  9. Sharp AU-X08CR User manual

Sharp AU-X08CR User manual

1
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
S3214AYX13CR/
SPLITTYPE
ROOM AIR CONDITIONERS
Intheinterestsofuser-safety(Requiredbysafetyregulationsinsome
countries) thesetshouldberestoredtoitsoriginalconditionandonly
parts identical to those specified should be used.
SERVICE MANUAL
Page
SPECIFICATIONS ............................................................................................................................................. 2
EXTERNAL DIMENSIONS .................................................................................................................................4
WIRING DIAGRAMS ......................................................................................................................................... 6
ELECTRICAL PARTS.........................................................................................................................................9
BLOCK DIAGRAM ............................................................................................................................................10
MICROCOMPUTER CONTROL SYSTEM .......................................................................................................12
FUNCTIONS .................................................................................................................................................... 19
FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES ............................................................... 25
BREAKDOWN DIAGNOSIS PROCEDURE .................................................................................................... 27
REFRIGERATION CYCLE ............................................................................................................................. 30
PERFORMANCE CURVES ............................................................................................................................. 32
DISASSEMBLING PROCEDURE.................................................................................................................... 33
OPTION ........................................................................................................................................................... 41
REPLACEMENT PARTS LIST ........................................................................................................................ 42
REFRIGERANT PIPING INSTALLATION/SERVICE MANUAL FOR AIR CONDITIONERS USING R-410A..49
TABLE OF CONTENTS
INDOOR UNIT
AH-X08CR/10CR/13CR
AY-X08CR/10CR/13CR
OUTDOOR UNIT
AU-X08CR/10CR/13CR
AE-X08CR/10CR/13CR
MODELS
SHARP CORPORATION
New Refrigerant : R-410A
2
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
SPECIFICATIONS
MODEL
I
NDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
ITEMS AH-X08CR AU-X08CR AH-X10CR AU-X10CR AH-X13CR AU-X13CR
Cooling capacity
(Min. ~ Max.)
kW 2.2(0.9 _ 2.7) 2.8(0.9 _3.3) 3.6(0.9 _4.0)
Moisture removal Liters/h 0.6 0.7 1.3
Electrical data
Phase Single
Rated frequency Hz 50
Rated voltage range V 198 to 264
Rated voltage V 220 - 240
Rated current A 3.4 _3.1 4.3 _4.0 5.5 _5.1
Rated input W 730 930 1200
Power factor % 98 _ 98 98 _ 97 99 _ 98
Type Hermetically sealed rotary type
Compressor Model DA89X1F-20F
Oil charge Ester oil VG68 370ml
Evaporator Bare tube type Grooved tube type Grooved tube type
Refrigerant system Condenser Louver Fin and Grooved tube type
Control Capillary tube
Refrigerant volume
640g 690g 660g
(R-410A)
Noise level High dB(A) 33 43 36 43 38 48
(at cooling) Med. dB(A) 29 – 32 – 33 -
Low dB(A) 27 – 27 – 29 -
Fan system
Drive Direct drive
Air flow quantity High m3/min. 7.5 28 8.7 28 9.3 30
(at cooling) Med. m3/min. 6.8 – 7.8 – 8.1 –
Low m3/min. 6.0 – 6.0 – 6.6 –
Fan
Cross flow fan Propeller fan Cross flow fan Propeller fan Cross flow fan Propeller fan
Connections
Refrigerant coupling Flare type
Refrigerant tube size Gas, Liquid 3/8", 1/4"
Drain piping mm O.D ø 18
Others Compressor: Compressor thermistor
Safety device Fan motors: Thermal fuse
Fuse, Micro computer control
Air filters Polypropylene net (Washable)
Width mm 815 780 815 780 815 780
Net dimensions Height mm 278 540 278 540 278 540
Depth mm 198 269 198 269 198 269
Net weight kg 9 30 9 30 10 33
Note: The condition of star " " marked item are ‘ISO5151’ : 1994(E), condition T1.
3
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
MODEL
I
NDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
ITEMS AY-X08CR AE-X08CR AY-X10CR AE-X10CR AY-X13CR AE-X13CR
Cooling capacity
(Min. ~ Max.)
kW 2.2(0.9 _ 2.7) 2.8(0.9 _3.3) 3.6(0.9 _4.0)
Heating capacity
(Min. ~ Max.)
kW 3.2(0.9 _ 3.6) 3.7(0.9 _5.0) 4.8(1.0 _6.2)
Moisture removal(at cooling) Liters/h 0.7 0.8 1.3
Electrical data
Phase Single
Rated frequency Hz 50
Rated voltage range V 198 to 264
Rated voltage V 220 - 240
Cool A 3.4 _3.1 4.3 _4.0 5.5 _5.1
Rated current Heat A 4.2 _3.9 4.9 _4.5 6.8 _6.2
Cool W 730 930 1200
Rated input Heat W 910 1050 1480
Cool % 98 _98 98 _97 99 _98
Power factor Heat % 98 _97 97 _97 99 _99
Type Hermetically sealed rotary type
Compressor Model DA89X1F-20F
Oil charge Ester oil VG68 370ml
Evaporator Louver Fin and Grooved tube type
Refrigerant system Condenser Corrugate Fin and Grooved tube type
Control Capillary tube
Refrigerant volume
750g 770g 870g
(R-410A)
De-lce system Micro computer controled reversed systems
Noise level High dB(A) 33 43 36 43 38 48
(at cooling) Med. dB(A) 29 – 32 – 33 -
Low dB(A) 27 – 27 – 29 -
Fan system
Drive Direct drive
Air flow quantity High m3/min. 7.5 28 9.8 27.7 9.3 30
(at cooling) Med. m3/min. 6.8 – 8.2 – 8.1 –
Low m3/min. 6.0 – 6.1 – 6.6 –
Fan
Cross flow fan Propeller fan Cross flow fan Propeller fan Cross flow fan Propeller fan
Connections
Refrigerant coupling Flare type
Refrigerant tube size Gas, Liquid 3/8", 1/4"
Drain piping mm O.D ø 18
Others Compressor: Compressor thermistor
Safety device Fan motors: Thermal fuse
Fuse, Micro computer control
Air filters Polypropylene net (Washable)
Width mm 815 780 815 780 815 780
Net dimensions Height mm 278 540 278 540 278 540
Depth mm 198 269 198 269 198 269
Net weight kg 9 33 10 33 10 37
Note: The condition of star " " marked item are ‘ISO5151’ : 1994(E), condition T1.
4
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
EXTERNAL DIMENSIONS
Figure E-1. INDOOR UNIT
Figure E-2. OUTDOOR UNIT
Length unit (mm)
815
278
198
1100
Remote controller
58
18.5
22
140
INVERTER AIR CONDITIONER
269
179.5
182.5
136
81
780
70
540
310
335
540
12
37.5
4.5
58
158
16
5
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
Figure E-3. INSTALLATION DIMENSIONS
815 (unit size)
More than 50mm
E
Center of wall hole:
Leftward piping Center of wall hole: Backward piping
Outline of indoor unit
55 95
80 55
AJ
IF
ED
D
FA
CJ
H
I
GB
21
278 (unit size)
38
Ceiling
E
6
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
WIRING DIAGRAMS
Figure W-1. Wiring Diagram for AH-X08CR/X10CR/X13CR and AY-X08CR/X10CR/X13CR
BROWN RY1
In Out
CB612-1
10
7
8
6
Temperature
Indicator
Blinking No. Abnormal contents
AC overcurrent
Abnormal AC current
WPE1
250V
3A
INDOOR UNIT
UNIT
TO
UNIT
CORD
Power factor module(AF1) error
13
Overheat of the power module(IPM) or
short circuit of the power module(IPM) heat-sink thermistor
Open circuit of the power module(IPM) heat-sink thermistor
Rotation error of the compressor
OUTDOOR UNIT
N
1
2
TERMINAL BOARD
CONTROL BOARD UNIT
POWER
SUPPLY
TERMINAL BOARD 2
SINGLE
PHASE
N
1
2
CONTROL
BOARD
UNIT
M
M
FAN MOTOR
COMPRESSOR
N
1
TERMINAL BOARD 1
M
M
LOUVER
(LOWER)
SERIAL
SIGNAL
CIRCUIT
BLUE
BLUE
BLACK
S
RED
N
INTERNAL
THERMAL
FUSE
RECEIVER
BOARD UNIT R.P.M.
SIGNAL
FAN MOTOR
CAPACITOR
430V 2.0µF
FAN MOTOR
LOUVER
(UPPER)
13
TH1
5
CN1
BCN1
BCN3
BCN2
CN2
CN3
TH2
YELLOW
ORANGE
CN6
CN7
DISPLAY
BOARD
UNIT CN101
CN102
ROOM TEMP.
THERMISTOR
PIPE TEMP.
THERMISTOR
GREEN-YELLOW
TRANS1 SSR1
1
3
4
2
RED
BLUE
BLACK
C1
LED INDICATION FOR SELF-DIAGNOSIS
5
2
3
1
14
17
18
19
Short circuit of the outdoor thermistor
Overheat of the compressor
Open circuit of the outdoor thermistor
Power module(IPM) abnormality
Open circuit of serial signal line
Abnormal fan motor of indoor unit
Short circuit of serial signal line
CB612-2
<Indication of the abnormal condition>
LED indicator will blink,if the set
is in abnormal condition.
7
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
Figure W-2. Wiring Diagram for AE-X08CR/X10CR
+
-
+
-
N
1
2
INDOOR UNIT TERMINAL
BOARD
CONTROL
BOARD
UNIT
POWER
SUPPLY
FAN
MOTOR
TERMINAL BOARD
UNIT TO UNIT CORD
SINGLE PHASE
220-240V 50Hz
BL
T2
BR
T3
RE
FC4
BULK HEAD
RE
T1 WPE1
C1
C2
C3
C4
C33
C34
15A
250V
SA1
RY1
T4
BCN11
CT1
The voltage is high at C8 (electronic capacitors) on outdoor unit.
For mentenance discharge at C8 to prevent electric shock.
In case that WPE101 has been fused, the voltage is kept high at C8.
CAUTION
BK:BLACK RE:RED YE:YELLOW
BL:BLUE WH:WHITE G:GREEN
BR:BROWN OR:ORANGE
GR:GRAY G(Y):GREEN-YELLOW
BL GR
G(Y)G(Y)
FAN
MOTOR
BL
PTC
MRY1
IN OUT
T6
T5
BK
TP
TN
YE
C8
OUTDOOR UNIT
POWER
TRANSISTOR
MODULE (QM101)
TU TV TW
RE WH OR
COMPRESSOR
THERMISTOR
PIPE TEMP.
THERMISTOR
OUTDOOR
TEMP.
THERMISTOR
COMP. TEMP.
CN8
TH2
TH1
TH3
RE
OR
G
3
15
LED INDICATION OF SELF-DIAGNOSIS
ON OUTDOOR UNIT
LED BLINKING
LED turns on
Slow flashing (1 time for 2 seconds)
Quick flashing (3 times for 2 seconds)
Example: NO.2 Overheat of the compressor
1.0sec 0.6sec 0.6sec 1.0sec 0.6sec 0.6sec CB565
1
2
3
410
NO. LED indication pattern Mulfunction part or abnormal condition
Normal
Abnormal signal line
Overheat of the compressor
DC overcurrent of the power module (QM101)
Short circuit of the thermistor
7
8
6
NO. LED indication pattern Mulfunction part or abnormal condition
Open circuit of the thermistor
AC overcurrent
AC abnormal current
BK
1
2
3
4
5
6
NR1
NR2
CNR1
N
1
2
L3 L4
WPE3
3A
250V
CN3
CONTROL BOARD UNIT
DIODE BRIDGE
DB1
BL
C5
WPE101
20A
250V
OR
FC1
C10
C
AM
CONTROL
BOX
FAN MOTOR
CAPACITOR
1.5µF 450V
C31 +
-
L1
WH
C8:1000µF 420V
BL
~
~
9Power factor module(AF1) error
S
R
C(T)
FC5
AF1L-
L+
I-
I+
ACTIVE
FILTER O-
O+
WH
YE
BR
FC2
3
1
RY2
CNR2
4-WAY
VALVE
5
11
Overheat of the power module or
short circuit of the heat-sink thermistor
Open circuit of the heat-sink thermistor
Rotation error of the compressor
C36
C35 C37
C38
BK
1
3
THERMISTOR
HEAT-SINK
TEMP.
CN7
41
YE BL
CN12
CN13 BCN2
CN101
CN102
CN6
2
4
6
RE
WH
OR
POWER
TRANSISTOR
UNIT
NO.3 DC overcurrent of the power module (QM101)
1.0sec 0.6sec 0.6sec 1.0sec 0.6sec 0.6sec 0.6sec
0.6sec
x 2times
x 3times
x 4times
x 5times
x 6times
x 7times
x 9times
x 11times
x 13times
x 14times
This circuit
is removed
about cooling
only models
CN4
8
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
Figure W-3. Wiring Diagram for AE-X13CR
+
-
+
-
N
1
2
INDOOR UNIT TERMINAL
BOARD
CONTROL
BOARD
UNIT
POWER
SUPPLY
FAN
MOTOR
TERMINAL BOARD
UNIT TO UNIT CORD
SINGLE PHASE
220-240V 50Hz
BL
T2
BR
T3
RE
FC4
BULK HEAD
RE
T1 WPE1
C1
C2
C3
C4
C33
C34
20A
250V
SA1
RY1
T4
BCN11
CT1
The voltage is high at C8 (electronic capacitors) on outdoor unit.
For mentenance discharge at C8 to prevent electric shock.
In case that WPE101 has been fused, the voltage is kept high at C8.
CAUTION
BK:BLACK RE:RED YE:YELLOW
BL:BLUE WH:WHITE G:GREEN
BR:BROWN OR:ORANGE
GR:GRAY G(Y):GREEN-YELLOW
BL GR
G(Y)G(Y)
FAN
MOTOR
BL
PTC
MRY1
IN OUT
T6
T5 BK
TP
TN
YE
C8
OUTDOOR UNIT
POWER
TRANSISTOR
MODULE (QM101)
TU TV TW
RE WH OR
COMPRESSOR
THERMISTOR
PIPE TEMP.
THERMISTOR
OUTDOOR
TEMP.
THERMISTOR
COMP. TEMP.
CN8
TH2
TH1
TH3
RE
OR
G
3
15
LED INDICATION OF SELF-DIAGNOSIS
ON OUTDOOR UNIT
LED BLINKING
LED turns on
Slow flashing (1 time for 2 seconds)
Quick flashing (3 times for 2 seconds)
Example: NO.2 Overheat of the compressor
1.0sec 0.6sec 0.6sec 1.0sec 0.6sec 0.6sec CB566
1
2
3
410
NO. LED indication pattern Mulfunction part or abnormal condition
Normal
Abnormal signal line
Overheat of the compressor
DC overcurrent of the power module (QM101)
Short circuit of the thermistor
7
8
6
NO. LED indication pattern Mulfunction part or abnormal condition
Open circuit of the thermistor
AC overcurrent
AC abnormal current
BK
1
2
3
4
5
6
NR1
NR2
CNR1
N
1
2
L3 L4
WPE3
3A
250V
CN3
CONTROL BOARD UNIT
DIODE BRIDGE
DB1
BL
C5
WPE101
20A
250V
OR
FC1
C10
C
AM
CONTROL
BOX
FAN MOTOR
CAPACITOR
2.0µF 450V
C31 +
-
L1
WH
C8:1300
µ
F 420V
BL
~
~
9Power factor module(AF1) error
S
R
C(T)
FC5
AF1
L-
L+
I-
I+ACTIVE
FILTER O-
O+
WH
YE
BR
FC2
3
1
RY2
CNR2
4-WAY
VALVE
511
Overheat of the power module or
short circuit of the heat-sink thermistor
Open circuit of the heat-sink thermistor
Rotation error of the compressor
C36
C35 C37
C38
BK
1
3THERMISTOR
HEAT-SINK
TEMP.
CN7
41
YE BL
CN12
CN13 BCN2
CN101
CN102
CN6 2
4
6RE
WH
OR
POWER
TRANSISTOR
UNIT
NO.3 DC overcurrent of the power module (QM101)
1.0sec 0.6sec 0.6sec 1.0sec 0.6sec 0.6sec 0.6sec
0.6sec
x 2times
x 3times
x 4times
x 5times
x 6times
x 7times
x 9times
x 11times
x 13times
x 14times
This circuit
is removed
about cooling
only models
CN4
9
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
Figure W-4. Wiring Diagram for AU-X08CR/X10CR
+
-
+
-
N
1
2
INDOOR UNIT TERMINAL
BOARD
CONTROL
BOARD
UNIT
POWER
SUPPLY
FAN
MOTOR
TERMINAL BOARD
UNIT TO UNIT CORD
SINGLE PHASE
220-240V 50Hz
BL
T2
BR
T3
RE
FC4
BULK HEAD
RE
T1WPE1
C1
C2
C3
C4
C33
C34
15A
250V
SA1
RY1
T4
BCN11
CT1
The voltage is high at C8 (electronic capacitors) on outdoor unit.
For mentenance discharge at C8 to prevent electric shock.
In case that WPE101 has been fused, the voltage is kept high at C8.
CAUTION BK:BLACK RE:RED YE:YELLOW
BL:BLUE WH:WHITE G:GREEN
BR:BROWN OR:ORANGE
GR:GRAY G(Y):GREEN-YELLOW
BL GR
G(Y)G(Y)
FAN
MOTOR
BL
PTC
MRY1
IN OUT
T6
T5 BK
TP
TN
YE
C8
OUTDOOR UNIT
POWER
TRANSISTOR
MODULE (QM101)
TU TV TW
RE WH OR
COMPRESSOR
THERMISTOR
PIPE TEMP.
THERMISTOR
OUTDOOR
TEMP.
THERMISTOR
COMP. TEMP.
CN8
TH2
TH1
TH3
RE
OR
G
3
15
LED INDICATION OF SELF-DIAGNOSIS
ON OUTDOOR UNIT
LED BLINKING
LED turns on
Slow flashing (1 time for 2 seconds)
Quick flashing (3 times for 2 seconds)
Example: NO.2 Overheat of the compressor
1.0sec 0.6sec 0.6sec 1.0sec 0.6sec 0.6sec CB567
1
2
3
410
NO. LED indication pattern Mulfunction part or abnormal condition
Normal
Abnormal signal line
Overheat of the compressor
DC overcurrent of the power module (QM101)
Short circuit of the thermistor
7
8
6
NO. LED indication pattern Mulfunction part or abnormal condition
Open circuit of the thermistor
AC overcurrent
AC abnormal current
BK
1
2
3
4
5
6
NR1
NR2
CNR1
N
1
2
L3 L4
WPE3
3A
250V
CN3
CONTROL BOARD UNIT
DIODE BRIDGE
DB1
BL
C5
WPE101
20A
250V
OR
FC1
C10
C
AM
CONTROL
BOX
FAN MOTOR
CAPACITOR
1.5µF 450V
C31 +
-
L1
WH
C8:1000µF 420V
BL
~
~
9Power factor module(AF1) error
S
R
C(T)
FC5
AF1
L-
L+
I-
I+ACTIVE
FILTER O-
O+
WH
YE
BR
FC2
511
Overheat of the power module or
short circuit of the heat-sink thermistor
Open circuit of the heat-sink thermistor
Rotation error of the compressor
C36
C35 C37
C38
BK
1
3THERMISTOR
HEAT-SINK
TEMP.
CN7
41
YE BL
CN12
CN13 BCN2
CN101
CN102
CN6 2
4
6RE
WH
OR
POWER
TRANSISTOR
UNIT
NO.3 DC overcurrent of the power module (QM101)
1.0sec 0.6sec 0.6sec 1.0sec 0.6sec 0.6sec 0.6sec
0.6sec
x 2times
x 3times
x 4times
x 5times
x 6times
x 7times
x 9times
x 11times
x 13times
x 14times
10
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
Figure W-5. Wiring Diagram for AU-X13CR
+
-
+
-
N
1
2
INDOOR UNIT TERMINAL
BOARD
CONTROL
BOARD
UNIT
POWER
SUPPLY
FAN
MOTOR
TERMINAL BOARD
UNIT TO UNIT CORD
SINGLE PHASE
220-240V 50Hz
BL
T2
BR
T3
RE
FC4
BULK HEAD
RE
T1 WPE1
C1
C2
C3
C4
C33
C34
20A
250V
SA1
RY1
T4
BCN11
CT1
The voltage is high at C8 (electronic capacitors) on outdoor unit.
For mentenance discharge at C8 to prevent electric shock.
In case that WPE101 has been fused, the voltage is kept high at C8.
CAUTION BK:BLACK RE:RED YE:YELLOW
BL:BLUE WH:WHITE G:GREEN
BR:BROWN OR:ORANGE
GR:GRAY G(Y):GREEN-YELLOW
BL GR
G(Y)G(Y)
FAN
MOTOR
BL
PTC
MRY1
IN OUT
T6
T5 BK
TP
TN
YE
C8
OUTDOOR UNIT
POWER
TRANSISTOR
MODULE (QM101)
TU TV TW
RE WH OR
COMPRESSOR
THERMISTOR
PIPE TEMP.
THERMISTOR
OUTDOOR
TEMP.
THERMISTOR
COMP. TEMP.
CN8
TH2
TH1
TH3
RE
OR
G
3
15
LED INDICATION OF SELF-DIAGNOSIS
ON OUTDOOR UNIT
LED BLINKING
LED turns on
Slow flashing (1 time for 2 seconds)
Quick flashing (3 times for 2 seconds)
Example: NO.2 Overheat of the compressor
1.0sec 0.6sec 0.6sec 1.0sec 0.6sec 0.6sec
CB568
1
2
3
410
NO. LED indication pattern Mulfunction part or abnormal condition
Normal
Abnormal signal line
Overheat of the compressor
DC overcurrent of the power module (QM101)
Short circuit of the thermistor
7
8
6
NO. LED indication pattern Mulfunction part or abnormal condition
Open circuit of the thermistor
AC overcurrent
AC abnormal current
BK
1
2
3
4
5
6
NR1
NR2
CNR1
N
1
2
L3 L4
WPE3
3A
250V
CN3
CONTROL BOARD UNIT
DIODE BRIDGE
DB1
BL
C5
WPE101
20A
250V
OR
FC1
C10
C
AM
CONTROL
BOX
FAN MOTOR
CAPACITOR
2.0µF 430V
C31
+
-
L1
WH
C8:1300µF 420V
BL
~
~
9Power factor module(AF1) error
S
R
C(T)
FC5
AF1
L
-
L
+
I
-
I
+
ACTIVE
FILTER O
-
O
+
WH
YE
BR
FC2
511
Overheat of the power module or
short circuit of the heat-sink thermistor
Open circuit of the heat-sink thermistor
Rotation error of the compressor
C36
C35 C37
C38
BK
1
3
THERMISTOR
HEAT-SINK
TEMP.
CN7
41
YE BL
CN12
CN13 BCN2
CN101
CN102
CN6
2
4
6
RE
WH
OR
POWER
TRANSISTOR
UNIT
NO.3 DC overcurrent of the power module (QM101)
1.0sec 0.6sec 0.6sec 1.0sec 0.6sec 0.6sec 0.6sec
0.6sec
x 2times
x 3times
x 4times
x 5times
x 6times
x 7times
x 9times
x 11times
x 13times
x 14times
27
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
BREAK DOWN DIAGNOSIS PROCEDURE
Self-diagnostic procedure using display mode
If the timer lamp blinks during operation, the problem can be diagnosed using the following table.
: Blinks at 2-second intervals : OFF : ON : Blinks 3 times at 0.2-second intervals
The error of outdoor unit
Display by indoor unit operation lamp
Displayed in a pattern which comes on at the same
time as the timer lamp
4 seconds off
What to check, procedure
Display by
outdoor
unit lamp
LED 1 Diagnosis Solution
Condition
of indoor
and
outdoor
unit
Normal
Twice
3 times
4 times
5 times
6 times
7 times
DC overcurrent error
AC overcurrent error
Normal
Overheat of the power
module or short circuit
of the heatsink
thermistor.
1. Check the circuit in the power transistor module.
2. Is the outdoor fan revolving ?
1. Is the discharge outlet of the outdoor unit clogged ?
1. Measure the resistance of heatsink thermistor TH6 on the heatsink
in outdoor unit.
2. Check rotation of the fan motor in outdoor unit.
3. Is the power supply voltage at least 198V at full power operation ?
1. Measure the resistance of thermistor TH2 on the outdoor unit
(see Figure 3).
1. Replace power transistor
module
1. Clear the discharge outlet.
11 times Power factor module error
1. CHeck wiring of power factor module. 1. Replace the power factor module.
1. Reattach.
2. Reattach CN101 and CN102,
otherwise replace power transistor
module assembly or outdoor control
board assembly.
9 times
14 times
13 times
Rotation errot of the
compressor
1. Has not if escaped from the compressor CN6 ?
2. Is the power supplied of 15V and 6V supplied to the IPM PWB.
1. Replace the heatsink thermistor.
Open circuit of the
heatsink thermistor.
1. Are the connectors of the heatsink thermistor in outdoor unit well
attached ?
2. Measure the resistance of thermistor TH6 on the heatsink.
(See Figure 3).
Overheat of the comp-
ressor error
(protector operating) or
outdoor compressor
thermistor TH1 short
1. Reattach.
2. Replace the heatsink thermistor.
1. Replace the outdoor control board
assembly
(Current transformer wire break.)
1. Reattach.
2. Replace the outdoor thermistor
assembly.
1. Replace the outdoor thermistor
assembly.
1. Clear the discharge outlet.
2. Assure power supply voltage.
3. Refill to rated amount.
4. Replace the outdoor ther-mistor
assembly.
5. Replace the indoor control board
assembly or only TH2.
1. Can voltage be detected at the current transformer on the outdoor
unit control board?
1. Is the connector of the outdoor unit thermistors well attached ?
(see Figure 3).
2. Measure the resistance of thermistors TH1 and TH2 on the
outdoor unit (see Figure 3).
1. Is the discharge outlet of the outdoor unit clogged ?
2. Is the power supply voltage at least 198 V at full power operation ?
3. Check for refrigerant leaks at the tubing connections.
4. Measure the resistance of compressor thermistor TH1 on the
outdoor unit (see Figure 3).
5. Measure the resistance of heat exchanger pipe thermistor TH2 on
the indoor unit (see Figure 1).
AC abnormal current
error
Open circuit of the
outdoor thermistor error
Short circuit of the
outdoor thermistor error
2. Reattach CN3, otherwise replace
the fan motor of outdoor unit.
3. Assure power supply voltage.
28
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
Note: 1. Normal : Only the timer lamp blinks. Error : Displayed by blinking of run
lamp (above table).
2. If the power plug is removed from the outlet or the breaker is switched to
"OFF", the self-diagnostic memory will be erased.
3. Example of outdoor unit LED 1 blinking :
: Blinks at 2-second intervals : OFF : ON : Blinks 3 times at 0.2-second intervals
The error of indoor unit
Display by indoor unit operation lamp
Displayed in a pattern which comes on at the same
time as the timer lamp
4 seconds off
What to check, procedure
Display by
outdoor
unit lamp
LED 1 Diagnosis Solution
Condition
of indoor
and
outdoor
unit
Serial short
Serial open 1. Check the wiring between units.
1. Check the wiring between units.
1. Check the wiring between units.
2. Check the fuse in the outdoor unit.
3. Indoor control board.
4. Outdoor control board.
1. Rewire.
1. Rewire.
Indoor fan out of order 1. Is the fan motor locked ?
2. Is the wiring connector firmly fitted ?
3. Is the speed signal applied to the motor ?
Outdoor power supply
does't turn on.
Wiring mistake.
1. Rewire.
2. Replace the fuse, replace the
outdoor board assembly.
3. Replace the board.
4. Replace the board.
1. Replace fan motor
2. Reattach.
3. Replace the indoor control board
assembly.
1
sec. 1
sec. 0.6
sec. 1
sec. 1
sec. 1
sec. 1
sec. 1
sec. 1
sec.
Overheat of the compressor
0.6
sec.
1
sec. 0.6
sec. 1
sec. 0.6
sec.
2 times
OFF
ON
OFF
32
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
PERFORMANCE CURVES
NOTE: 1) Indoor fan speed: Hi
2) Vertical adjustment louver "45˚", Horizontal adjustment louver "front"
3) Indoor air temp. : Cooling 27˚C, Heating 20˚C
Figure P-1. At Cooling for AH-X08CR Figure P-2. At Cooling for AH-X10CR
Figure P-3. At Cooling for AH-X13CR Figure P-4. At Cooling for AY-X08CR
Figure P-5. At Cooling for AY-X10CR Figure P-6. At Cooling for AY-X13CR
25 30 35 40
2.0
2.2
2.4
2.6
10
12
14
600
700
800
900
Cooling capacity(kW)
Outside air temp.(˚C)
Input(W)
Outlet air temp.(˚C)
(Running frequency: 50HZ)
25 30 35 40
2.4
2.6
2.8
3.0
3.2 12
14
16
700
800
900
1000
(Running frequency: 62Hz)
Cooling capacity(kW)
Outside air temp.(˚C)
Input(W)
Outlet air temp.(˚C)
25 30 35 40
3.2
3.4
3.6
3.8
4.0 10
12
14
1000
1100
1200
1300
(Running frequency: 81Hz)
Cooling capacity(kW)
Outside air temp.(˚C)
Input(W)
Outlet air temp.(˚C)
25 30 35 40
2.0
2.2
2.4
2.6
10
12
14
600
700
800
900
Cooling capacity(kW)
Outside air temp.(˚C)
Input(W)
Outlet air temp.(˚C)
(Running frequency: 51Hz)
25 30 35 40
2.4
2.6
2.8
3.0
3.2 12
14
16
700
800
900
1000
(Running frequency: 63Hz)
Cooling capacity(kW)
Outside air temp.(˚C)
Input(W)
Outlet air temp.(˚C)
25 30 35 40
3.2
3.4
3.6
3.8
4.0 10
12
14
1000
1100
1200
1300
(Running frequency: 83Hz)
Cooling capacity(kW)
Outside air temp.(˚C)
Input(W)
Outlet air temp.(˚C)
33
AH/AY-X08CR
AH/AY-X10CR
AH/AY-X13CR
Figure P-7. At Heating for AY-X08CR Figure P-8. At Heating for AY-X10CR
Figure P-9. At Heating for AY-X13CR
-5 0 7510
2.4
2.8
3.2
3.6
35
40
45
700
800
900
1000
(Running frequency: 68Hz)
Heating capacity(kW)
Outside air temp.(˚C)
Input(W)
Outlet air temp.(˚C)
-5 0 5 7 10
2.5
3.0
3.5
4.0 30
35
40
45
800
900
1000
1100
(Running frequency: 79Hz)
Heating capacity(kW)
Outside air temp.(˚C)
Input(W)
Outlet air temp.(˚C)
-5 0 5 7 10
3.0
3.5
4.0
4.5
5.0
5.5
30
35
40
45
1200
1300
1400
1500
1600 (Running frequency: 96Hz)
Heating capacity(kW)
Outside air tem
p
.
(
˚C
)
Input(W)
Outlet air temp.(˚C)

This manual suits for next models

11

Other Sharp Air Conditioner manuals

Sharp AY-XP12GHR User manual

Sharp

Sharp AY-XP12GHR User manual

Sharp AH-X08BE User manual

Sharp

Sharp AH-X08BE User manual

Sharp CVP12PX - Ha Sh 11500 Btu Portable Air... User manual

Sharp

Sharp CVP12PX - Ha Sh 11500 Btu Portable Air... User manual

Sharp AY-M09AE User manual

Sharp

Sharp AY-M09AE User manual

Sharp AY-XM09BE User manual

Sharp

Sharp AY-XM09BE User manual

Sharp AH-AP09CF User manual

Sharp

Sharp AH-AP09CF User manual

Sharp CV-P09LX User manual

Sharp

Sharp CV-P09LX User manual

Sharp AF-100DX User manual

Sharp

Sharp AF-100DX User manual

Sharp AY-XM12CR User manual

Sharp

Sharp AY-XM12CR User manual

Sharp AH-AP9MMV User manual

Sharp

Sharp AH-AP9MMV User manual

Sharp AE-X9USR User manual

Sharp

Sharp AE-X9USR User manual

Sharp AY-X10CR User manual

Sharp

Sharp AY-X10CR User manual

Sharp AY-XPC18LR User manual

Sharp

Sharp AY-XPC18LR User manual

Sharp CV-P09FR User manual

Sharp

Sharp CV-P09FR User manual

Sharp GS-XP9FGR User manual

Sharp

Sharp GS-XP9FGR User manual

Sharp FU-Z35TA User manual

Sharp

Sharp FU-Z35TA User manual

Sharp AY-AP12FHR User manual

Sharp

Sharp AY-AP12FHR User manual

Sharp AE-X15PU User manual

Sharp

Sharp AE-X15PU User manual

Sharp AY-XPC12JR User manual

Sharp

Sharp AY-XPC12JR User manual

Sharp AH-A9FEF User manual

Sharp

Sharp AH-A9FEF User manual

Sharp AH-X079E User manual

Sharp

Sharp AH-X079E User manual

Sharp PJ-A36TV-B User manual

Sharp

Sharp PJ-A36TV-B User manual

Sharp Air Conditioner User manual

Sharp

Sharp Air Conditioner User manual

Sharp AY-X08BE User manual

Sharp

Sharp AY-X08BE User manual

Popular Air Conditioner manuals by other brands

Samsung NS100HHXEH Service manual

Samsung

Samsung NS100HHXEH Service manual

Fujitsu ABYG45KRTA Design & technical manual

Fujitsu

Fujitsu ABYG45KRTA Design & technical manual

Fujitsu GENERAL ABHG36KRTA Service manual

Fujitsu

Fujitsu GENERAL ABHG36KRTA Service manual

Panasonic CS-SC9BKN Operating lnstructions

Panasonic

Panasonic CS-SC9BKN Operating lnstructions

Toshiba RAV-SP804AT-E installation manual

Toshiba

Toshiba RAV-SP804AT-E installation manual

Lennox VRF V22A Series Installation instruction

Lennox

Lennox VRF V22A Series Installation instruction

Global Industrial 293133 user manual

Global Industrial

Global Industrial 293133 user manual

Daewoo Dhome DA9KWE user manual

Daewoo

Daewoo Dhome DA9KWE user manual

Siemens S1 RKM 09102 Instructions for use

Siemens

Siemens S1 RKM 09102 Instructions for use

MDV MDSF-07HRN1 Service manual

MDV

MDV MDSF-07HRN1 Service manual

Amcor APC 2000E owner's manual

Amcor

Amcor APC 2000E owner's manual

Mitsubishi Electric PLFY-P-VAM-E installation manual

Mitsubishi Electric

Mitsubishi Electric PLFY-P-VAM-E installation manual

Bryant DURAPAC 579F User's information manual

Bryant

Bryant DURAPAC 579F User's information manual

Soleus Air PAC12 user manual

Soleus Air

Soleus Air PAC12 user manual

Mitsubishi Electric MSZ-GA22VA operating instructions

Mitsubishi Electric

Mitsubishi Electric MSZ-GA22VA operating instructions

Harbor Point HF-25GW Installation, operation and maintanance manual

Harbor Point

Harbor Point HF-25GW Installation, operation and maintanance manual

Impecca ISMI-W092 manual

Impecca

Impecca ISMI-W092 manual

Carrier EconoMiser2 CRECOMZR087A00 installation instructions

Carrier

Carrier EconoMiser2 CRECOMZR087A00 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.