(Be sure to read these precautions before using our products.)
The safety precautions are classified into 2 categories: “Warning” and “Caution”.
Warning: Procedures which may lead to dangerous conditions and cause death or serious injury, if not
carried out properly.
Caution: Procedures which may lead to dangerous conditions and cause superficial to medium injury or
physical damage or may degrade or damage the product, if not carried out properly.
Caution for Installation
This instrument is intended to be used under the following environmental
conditions (IEC61010-1)]: Overvoltage category , Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to
122 ) that does not change rapidly, and no icing.
• An ambient non-condensing humidity of 35 to 85 %RH
• No large capacity electromagnetic switches or cables through which large
current is flowing
• No water, oil or chemicals or where the vapors of these substances can
come into direct contact with the unit
• Take note that the ambient temperature of this unit – not the ambient
temperature of the control panel – must not exceed 50 (122 ) if mounted
through the face of a control panel, otherwise the life of electronic
components (especially electrolytic capacitors) may be shortened.
Warning
• To prevent electric shock or fire, only Shinko or other qualified service personnel may handle the inner
assembly.
• To prevent electric shock, fire or damage to the instrument, parts replacement may only be undertaken by
Shinko or other qualified service personnel.
SAFETY PRECAUTIONS
• To ensure safe and correct use, thoroughly read and understand this manual before using this instrument.
• This instrument is intended to be used for industrial machinery, machine tools and measuring equipment.
Verify correct usage after purpose-of-use consultation with our agency or main office. (Never use this
instrument for medical purposes with which human lives are involved.)
• External protection devices such as protective equipment against excessive temperature rise, etc. must be
installed, as malfunction of this product could result in serious damage to the system or injury to personnel.
Proper periodic maintenance is also required.
• This instrument must be used under the conditions and environment described in this manual. Shinko
Technos Co., Ltd. does not accept liability for any injury, loss of life or damage occurring due to the
instrument being used under conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being
utilized in the manufacture of weapons of mass destruction (i.e. military
applications, military equipment, etc.), please investigate the end users and
the final use of this instrument. In the case of resale, ensure that this
instrument is not illegally exported.
Specifications
Power supply
voltage
100 to 240 V AC 50/60 Hz, Allowable voltage fluctuation: 85 to 264 V AC
24 V AC/DC 50/60 Hz, Allowable voltage fluctuation: 20 to 28 V AC/DC
EVT output
Alarm output:
(Alarm, Loop break alarm and optional Heater burnout alarm utilize common
output terminals.)
The alarm action point is set by deviation from the SV (excluding Process
alarm), and if the input goes outside the range, alarm is turned ON or OFF
(High/ Low limit range alarm).
When De-energized action is selected in [Alarm action Energized/
De-energized], alarm is activated conversely.
Setting accuracy: Same as basic accuracy
Action: ON/OFF action
Hysteresis: Thermocouple, RTD inputs: 0.1 to 100.0 ( )
DC voltage, current inputs: 1 to 1000 (The placement of the
decimal point follows the selection.)
Output: Open collector, Control capacity: 0.1 A 24 V DC
Alarm type: High limit alarm, Low limit alarm, High/Low limits alarm,
High/Low limits independent alarm, High/Low limit range alarm, High/Low
limit range independent alarm, Process high alarm, Process low alarm,
High limit with standby alarm, Low limit with standby alarm, High/Low
limits with standby alarm, High/Low limits with standby independent
alarm.
Energized/De-energized action are applied to the above alarms, totaling
24 alarm types. No alarm action can also be selected.
Alarm Energized/De-energized: Alarm output Energized/ De-energized can
be selected.
Alarm Energized Alarm De-energized
EVT indicator (Red) Lit Lit
EVT output ON OFF
Alarm HOLD function: Once an alarm is activated, the alarm output is
maintained until the power is turned off.
Loop break alarm output:
(Loop break alarm, Alarm and optional Heater burnout alarm utilize common
output terminals.)
Detects heater burnout, sensor burnout and actuator trouble.
Setting range:
Loop break alarm time: 0 to 200 minutes
Loop break alarm span:
Thermocouple, RTD inputs: 0 to 150 ( ) or 0.0 to 150.0 ( )
DC voltage, current inputs: 0 to 1500 (The placement of the decimal point
follows the selection.)
Output: Open collector, Control capacity: 0.1 A 24 V DC
Basic accuracy
(at ambient
temperature 23 ,
for a single unit
mounting)
Thermocouple input: Within 0.2% of each input span 1 digit, or 2
(4 ), whichever is greater
However, R, S inputs, 0 to 200 (0 to 400 ): Within 6 (12 )
B input, 0 to 300 (0 to 600 ): Accuracy is not guaranteed.
K, J, E, T, N inputs, Less than 0 (32 ):
Within 0.4% of input span 1 digit, or 4 (8 ), whichever is
greater
RTD input: Within 0.1% of each input span 1 digit or 1 (2 ),
whichever is greater
DC voltage input: Within 0.2% of each input span 1 digit
Direct current input: Within 0.2% of each input span 1 digit
Input sampling
period 125 ms
Power
consumption
100 to 240 V AC: Approx. 5 VA max.
24 V AC: Approx. 4 VA max.
24 V DC: Approx. 4 W max.
Ambient
Temperature,
Humidity
0 to 50 ,
35 to 85 %RH (Non-condensing)
Weight Approx. 100 g
Accessories
Instruction manual excerpt: 1 copy
When W option is ordered: Connector harness 3 m 1 length
When
W option
(5A, 10A, 20A) is ordered: CT (CTL-6S) 1 piece
When
W option
(50A) is ordered: CT (CTL-12-S36-10L1U) 1 piece
When EI option is ordered:
Connector harness AOJ 3 m 1 length
When EA option is ordered:
Connector harness AOJ 3 m 1 length
Control output
(OUT1)
Relay contact 1a, Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos =0.4)
Electrical life: 100,000 cycles
Non-contact voltage (for SSR drive): 12 V DC 15%
Max 40 mA (short circuit protected)
Direct current: 4 to 20 mA DC, Load resistance: Max 550
Output accuracy: Within 0.3% of output span
Resolution: 12000
Heating/Cooling
control output
(OUT2)
(DC option)
Output: Open collector, Control capacity: 0.1 A 24 V DC
External Dimensions (Scale: mm)
Name and Functions
①EVT indicator The red LED turns on when Event output (Alarm, Loop break alarm or optional Heater burnout alarm) is ON.
The red LED also turns on when Cooling output is ON if Heating/Cooling control option is ordered.
②OUT indicator
The green LED turns on when OUT (control output) is ON (when Heating output is ON if Heating/Cooling control option is
ordered).
For Direct current output, flashes in 125 ms cycles corresponding to the output MV.
③T/R indicator The yellow LED flashes during Serial communication TX output (transmitting).
④AT indicator The yellow LED flashes while auto-tuning (AT) is performing.
⑤PV Display Indicates the PV (process variable), or setting characters in setting mode with a red LED.
⑥SV Display Indicates the SV (desired value), output MV (manipulated variable) or each set value in each setting mode with a green LED.
⑦UP key Increases the numeric value.
⑧DOWN key Decreases the numeric value.
⑨MODE key Switches the setting mode or registers the set data.
(Registers the set data by pressing the MODE Key.)
⑩SUB-MODE key
Enters Auxiliary function setting mode 2 in combination with the MODE key.
If Control output OFF is selected in [SUB-MODE key function]: Turns all outputs OFF as if the power were turned OFF.
If Auto/Manual control is selected in [SUB-MODE key function]: Switches the Auto/Manual control.
If Alarm HOLD cancel is selected in [SUB-MODE key function]: Cancels Alarm HOLD.
Caution
When setting the specifications and functions of this unit, connect mains power cable to terminals 1 and 2 first, then set them referring to “Key Operation Flowchart”,
before “Mounting to the Control Panel” and “Wiring”.
Do not pull or bend the lead wire on the terminal side when wiring or after wiring, as it could cause malfunction.
Terminal Arrangement