Seltron ZCE6 Basic User manual

Zone heating / cooling controller
ZCE6 Basic and ZCE6 Advance
EN Instructions for use and setup

2 English
INTRODUCTION
ZCE6 controllers have been designed for the control of zone heating and/or
cooling. The control is carried out using thermal actuators on the distributor valves
based on the temperatures obtained from room units. There are six independent
temperature zones with the possibility of controlling fourteen heating-cooling
units in total. The ZCE6 Advance controllers also enable the control of the energy
source, mixing valve and circulation pump. The controller allows wired or wireless
connection of room units. The 24V thermal actuators can be used with additional
24V power supply. More controllers can be connected together when more tem-
perature zones or units are needed.

English 3
1-Connection terminals for controller power supply (230V~).
2-Connection terminals for circulation pump, energy source and mixing valve
control. *
3-Connection terminals for the control of 24V~ thermal actuators.**
4-Selector switch for the control voltage of thermal actuators. **
5-LED lights for the signalisation of operation.
6-Connection terminals for the control of thermal actuators.
7-Connection terminals for connecting wired room units.
8-Connection terminals for connecting temperature sensors and digital inputs.
9-Connection terminals for the BUS connection of controllers.
10-Spare electrical fuse.
11-Electrical fuse.
12-Conrmation key .
13-Selection key .
14-Connection terminals for the antenna for wireless room units.
15-AUX connection terminals.
*Only with ZCE6 Advance.
**Connection terminals and the switch are located under a protective cover.
APPEARANCE OF THE CONTROLLER
1
10
2 3 4 5 67 8 9
11 12 13 14 15

4 English
Signalisation of temperature zone operation.
When the LED light is on, the thermal actuators connected to
the zone are in the open state, and vice versa.
SIGNALISATION OF OPERATION
Signalisation of circulation pump output operation. When the
LED light is on, the output is active. *
Signalisation of energy source output operation. When the
LED light is on, the output is active. *
Signalisation of mixing valve output operation. When the LED+
light is on, the mixing valve opens, when the LED- light is on,
the mixing valve closes. *
Signalization of the leading (Master) controller in BUS con-
nection. When the LED light is on, the controller in the BUS
connection is the leading one (Master), and when the LED
light ashes, the controller is the subordinate one (Slave).
Signalisation of pairing process. When the LED light ashes,
the controller is in the pairing phase.
Signalisation of the controller status. When the LED light is on,
the controller is in normal operation, when the LED light is o,
the menu page is displayed.
*Only with ZCE6 Advance.

English 5
MENU
In the menu, we carry out basic settings of the controller. We move from the home
screen to the menu by holding the key for 2 seconds; we move between
individual groups in menu by pressing the key.

6 English
MENU – HYDRAULIC SCHEME
The ZCE6 Advance controller has three hydraulic schemes to choose from, the
ZCE6 Basic only 1 scheme. Hydraulic schemes are shown in chapter »Hydraulic
schemes«.
Example: Shift from scheme 1 to scheme 3.

English 7
MENU – PAIRING OF ROOM UNITS
With the pairing process, we connect the RCD room unit with the controller and at
the same time assign zones to it.
Example: Pairing the RCD room unit with zone 1 and 2.

8 English
MENU – MASTER CONTROLLER
If more controllers are connected to the BUS connection, one controller must be
set as the leading (Master) controller.
Example: Setting the master controller.

English 9
MENU – PAIRING OF THE CONTROLLERS (MASTER CONTROLLER)
When more controllers are interconnected in the BUS connection, the controllers
must be connected – paired.
Example: Activation of the pairing process on the master controller.

10 English
MENU – PAIRING OF CONTROLLERS (SLAVE CONTROLLER)
After activating the pairing process on the master controller, pairing on slave con-
trollers must also be activated.
Example: Activation of the pairing process on the rst slave controller.

English 11
MENU – MANUAL MODE
During start-up or testing of the controller, the zone outputs, circulation pumps,
source or mixing valve can be manually switched on or o.
Example: Manual ON / OFF of the zone 3 output.

12 English
MENU – RESET
There are three types of resets available:
RESET 1 – pairing reset of room units,
RESET 2 – pairing reset of controllers,
RESET 3 – reset of the entire controller to the factory settings.
Example: Activation of reset 3.

English 13
CONTROLLER PARAMETERS
All additional settings and adjustments of the controller operation are carried out
using the parameters. The parameters can be accessed using the room unit, as
described in the instructions for the room unit in the section “SERVICE PANEL
FOR CONTROLLER SETTINGS”.
Pa-
rame-
ter
Function Description Setting
range
Default
value
GENERAL PARAMETERS
C1.1 HYDRAULIC SCHEME Selection of hydraulic scheme or system conguration. The
ZCE6 Basic only has scheme 1 available.
1 ÷ 3
1
C1.2 TYPE OF THERMAL
ACTUATORS
This setting denes whether the thermal actuators are NC
or NO type.
1 - NC
2 - NO 1
C1.4 OPERATION MODE
OF DIGITAL INPUT
“EXTERNAL TIMER”
This setting denes the operation mode of the controller
when a short circuit is detected on the digital input
“External timer”.
0 - NOT IN USE
1 - DAY TEMP.
2 - NIGHT TEMP.
3 - FROST
PROTECTION
TEMP.
4 - TEMP.
DEFINED WITH
PARAMETER.
C1.5
0
C1.5 REQUESTED
TEMPERATURE OF
DIGITAL INPUT “EX-
TERNAL TIMER”
This setting denes what kind of temperature shall
be maintained in case of a short circuit if digital input
“External timer” operation mode is set to value 4 (dened
temperature).
4 ÷ 40 °C
20
C1.6 HEATING / COOLING
OPERATION MODE
This setting denes what kind of mode the controller
should perform.
Value 0: operation mode is dened with auxiliary input
“cooling” (short circuit = cooling mode)
Value 1: Heating mode.
Value 2: Cooling mode.
0 - AUXILIARY
INPUT
1 - HEATING
2 - COOLING 0
C1.7 OPERATION MODE
OF INPUT “DEW
POINT”
This setting denes if the input “dew point” is operated by
NC or NO signal from the digital sensor of the dew point
or an analog sensor is on the input (FCD dew sensor).
0 - NOT IN USE
1 - DIGITAL
INPUT - NC
2 - DIGITAL
INPUT - NO
3 - ANALOGUE
INPUT
3
C1.13 AUTOMATIC SHIFT
OF CLOCK TO SUM-
MER/WINTER TIME
Based on the calendar, the controller automatically shifts
the clock to summer or winter time.
0 - NO
1 - YES 1

14 English
Pa-
rame-
ter
Function Description Setting
range
Default
value
C1.14 ANTI-BLOCK FUNC-
TION
All control outputs that haven’t been activated in the last
week are activated on Friday between 20:00 and 20:15.
Circulation pump runs for 30 seconds, thermal actuators
are activated simultaneously for 5 minutes, mixing valve
is opened and closed.
0 - NO
1 - YES
0
C1.15 OPERATION MODE
OF OUTPUT “10V”
This setting denes the 10V output operation mode.
Value 1: Permanent 10V power supply for digital dew
point sensor.
Value 2: Analogue control signal 0-10V for energy source.
1 - 10V POWER
SUPPLY FOR
SENSOR
2 - 0 ÷ 10V
FOR SOURCE
CONTROL
1
C1.18 SENSOR T1 CALI-
BRATION
Correction of displayed measured temperature for sensor
T1.
-5 ÷ 5°C
0
C1.19 SENSOR T2 CALI-
BRATION
Correction of displayed measured temperature for sensor
T2.
-5 ÷ 5°C
0
C1.20 SENSOR T3 CALI-
BRATION
Correction of displayed measured temperature for sensor
T3.
-5 ÷ 5°C
0
OPERATING MODE PARAMETERS
C2.1 CONTROL ALGO-
RITHM
This setting determines the control algorithm for
temperature zones. When set to “0”, the setting of the
control algorithm on each individual room unit is taken
into account, while by the “1”, “2” and “3” settings, the
control algorithm for all temperature zones is determined
by the setting.
0 - ROOM UNIT
SETTINGS
1 - P MODE
2 - PI MODE
3 - HYSTERESIS
0
C2.2 I-CONSTANT This setting determines the value of the I-constant in PI
mode.
0.2 ÷ 4.0
1.0
C2.3 P ZONE This setting determines the width of the P zone. 0.5 ÷ 2.0°C
1.0
C2.4 SHIFT OF P ZONE –
HEATING
This setting determines the shift of the P zone when the
controller is in heating mode.
0.0 ÷ 1.0°C
0.2
C2.5 SHIFT OF P ZONE –
COOLING
This setting determines the shift of the P zone when the
controller is in cooling mode.
0.0 ÷ 1.0°C
0.2
C2.6 MINIMUM OPER-
ATION TIME OF
OUTPUT (THERMAL
ACTUATOR)
After switching on the thermal actuator, it remains active
for at least the set minimum time.
120 ÷ 300sec
120
CIRCULATION PUMP AND SOURCE PARAMETERS
C3.2 CIRCULATION PUMP
SWITCH-ON DELAY
This setting determines the circulation pump switch-on
delay.
0 ÷ 900sec
0
C3.3 CIRCULATION PUMP
SWITCH-OFF DELAY
This setting determines the circulation pump switch-off
delay when there is no requirement for heating.
0 ÷ 900sec
300

English 15
Pa-
rame-
ter
Function Description Setting
range
Default
value
C3.4 TYPE OF CIRCULA-
TION PUMP OUTPUT
This setting inverts the operation of the circulation pump
output.
1 - NORMAL
2 - INVERTED 1
C3.12 SOURCE SWITCH-
ON DELAY
Setting of source switch-on delay. 0 ÷ 900sec
0
C3.13 SOURCE SWITCH-
OFF DELAY
Setting of source switch-off delay. 0 ÷ 900sec
0
C3.14 TYPE OF SOURCE
OUTPUT
This setting inverts the operation of the source output. 1 - NORMAL
2 - INVERTED 1
MIXING CIRCUIT PARAMETERS
C4.1 HEATING CURVE
STEEPNESS
The heating curve steepness provides information about
the required temperature of heating devices at a certain
outdoor temperature.
0.2 ÷ 2.6
0.5
C4.2 PARALLEL SHIFT OF
HEATING CURVE
This setting determines the parallel shift of the heating
curve or the calculated temperatures of the supply line.
The setting can be used to eliminate the deviation be-
tween the required and actual room temperature.
-5.0 ÷ 5.0°C
0.0
C4.3 INFLUENCE OF
ROOM TEMPERA-
TURE DEVIATION
Setting the inuence of room temperature deviation.
Lower value means lower inuence, higher value means
higher inuence.
0.1 ÷ 3.0
1.0
C4.4 SUPPLY LINE TEM-
PERATURE
This setting determines how the supply line temperature
is determined.
1 - WEATH-
ER-COMPEN-
SATED
2 - CONSTANT
TEMP.
1
C4.5 CONSTANT SUPPLY
LINE TEMPERATURE
– HEATING
This setting determines the constant supply line tempera-
ture for heating when a constant supply line temperature
is selected.
10 ÷ 55 °C
35
C4.6 CONSTANT SUPPLY
LINE TEMPERATURE
– COOLING
This setting determines the constant supply line tempera-
ture for cooling when a constant supply line temperature
is selected.
16 ÷ 40°C
24
C4.10 MAXIMUM SUPPLY
LINE TEMPERATURE
– HEATING
This setting determines the maximum supply line tem-
perature for heating.
20 ÷ 60°C
45
C4.11 MINIMUM SUPPLY
LINE TEMPERATURE
– HEATING
This setting determines the minimum supply line tempera-
ture for heating.
15 ÷ 40°C
20
C4.12 MAXIMUM SUPPLY
LINE TEMPERATURE
– COOLING
This setting determines the maximum supply line tem-
perature for cooling.
20 ÷ 40°C
35
C4.13 MINIMUM SUPPLY
LINE TEMPERATURE
– COOLING
This setting determines the minimum supply line tempera-
ture for cooling.
15 ÷ 30°C
18
C4.14 MIXING VALVE
P-CONSTANT
The setting indicates how intensely the controller corrects
the position of the mixing valve. A lower value means
shorter movements and a higher value longer movements
of the mixing valve.
0.5 ÷ 2.0
1.0

16 English
Pa-
rame-
ter
Function Description Setting
range
Default
value
C4.15 MIXING VALVE
I-CONSTANT
The setting indicates how frequent the controller corrects
the position of the mixing valve. Lower value means low
frequency and higher value means higher frequency of
mixing valve position corrections.
0.5 ÷ 2.0
1.0
C4.16 MIXING VALVE
D-CONSTANT
Setting of the sensitivity of mixing valve for supply line
temperature changes.
0.5 ÷ 2.0
1.0
C4.17 ACTUATOR RUN-
NING TIME
Setting of the actuator running time. 60 ÷ 240sec
120
C4.18 BACKLASH OF
MIXING VALVE
Setting of the mixing valve running time to compensate
the backlash of actuator and mixing valve assembly,
which occurs by change of rotation direction.
1 ÷ 5sec
1
C4.19 INITIAL MIXING
VALVE MOVEMENT
FROM OPEN POSI-
TION
Setting of initial mixing valve movement duration when
moving from open position.
7 ÷ 30sec
15
C4.20 INITIAL MIXING
VALVE MOVEMENT
FROM CLOSED
POSITION
Setting of initial mixing valve movement duration when
moving from closed position.
7 ÷ 30sec
15
BACKUP OPERATION PARAMETERS
C7.1 DELAYED SWITCH-
ING TO BACKUP
OPERATION
This setting determines a time-delayed changeover
to backup operation after the loss of communication
between the room unit and the controller.
0 ÷ 240min
120
C7.2 PERIOD OF BACKUP
OPERATION
This setting determines the period of backup operation. 0 ÷ 240min
60
C7.3 BACKUP OPERA-
TION OF ZONE 1
(PERIOD PERCENT-
AGE)
This setting determines the percentage of zone 1 opera-
tion in a period.
0 ÷ 50%
30
C7.4 BACKUP OPERA-
TION OF ZONE 2
(PERIOD PERCENT-
AGE)
This setting determines the percentage of zone 2 opera-
tion in a period.
0 ÷ 50%
30
C7.5 BACKUP OPERA-
TION OF ZONE 3
(PERIOD PERCENT-
AGE)
This setting determines the percentage of zone 3 opera-
tion in a period.
0 ÷ 50%
30
C7.6 BACKUP OPERA-
TION OF ZONE 4
(PERIOD PERCENT-
AGE)
This setting determines the percentage of zone 4 opera-
tion in a period.
0 ÷ 50%
30

English 17
Pa-
rame-
ter
Function Description Setting
range
Default
value
C7.7 BACKUP OPERA-
TION OF ZONE 5
(PERIOD PERCENT-
AGE)
This setting determines the percentage of zone 5 opera-
tion in a period.
0 ÷ 50%
30
C7.8 BACKUP OPERA-
TION OF ZONE 6
(PERIOD PERCENT-
AGE)
This setting determines the percentage of zone 6 opera-
tion in a period.
0 ÷ 50%
30
INTEGRATION PARAMETERS
C8.1 INFLUENCE OF
ROOM
UNIT ON ZONE 1
Setting of inuence of room unit on the heating zone 1. 0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.2 INFLUENCE OF
ROOM
UNIT ON ZONE 2
Setting of inuence of room unit on the heating zone 2. 0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.3 INFLUENCE OF
ROOM
UNIT ON ZONE 3
Setting of inuence of room unit on the heating zone 3. 0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.4 INFLUENCE OF
ROOM
UNIT ON ZONE 4
Setting of the inuence of room unit on the heating zone
4.
0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.5 INFLUENCE OF
ROOM
UNIT ON ZONE 5
Setting of the inuence of room unit on the heating zone
5.
0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6

18 English
Pa-
rame-
ter
Function Description Setting
range
Default
value
C8.6 INFLUENCE OF
ROOM
UNIT ON ZONE 6
Setting of the inuence of room unit on the heating zone
6.
0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.7 ROOM UNIT ON
WIRE INPUT 1
Setting of room unit to be connected to wire input 1. 0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.8 ROOM UNIT ON
WIRE INPUT 2
Setting of room unit to be connected to wire input 2. 0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.9 ROOM UNIT ON
WIRE INPUT 3
Setting of room unit to be connected to wire input 3. 0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.10 ROOM UNIT ON
WIRE INPUT 4
Setting of room unit to be connected to wire input 4. 0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.11 ROOM UNIT ON
WIRE INPUT 5
Setting of room unit to be connected to wire input 5. 0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6

English 19
Pa-
rame-
ter
Function Description Setting
range
Default
value
C8.12 ROOM UNIT ON
WIRE INPUT 6
Setting of room unit to be connected to wire input 6. 0 - ROOM UNIT 1
1 - ROOM UNIT 2
2 - ROOM UNIT 3
3 - ROOM UNIT 4
4 - ROOM UNIT 5
5 - ROOM UNIT 6
6 - NO INFLU-
ENCE
6
C8.13 ALL PAIRED ROOM
UNITS
The value converted in binary format represents the
addresses of wired and wireless room units, which are
connected (paired) to the controller.
Example:
Value 13 (001101 in binary format) means that the room
units 1, 3 and 4 are paired.
Binary
0 - 000000
1 - 000001
2 - 000010
3 - 000011
…
0
C8.14 WIRELESS (RF)
PAIRED ROOM
UNITS
The value converted in binary format represents the
addresses of wireless room units, which are connected
(paired) to the controller.
Binary
0 - 000000
1 - 000001
2 - 000010
3 - 000011
…
0
C8.15 RF CHANNEL Setting of the RF (frequency) channel through which the
controller communicates with wireless room units.
0 ÷ 7
0
C8.16 CONTROLLER RF
ADDRESS
Setting of the controller RF address for wireless communi-
cation with room units.
0 ÷ 9
0
C8.17 RF ADDRESS
OF PAIRING
Setting of an additional RF address for pairing of wireless
communication with room units.
0 ÷ 255
0
C8.18 PAIRED SUBOR-
DINATE (SLAVE)
CONTROLLERS
The value converted in binary format represents the
addresses of Slave controllers, which are connected
(paired) to the Master controller.
Binary
0 - 000000
1 - 000001
2 - 000010
3 - 000011
…
0
C8.19 LEADING (MASTER)
CONTROLLER
Setting of the controller as the leading (Master) controller
or not.
0 - NO
1 - YES 0
C8.20 SUBORDINATE
(SLAVE) CONTROL-
LER ADDRESS
Setting of the address of subordinate (Slave) controller. 0 - NOT SLAVE
1 - SUBORDI-
NATE 1
2 - SUBORDI-
NATE 2
3 - SUBORDI-
NATE 3
4 - SUBORDI-
NATE 4
5 - SUBORDI-
NATE 5
0

20 English
DESCRIPTION OF SYSTEM OPERATION
Parameter C1.2 is used to select the type of thermal actuators connected to the
controller. Type NC opens the thermal actuator when the output is under control
voltage, type NO opens the thermal actuator when there is no control voltage at
the output.
Parameter C2.1 is used to select between three zone control modes:
C2.1=0 - operation after setting the RCD room unit,
C2.1=1 - P control mode,
C2.1=2 - PI control mode,
C2.1=3 - hysteresis control mode.
Parameter C2.6 is used to set the minimum switch-on time for zone output (ther-
mal actuator).
In P and PI control mode, the operating (modulating) time of zone output is cal-
culated on the basis of deviation of measured temperature from required room
temperature within the ED time constant (period). The length of the ED period is
set on the room unit, for each heating zone separately. With parameter C2.3, the
width of the zone is dened, in which the ED modulation is carried out.
With parameter C2.2, the size of the I-constant in PI mode is dened. In case of
greater deviation of measured temperature from required room temperature, I-con-
stant inuences the speed of the automatic shift of P zone (+/-0.1°C in one step).
Manual shift of the P zone can be carried out by parameter C2.4 for heating and
parameter C2.5 for cooling.
In hysteresis control mode, the condition (ON/OFF) of zone output is dened on
the basis of deviation of measured temperature from the required room tempera-
ture and the value of set hysteresis. The value of the hysteresis is set on the room
unit, for each heating zone separately.
Zone control (thermal actuators)
This manual suits for next models
1
Table of contents
Other Seltron Controllers manuals