1-10 Power ON start
If a jumper wire is inserted into the place indicated
JP99 on the indoor control board, and the power
plug is inserted. Cooling mode will be automatically
determined by the room temperature sensor on the
main unit, and operation will begin.
1-11 Compressor relay
(1) It is ON during operation, and when operation is
stopped, goes OFF after a delay of 100 seconds
(not immediately).
Power select Cooling
HAH-S32DP2 8.5 A
L 6.7 A
(2) The minimum OFF time of the relay is 80 seconds.
It will not go ON again before 80 seconds elapses.
(3) If air conditioner operation is turned on again
during the 100 second delay before the
compressor relay goes off, the compressor relay
will stay on.
1-12 Power selector [AH-S32DP2]
Operation power "H " (High) or "L" (Low) can be
selected by switching the POWER SELECTOR
slide switch located above the AUX. button.
1-13 Auto Restart
When power failure occures, after power is
recovered, the unit will automatically restart in the
same setting which were active before the power
failure.
Operating mode (Cool, Dry)
Temperature adjustment (within 2˚C range)
automatic operation
Temperature setting
Fan setting
Air flow direction
Power ON/OFF
Automatic operation mode setting
Swing louver
Setting not memorized
Timer setting
Full power setting
1-14 Indoor/outdoor temperature display
Every time the Temperature check button is
pressed on the remote control, the display changes
in the order of indoor temperature outdoor
temperature no display. The temperature is
displayed on the temperature indicator on the main
unit to be referred to for energy saving.
(When the unit is not running, the display changes
between indoor temperature and no display.)Indoor
temperature is the temperature of the suction air
measured by the room thermistor, and outdoor
temperature is that measured by the outdoor
temperature thermistor. When indoor temperature
is displayed, the indoor LED on the main unit is lit,
and when outdoor temperature is displayed, the
outdoor LED is lit. For 90 seconds after the
operation starts, - - is displayed instead of the
actual outdoor temperature since it is still being
measured.Because of the effect of the exchanger,
the unit cannot confirm the exact indoor
temperature right after the operation is terminated.
Therefore, for one hour since the operation is
stopped, the indoor temperature immediately before
the operation is stopped is displayed. After over
one hour since it is stopped, the unit displays the
actual room temperature at that point.
1-15 Error diagnostic display
(a) Indoor unit
(1) When an error is detected, all relays are
turned off. At the same time, the details of the
error are displayed by flashing the number
corresponding to the type of the error. The
details can also be displayed by pressing down
the emergency operation switch for 5 seconds
or more in the state of operation stop.However,
if the operation is continued only in the serial
open state and the state remains unchanged
after that, the main relay is turned off in 8
minutes. In the serial short state, the error is
not displayed and the operation is continued. If
the unit stays in the same state, the main relay
is turned off in 8 minutes. Although the error is
not displayed, it is memorized and can be
displayed when it is recalled.
(2) If the operation is stopped and the emergency
operation button is pressed down for 5 seconds
or more, the self-diagnosis memory can be
recalled.
(3) Details of self-diagnosis (error mode) are
informed by the flashing number as well as the
lighting pattern of the operation lamp which
flashes with the timer lamp.(For details, refer to
Error diagnostic method.)