted with a
protection against mechanical stresses. The specific ambient tempera-
ture range must be observed. The user must provide for a protection
against the permanent influence of UV rays.
2.4 Technical data
Equipment category:
L
II 3GD
Ex protection: Ex nC IIC T5 Gc X;
Ex tc IIIC T90°C Dc X
Standards: IEC 60947-5-1; EN 60079-0; EN 60079-15;
EN 60079-31; BG-GS-ET-15
Design: EN 50041
Enclosure: light-alloy diecast, paint finish
Max. impact energy: 1 J
Actuating speed: max. 1 m/s
Protection class: IP67 to IEC 60529
Contact material: Silver
Contact type: change-over with double break Zb,
or 2 NC contacts, galvanically separated contact bridges
Switching system:
A
IEC 60947-5-1, slow or snap action,
positive break NC
Connection: screw terminals
Cable section: min. 0.75 mm², max. 2.5 mm²
(including conductor ferrules)
Cable entry: 3 x M20 x 1.5
Rated impulse withstand voltage Uimp: 6 kV;
-03Z, -12Z: 4 kV
Rated insulation voltage Ui: 500 V;
-03Z, -12Z: 250V
Thermal test current Ithe:10 A
Utilisation category: AC-15 / DC-13
Rated operating current/voltage Ie/Ue:4 A / 230 VAC
4 A / 24 VDC
Max. fuse rating: 6 A gG D-fuse
Ambient temperature:
Mechanical life: 30 million operations
Switching frequency: max. 5000/h
Bounce duration: snap action: in accordance with actuating speed;
slow action: <2 m/s
Switchover time: snap action: <2 m/s;
slow action: in accordance with actuating speed
Cable cross-section: min. Ø 7 mm; max. Ø 12 mm
Cable glands:
L
II 2GD
Tightening torque
- Cover screws: min. 1.0 Nm
- Cable gland: min. 8 Nm
2.5 Safety classification
Standards: ISO 13849-1
B10d (NC contact): 20,000,000
B10d (NO contact)
at 10% ohmic contact load: 1,000,000
Service life: 20 years
TF
d
10d op op
op
n
(Specifications can vary depending on the application-specific parame-
ters hop, dop, tcycle as well as the load.)