7. Current control
This system, in order to prevent overcurrent during
heating operation, controls the outdoor fan motor and
changes the indoor fan motor speed by detecting total
current.
WhenthecurrentexceedsP2,theoutdoorfanmotoris
automatically turned off, and when the current falls
below P4, the outdoor fan motor is turned on.
WhenthecurrentexceedsP3andtheindoorfanspeed
shiftsdownbecauseofcoldair(5.Preheatairflow),the
changes in the indoor fan speed shifts up as follows,
from "off" to "UL", or from "UL" to "L". And when the
current falls bellow P5, the indoor fan speed shift up is
canceled.
Figure Y-10
8. Freeze preventive
When the indoor pipe temperature falls below -1˚C
duringcooloperationordryoperation,thecompressor
is turned off.
9. Defrost
The defrost timer (integrating the operation time of
compressor) counts time with microcomputer during
heat operation.
Frost of outdoor pipe is estimated by indoor pipe
temperature (TH2), room temperature (TH1), indoor
fan speed and operation state of compressor.
In the defrost operation, first the compressor is turned
off, the fan speed is set to “UL” and the outdoor fan
motor is turned off.
30 seconds later the indoor fan motor is turned off, 50
seconds later the reverse valve is turned off, and 60
seconds later the compressor is turned on.
In the end of defrosting, the compressor is turned off,
theoutdoorfanmotoristurnedon,50secondslaterthe
reverse valve is turned on, 60 seconds later the
compressor is turned on, starting heat operation.
Atthistime,theindoorfanmotoristurnedofforthefan
speed is set to “UL” if preheat air flow function is
effective.
Figure Y-11
Figure Y-12
10. Delayed operation of the reverse valve
Whentheheat operationisshut downorthe operating
modeisswitchedfromheattocoolordry,orviceversa,
the reverse valve is switched after 3 minutes.
11. Test run
If the “TEST RUN” button in the unit is pushed during
suspension of operation, cool test operation starts. At
this time, the fan speed is set to “AUTO”.
If this button is pushed during operation, the test
operation starts in current operation mode. The
operation LED (red) flickers during test run.
In cool and heat mode continuous compressor on
operationisperformed.In dry modetheoperationis in
dehumidifying zone. In fan only mode the indoor fan
motor runs continusly.
12. Timer
12-1 24-HOUR PROGRAMMABLE ON/OFF TIMER
ON-TIMERorOFF-TIMERcanbeindependently
programmed.Whentheunitoperatesduringone
houraftertheOFF-timeisset,thermostatsetting
is automatically shifted (+1˚C in cool operation
and dry operation, -3˚C in heat operation, 16˚C -
32˚C).
When the ON-timer is set in heat operation and
cool operation, operation starts before 0 to 30
minutes(depends on the room temperature) so
that preset temperature is obtaind at set time.
12-2 ONE-HOUR TIMER
When ONE-HOUR timer is set, the unit turns off
automaticallyafterone hour. Theonehour timer
operation has priority over other time operation,
such as the TIMER ON and TIMER OFF. If the
ONE-HOUR TIMER button is pressed again
duringoperation,theunitwilloperateadditionally
for another one hour.