Seresco NV Series OMM 8September 2020
Layout and Components
The general layout and components location is the same for all dehumidifiers of current type, however some may
vary, based on the dehumidifier’s specific options –refer to submittal documentation. Pic. D.1 below shows
all/most available options for the NV-080 (BX cab), some of which may not be present on your dehumidifier.
Dehumidifier Main Components
•Main Blower (1) is in the main blower compartment downstream of the min outdoor air opening.
•Main Electric Panel (2) is typically on the supply end. Some models are equipped with multiple main blowers.
•Min Outdoor Air (OA) Opening (4) is optionally equipped with a motorized damper and filter(s). The Manual
OA Damper (5) is usually used to set proper amount of outdoor air intake; in some cases, it could be equipped
with modulating actuator for automatic adjustment of outdoor air intake.
oOutdoor-installed dehumidifier would have louver(s) (76) installed at the OA opening.
•Optional Min Exhaust Fan (EF) Assembly (6) (fan and motorized damper) is located on the dehumidifier’s
return air side; Exhaust Air opening in outdoor-installed dehumidifier is equipped with louver(s) (76) also.
oMin Exhaust Fan Assembly is hinged and could be opened for better access to the fan electric box.
•Dehumidifier, equipped with Heat Recovery (HR) option, would have HR glycol coils (71), installed at the Min
Exhaust (EF) and Min Outdoor Air (OA) openings, and HR pump (72), installed in return air compartment.
oIf HR option is present, Min Exhaust Fan Assembly would normally be equipped with a filter rack.
•If dehumidifier is equipped with Purge option, additional Purge-exhaust fan (PF) (73) with motorized damper
would be installed on dehumidifier’s return air side, as well as additional (“Purge”) Outdoor Air (POA) (74)
opening(s), equipped with motorized dampers, would be located directly upstream of Main Filter Rack (9).
Motorized Return Air (RA) damper (75) would be located between return air side and POA opening(s).
oOutdoor- installed dehumidifier would have louvers (76) installed at the Purge-exhaust fan and Purge
Outdoor Air openings.
•Main Filter Rack (9) is downstream of POA openings to protect downstream hot water or chilled water coils.
•Space Cooling (10b), option that may be present in some models as a chilled water coil, typically located
downstream of the main filter rack.
•Space heater (11a and 11b) location, if the dehumidifier is equipped with one, may vary:
oHot water coil or Electric heater (11a) is usually located downstream of the main filter rack;
oGas heater (11b) is usually located immediately after the main blower(s), however, in some cases it
could be installed externally.
•Main Electric Panel contains Main Control Board (17), Operator Panel (18) and other electrical components.
Disconnect (77), if one is installed, is usually located on the outer wall, opposite to Main Electric Panel.