SPECIFICATIONS
Power Supply Without Display
With LED Ring or Display
16-30VDC/24VAC(1), 3.5W nominal, 4W max.
16-30 VDC/24VAC(1), 4.3W nominal, 5W max
Interface Color OLED (optional) 1.5”Organic LED Display, 128x128 PX, color
Air Quality Ring Color changing (red/yellow/green) LED ring
Analog Outputs (Analog
version only)
Quantity Up to 3 outputs
Source CO, RH%, Temp, Temp slider, TVOC (selectable)
Scale 0-5V, 0-10V, 4-20mA (switch selectable, programmable per output)
Protocol Output
(Communications version
only)
Protocol BACnet MS/TP or Modbus RTU
Connection 3-wire RS-485, with isolated ground
Data Rate 9600, 19200, 38400, 57600, 76800, 115200 (switch selectable)
Address Range 0-127
Relay Set-point (standard
except for PM models)
Type Solid-state output, 1A @ 30VAC/DC, N.O.
Source CO setpoint, RH setpoint, Temp setpoint, TVOC setpoint, PIR motion, air
quality, o (selectable)
Polarity NO/NC (selectable)
CO (optional)
Type Non-dispersive Infrared (NDIR)
Accuracy
±(30ppm + 3% of reading) (400-2000ppm), -10-50ºC, 0-85%RH
±(50ppm+ 5% of reading) (2000-5000ppm), -10-50ºC, 0-85%RH
>5000ppm consult factory
Resolution 1 ppm
Range 0-2000 PPM (Default) (Programmable up to 10,000 PPM)
Response time 90 seconds to 90% reading
Sample rate 1s
Temp and Pressure Compensated. Barometric pressure also readable over communications
Relative Humidity
(optional)
Type Digital CMOS
Accuracy ±2% over 0 to 80%RH range
Resolution 0.05%RH
Response time (3) 30s
Sample rate 3s
Operating range 0 to 100%RH (non-condensing)
Operating conditions (4) -4 to 140F (-20 to 60° C) @ RH>90%; -4 to 176F @ RH=50%
With RH option Without RH option
Type Silicon Band-gap NTC Thermistor
Temperature Transmitter
(optional)
Nominal Accuracy ±0.3° C (operating range) ±0.5° C (operating range)
Maximum Accuracy ±0.5° C (at 25° C), ±1.0° C ±1.0° C (at 25° C), ±2.0° C
Resolution 0.01° C 0.05° C
Response time 30s 30s
Sample rate 3s 100ms
TVOC (optional)
Type MOS
Gas Total VOC
Range 0-32,000 g/m
Response Time <10s
Output 0-2000 g/m (default) Programmable up to 32,000 g/m
PMx (optional)
CLASS 1 LASER PRODUCT
Type Optical
Size Range PM1.0, PM2.5, PM4.0, PM10.0
Scale 0-1000 g/m
Lower detection limit 0.3 m
Precision ±10 g/m (0-100g/m); ±10% (100-1000 g/m
PIR (optional)
Type Passive Infrared
Axis X eld of view 140, 15 ft (4.5m)
Axis Y eld of view 76, 15 ft (4.5m)
Ambient Light Type Phototransistor
Scale 0-100 fc (lm/ft), readable over communications
Operating Environment Temperature 32 to 122F (0 to 50C)
Humidity 0-95% non-condensing
Enclosure Material ABS Plastic
Dimensions 5.67”h x 3.00”w x 1.07”d
Compliance Agency CE, RoHS
(1) One side of transformer, secondary is connected to signal common. Dedicated transformer is recommended.
(2) Models with PM sensor included achieve ±5% accuracy over 0 to 80%RH range and an additional temperature shift of up +0.5° C
(3) Time for reaching 63% of reading at 25° C and 1 m/s airow
(4) Long term exposures to conditions outside normal range at high humidity may temporarily oset the RH reading (+3%RH after 60 hours.)
Issued7/11/2022 Document #152-0401-0G