Shinko DCL-33A User manual

1
Instruction manual
DIN rail mounting type indicating controller DCL-33A
No.DCL31E1 .
To prevent accidents arising from the misuse of this controller, please ensure the operator using it
receives this manual.
Caution
•
This instrument should be used according to the specifications described in this manual.
If it is not used according to the specifications, it may malfunction or breakdown.
•
Be sure to follow the warnings, cautions and notices. If not, serious injury or accidents may occur.
•
The specifications of the DCL-33A and the contents of this instruction manual are subject to change
without notice.
•
Care has been taken to assure that the contents of this instruction manual are correct, but if there are
any doubts, mistakes or questions, please inform our sales department.
• Be sure to check that the power is turned off when cleaning this instrument.
• Use a soft and dry cloth when cleaning the instrument.
(If paint thinner is used, it might deform or tarnish the unit.)
• As the display section is vulnerable, do not strike or scratch it with a hard object.
•
Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
•
Shinko Technos is not liable for any damages or secondary damages incurred as a result of
using this product, including any indirect damages.
1. Model name
1.1 Model name
DCL-3 3 A-
/ ,
Series name: DCL-300 (W22.5 x H75 x D100mm)
Control action
3
PID
Alarm A
Alarm action is selectable by key operation *1
Control output R
Relay contact: 1a
S
Non-contact voltage (for SSR drive): 12
+2
,
-0
Vdc
A
DC current: 4 to 20mAdc
Input M
Multi-range *2
Option
W (5A)
Heater burnout alarm
CT rated current: 5A
W (10A) CT rated current: 10A
W (20A) CT rated current: 20A
W (50A) CT rated current: 50A
C5 Serial communication Based on EIA RS-485
*1: Alarm action (9 types and no alarm) and Energized/Deenergized are selectable by key operation.
*2: Thermocouple, RTD, DC current and DC voltage are selectable by key operation.
1.2 How to indicate model name label
Model name label is on the right side of the case and the bottom of the inner assembly.
In the case of Heater burnout alarm output, CT rated current value is written in the bracket ( ).
Model name ----------------------------------
Option ------------------------------------------
Option ------------------------------------------
Instrument No. (Inner assembly only)--
DCL-33A-R/M Relay contact output/ Multi-range input
Heater burnout alarm output
W (20A)
No. XXXXXX

2
2. Name and functions of the sections
(1) Event (EVT) output action indicator
A red LED lights when Event output [Alarm, Loop break alarm or Heater burnout alarm (Option)]
is ON.
(2) Control output (OUT) action indicator
A green LED lights when the control output (OUT) is ON.
(3) Serial communication output indicator
A yellow LED blinks while serial communication TX (sending) is output.
(4) PID auto-tuning action indicator
A yellow LED blinks while PID auto-tuning is performing.
(5) PV display
Indicates actual temperature (PV) with a Red LED.
(6) SV display
Indicates setting value (SV) with a Green LED.
(7) key
Increases numeric value on the SV display or switches the selected item.
(8) key
Decreases numeric value on the SV display or switches the selected item.
(9) key
Changes the setting mode or registers setting value and the selected value.
(Resisters the setting value and selected value by pressing the key.) (Fig. 2-1)
(10) key
Selects the setting item with the key.
3. Operation
The sensor input character and temperature unit are indicated on the PV display for approx. 3
seconds after the power is turned on, and the rated scale maximum value is indicated on the
SV display. (Table 3.1-1)
(If the other value is set in the scaling high limit value, it is indicated on the SV display.)
During this time all outputs and the LED indicators are on their OFF status. After a while
control starts indicating actual temperature on the PV display and setting value on the SV display.
(Table 3.1-1)
Input Scale range Resolution
M
K 0 to 1370 0 to 2500 1 ( )
0.0 to 400.0 0.0 to 750.0 0.1 ( )
J 0 to 1000 0 to 1800 1 ( )
R 0 to 1760 0 to 3200 1 ( )
S 0 to 1760 0 to 3200 1 ( )
B 0 to 1820 0 to 3300 1 ( )
E 0 to 800 0 to 1500 1 ( )
T -199.9 to 400.0 -199.9 to 750.0 0.1 ( )
N 0 to 1300 0 to 2300 1 ( )
PL-II 0 to 1390 0 to 2500 1 ( )
C(W/Re5-26)
0 to 2315 0 to 4200 1 ( )
Pt100 -199.9 to 850.0 -199.9 to 999.9 0.1 ( )
-200 to 850 -300 to 1500 1 ( )
JPt100 -199.9 to 500.0 -199.9 to 900.0 0.1 ( )
-200 to 500 -300 to 900 1 ( )
4 to 20mA -1999 to 9999 *1, *2 1
0 to 20mA -1999 to 9999 *1, *2 1
0 to 1V -1999 to 9999 *1 1
*1: Scale range and
decimal point place
can be selected
*2: Needs to connect 50
shunt resistor (separately
sold) between input
terminals.
(1)
(2)
(5)
(6)
(3)
(4)
(7)
(8)
(9)
(10)

3
3.1 Operation flow chart
PV/SV display mode (Approx. 3s) Control output MV indication
+ + (Approx. 3s) + (Approx. 3s)
[Main setting mode] [Sub setting mode] [Auxiliary function setting mode 1] [Auxiliary function setting mode 2]
Main setting
[ ] PID auto-tuning Perform/Cancel
[ ] Setting value lock selection
[ ] Sensor selection
[ ]
Proportional band setting
[ ] Sensor correction setting
[ ] Scaling high limit setting
[ ]
Integral time setting
[ ] Instrument No. setting
[ ] Scaling low limit setting
[ ]
Derivative time setting
[ ] Data transfer rate selection
[ ] Decimal point place selection
[ ]
Anti-reset windup setting
[ ] PV filter time constant setting
[ ]
Proportional cycle setting
[ ] Control output high limit setting
[ ]
Manual reset setting
[ ] Control output low limit setting
[ ]
Alarm setting
[ ] Control output ON/OFF action
hysteresis [ ]
Heater burnout alarm setting
[ ] Alarm action selection
[ ]
Loop break alarm time setting
[ ] Alarm action
Energized/Deenergized [ ]
Loop break alarm action span
setting [ ] Alarm HOLD function selection
[ ]
Alarm hysteresis setting
[ ]
Alarm action delayed timer
setting [ ]
Setting value digital transmission
bias setting [ ] Direct/Reverse action selection
[ ]
Controller/Converter function
selection [ ] AT bias setting
[ ]
•
+ : Press the key while the key is being pressed.
•
+ (Approx. 3 seconds): Press the key while the key is being pressed.
•
+ (Approx. 3 seconds): Press the key while the key is being pressed.
For setting and selecting in each setting mode, press or key.

4
3.2 Main setting mode
Character
Name, Description, Setting range
Initial value
Main setting
• Set the value for controlled objects.
•
Scaling low limit setting value to Scaling high limit setting value
(Decimal point place follows the selection for DC current input)
M: 0
3.3 Sub setting mode
Character
Name, Description, Setting range
Initial value
PID auto-tuning Perform/Cancel
• Performs
PID auto-tuning. However when PID auto-tuning does
not finish after 4 hours it started, PID auto-tuning is shut down
compulsory.
•
PID cancellation :
PID auto-tuning performing:
Proportional band setting
• Sets the p
roportional band.
•
ON/OFF action when setting the value to 0.0
•
0.0 to 110.0%
2.5%
Integral time setting
•Sets the
integral time.
•
Setting the value to 0 disables this function.
• This
setting item is not indicated for ON/OFF action.
•
0 to 1000 seconds
200 seconds
Derivative time setting
• Sets the derivative time.
•
Setting the value to 0 disables this function.
•This
setting item is not indicated for ON/OFF action.
•
0 to 300 seconds
50 seconds
Anti-reset windup setting
• Sets
anti-reset windup.
• This
setting item is indicated only for PID action.
•
0 to 100%
50%
Proportional cycle setting
• Sets the proportional cycle value for the control output
(OUT).
• This
setting item is not indicated for ON/OFF action or DC
current output.
•
1 to 120 seconds
R : 30
seconds
S : 3 seconds
Manual reset setting
• Sets the resetting value manually.
•This
setting item is indicated only for P and PD action.
•
Proportional band converted value (In the case of DC voltage
and current input, decimal point place follows the selection.)
M: 0.0
Alarm setting
• Sets the action point for the alarm output.
•
Setting the value to 0 or 0.0 disables this function.
(excluding Process high and Process low alarm)
When Loop break alarm and Heater burnout alarm are applied
together, the output is common.
•
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
•
See (Table 3.3-1). (In the case of DC voltage and DC current
input, decimal point place follows the selection.)
M: 0

5
Character
Name, Description, Setting range
Initial value
Heater burnout alarm setting
• Sets the heater current value for
Heater burnout alarm.
•
Setting the value to 0.0 disables this function.
• Self-holding is not available for the alarm output.
When
alarm and Loop break alarm are applied together,
the output is common.
•
This setting item is not indicated when [Option: W] is not added.
• Rating
5A : 0.0 to 5.0A
Rating
20A: 0.0 to 20.0A
Rating
10A: 0.0 to10.0A
Rating
50A: 0.0 to 50.0A
0.0A
Loop break alarm time setting
•Sets the time to assess the Loop break alarm.
• Setting the value to
0 disables this function.
• When
alarm and Heater burnout alarm are applied together,
the output is common.
•
0 to 200 minutes
0 minutes
Loop break alarm action span setting
•Sets the action span to assess the Loop break alarm.
•Setting the value to
0 disables this function.
•When
alarm and Heater burnout alarm are applied together,
the output is common.
•
Thermocouple and RTD input
0 to 150 ( ) or 0.0 to 150.0 ( )
DC voltage and DC current input
0 to 1500 (Decimal point place follows the selection)
M: 0
(Table 3.3-1)
Alarm action type Setting range
High limit alarm -(Scaling span) to Scaling span -side minimum
setting value
-199.9 or -1999
+side maximum
setting value
999.9 or 9999
Low limit alarm -(Scaling span) to Scaling span
High/Low limits alarm 0 to Scaling span
High/Low limit range alarm 0 to Scaling span
Process high alarm Scaling low limit setting value to high limit value
Process low alarm Scaling low limit setting value to high limit value
High limit alarm w/standby -(Scaling span) to Scaling span
Low limit alarm w/standby -(Scaling span) to Scaling span
High/Low limits w/standby 0 to Scaling span
3.4 Auxiliary function setting mode 1
Character
Name, Description, Setting range
Initial value
Setting value LOCK designation
• Locks
the setting value to prevent setting errors.
The setting item to be locked is dependent on the designation.
• PID
auto-tuning cannot be carried out when Lock1 or Lock2
is selected.
•
(Unlock): All setting values can be changed.
(LOCK 1): None of setting values can be changed.
(LOCK 2): Only main setting mode can be changed.
Unlock
(LOCK 3): All setting values can be changed except Controller/Converter
function selection. However they return to their former value
after power is turned off because they are not saved in the
non-volatile memory. (Be sure to select LOCK 3 when using
with PC-900 [SVTC attached])

6
Sensor correction setting
• Sets the sensor correction value of the sensor.
•
Thermocouple and RTD input: -100.0 to 100.0 ( )
DC voltage and DC current input: -1000 to 1000 (Decimal point
place follows the selection.)
M: 0.0
Instrument number setting
• Sets the instrument number individually to each instrument
when connecting multiple instruments via serial communication.
•
This setting item is indicated only when [Option: C5] is added
•
0 to 95
0
Data transfer rate selection
•
Selects the data transfer rate to meet the rate of host computer.
•
This setting item is indicated only when [Option: C5] is added
•
2400bps: , 4800bps: , 9600bps: , 19200bps:
9600bps
3.5 Auxiliary function setting mode 2
Character
Name, Description, Setting range
Initial value
• Selects the
sensor type and temperature unit. K (0 to 1370 )
Input Character
K 0 to 1370 : 0 to 2500 :
0.0 to 400.0 : 0.0 to 750.0 :
J 0 to 1000 : 0 to 1800 :
R 0 to 1760 : 0 to 3200 :
S 0 to 1760 : 0 to 3200 :
B 0 to 1820 : 0 to 3300 :
E 0 to 800 : 0 to 1500 :
T -199.9 to 400.0 :
-199.9 to 750.0
:
N 0 to 1300 : 0 to 2300 :
PL- 0 to 1390 : 0 to 2500 :
C(W/Re5-26)
0 to 2315 : 0 to 4200 :
Pt100 -199.9 to 850.0 :
-199.9 to 999.9
:
-200 to 850 : -300 to 1500 :
JPt100 -199.9 to 500.0 :
-199.9 to 900.0
:
-200 to 500 :
-300 to 900 :
4 to 20mA -1999 to 9999:
0 to 20mA -1999 to 9999:
0 to 1V -1999 to 9999:
Scaling high limit setting
• Sets the scaling high limit value.
• Scaling low limit
setting value to Input range maximum value
(DC voltage and current input: Decimal point place follows the
selection.)
M: 1370
Scaling low limit setting
•Sets the scaling low limit value.
• Input
range minimum value to Scaling high limit setting value
(When DC voltage and DC current input,decimal point place
follows the selection.)
M: 0
Decimal point place selection
• Selects the decimal point place.
However, when thermocouple or RTD input is selected in
sensor selection, this setting item is not indicated.
• No decimal point
to the 3
rd
digit after decimal point
Decimal
point omitted

7
Character
Name, Description, Setting range
Initial value
PV filter time constant setting
• Sets the
PV filter time constant.
If the setting value is too large, it affects control result due to
the response delay.
•
0.0 to 10.0 seconds
0.0 seconds
Control output high limit setting
•Sets the control output high limit value.
• This setting item is not indicated when
ON/OFF action.
• Control output low limit
to 105%
Setting greater than 100% is effective to DC current output type
100%
Control output low limit setting
• Sets the control output low limit value.
• This
setting item is not indicated during ON/OFF action.
•
-5% to control output high limit
Setting less than 0% is effective to DC current output type.
0%
Control output ON/OFF action hysteresis setting
• Sets the
ON/OFF action hysteresis for the control output.
•
This setting item is indicated only for ON/OFF action (P=0)
•
Thermocouple and RTD input: 0.1 to 100.0 ( )
DC voltage and current input: 1 to 1000
(Decimal point place follows the selection.)
M: 1.0
Alarm action selection
• Selects alarm action type.
No alarm :
High limit alarm :
Low limit alarm :
High/Low limits alarm :
High/Low limit range alarm :
Process high alarm :
Process low alarm :
High limit alarm w/standby :
Low limit alarm w/standby :
High/Low limits alarm w/standby :
No alarm
Alarm action Energized/Deenergized
• Selects alarm action Energized/Deenergized.
•
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
•
Energized:
Deenergized:
Energized
Alarm HOLD function selection
• Selects whether alarm HOLD function is [Used] or not.
If alarm HOLD function is set to used, once the alarm
functions alarm output remains until the power is turned off.
•
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
• Alarm
HOLD [Not used]:
Alarm
HOLD
[Used]
:
Alarm HOLD
[Not used]
Alarm hysteresis setting
• Sets the alarm hysteresis.
•
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
•
Thermocouple and RTD input : 0.1 to 100.0 ( )
DC voltage and DC current input: 1 to 1000 (Decimal point
place follows the selection.)
M: 1.0

8
Alarm hysteresis
ON
OFF
Main setting +Alarm setting point
△
Alarm action delayed timer setting
• Sets the alarm action delayed time. Alarm output activates
when the setting time has passed after the input enters alarm
output range.
•
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
•
0 to 9999 seconds
0 seconds
Direct/Reverse selection
• Selects reverse (heating) or direct (cooling) control action.
• Reverse
(Heating) action:
Direct (Cooling) action :
Reverse
(Heating) action
AT bias setting
• Set the
PID auto-tuning bias value.
•
This setting item is not indicated when DC voltage or current
input is selected in [Sensor selection] and when action is not
PID, either.
•
0 to 50 (0 to 100 ) or 0.0 to 50.0 (0.0 to 100.0 )
20
Setting value digital transmission bias setting
• The desired value is the value that adds the one set in the
setting item to the received value by setting value digital
transmission.
•
This setting item is indicated only when [Option: C5] is added.
•
20% of scaling span (DC voltage and DC current: Decimal
point place follows the selection.)
0
Controller/ Converter function selection
• Selects
controller or converter function.
• This setting item is indicated only when the control output
is DC current output type.
• Controller function:
, Converter function:
Controller
function
Sensor correction function
This corrects the input value from the sensor. When a sensor cannot be set at a location where control
is desired, the sensor measuring temperature may deviate from the temperature in the controlled location.
When controlling with multiple controllers, the accuracy of the sensors has influence on the control.
Therefore, sometimes the measuring temperature (input value) does not concur with the same setting value.
In such case the control can be set at the desired temperature by shifting the input value of the sensors.
Loop break alarm
The alarm will be activated when the process variable (PV) does not rise as much value as the span or
greater within the time it takes to assess the Loop break alarm after the manipulated variable has reached
0% or the output low limit value. When the control action is Direct (Cooling), the alarm acts conversely.
Energized/Deenergized function
[If temperature alarm action Energized is selected]
When the alarm output indicator is lit, the alarm output (between terminal 8 and 9) is conducted (ON).
When the alarm output indicator is unlit, the alarm output is not conducted (OFF).
[If temperature alarm action Deenergized is selected]
When the alarm output indicator is lit, the alarm output (between terminal 8 and 9) is not conducted (OFF).
When the alarm output indicator is unlit, the alarm output is conducted (ON).
High limit alarm (Energized setting) High limit alarm (Deenergize setting)
(Fig. 3.5-1) (Fig. 3.5-2)
ON
OFF
Main setting
△
+Alarm setting point
Alarm hysteresis

9
3.6 Control output manipulated variable indication
Name and Description
Control output manipulated variable indication
Press the key for approx. 3 seconds during PV/SV indication mode.
Keep pressing the key until the output manipulated variable shows up, though the main
setting mode appears during the process.
(The control output manipulated variable is indicated on the SV display and the decimal point at
the second digit blinks in 0.5 seconds cycle.)
Pressing the key again, it reverts to the PV/SV mode.
4. Converter function
The converter function of this instrument converts each input (Thermocouple, RTD, DC voltage and
DC current input) value to 4 to 20mA and outputs taking advantage of the control parameter of the controller.
When this instrument is used as a converter, follow the process (1) to (7) described below.
When the process (1) to (7) is finished, this can be used as a converter.
(1): Wire and connect this instrument. (Power, Input and Output)
(2): Turn the power of this instrument ON.
(3): Call the “Auxiliary function setting mode 2” pressing the and key (for approx 3s).
(4): Select the sensor type from “Sensor selection” ( )”.
(5): Set the high limit of the value which is going to be converted from “Scaling high limit setting ( )”.
(6): Set the low limit of the value which is going to be converted from “Scaling low limit setting ( )”.
(7): Select converter ( ) from “Control/ Converter” function selection ( )”.
• Outputs the input from scaling low limit setting value to high limit value in 4 to 20mA.
The ratio of the changing quantity resolution is 1 to 1000 to scaling span.
• When functioning alarm action by Converter function, set the alarm action to Process
alarm action.
If converter function is selected from “Controller/Converter function selection” in auxiliary function
setting mode 2, the parameter below is automatically set. (Table 4.1-1)
But this is applied only to the DC current output type.
(Table 4.1-1)
Setting item Setting value Setting item Setting value
Main setting Scaling low limit Alarm setting 0
Proportional band setting 100.0% Loop break alarm time setting 0 seconds
Integral time 0 seconds Loop break alarm action span 0
Derivative time 0 seconds Direct/Reverse action selection Direct action
Manual reset setting 0.0
• How to fine-tune DC current output (4 to 20mA)
Carry out zero, span adjustment from zero side several times.
Carry out adjustment set by manual reset.
(1) Input the value so that the same scaling low limit value may be indicated on the PV display.
(2) Adjust the value so that the DC current output value may become 4mA by increasing
and decreasing manual reset value. Output decreases when manual reset value is set
to+ side, on the other hand output increases when it is set to – side.
Carry out adjustment of span in the proportional band
(1) Input the value so that the same scaling high limit value may be indicated on the PV display.
(2) Adjust the value so that the DC current output value may become 20mA by increasing
and decreasing manual reset value. Output decreases when proportional band value
is set to + side, on the other hand output increases when it is set to – side.
Caution
When shifting from converter function to controller function, the control parameter and values set by
converter function are held as they are even if the function is switched to controller function.
So, correct the control parameter and values set by converter function to the value necessary to the
controller function after switching to the controller function.

10
5. Running
When mounting and wiring to the control panel (DIN rail) are finished, running starts following the next
procedure.
(1) Turn the power supply to the DCL-33A ON.
For approx. 3s after power on, the character of the sensor type and temperature unit are indicated
on the PV display, and the rated maximum value is indicated on the SV display. See [Table 3.1-1].
(If any other value is set at the main setting value high limit setting, SV display indicates it.)
During this time, all outputs and LED indicators are in their OFF status.
After that PV display indicates actual temperature and SV display indicates the main setting value.
(2) Input the setting value.
Input each setting value referring to “3. Operation”.
(3) Turn the load circuit power ON.
Starts control action so as to keep temperature of the controlled object at the main setting value.
6. Other functions
(1) Power failure countermeasure.
Backs up the setting data in non-volatile IC memory.
(2) Self diagnosis
The CPU is monitored by a watchdog timer and when any abnormal status is found on the CPU,
the controller is switched to warm-up status.
(3) Automatic cold junction temperature compensation (Only thermocouple input)
Detects the temperature at the connection terminal between thermocouple and instrument and
keeps it on the same status at which the reference junction is located at 0 (32 ).
(4) Sensor burnout (Burnout)
When thermocouple or RTD input is burnt out, control output is turned OFF (DC current output
type: control output low limit) and “ ” blinks on the PV display.
When DC voltage and DC current input are burnt out, the status is as follows.
When DC current input (4 to 20mA) and DC voltage input (1 to 5V) are burnt out “ ” blinks
on the PV display.
When DC voltage input (0 to 1V) is burnt out, “ ” blinks on the PV display.
When DC current input (0 to 20mA) is burnt out, the same value at 0mA is indicated.
When DC current input (0 to 10V) is burnt out, a value close to 0V is indicated.
(5) Input burnout indication
Thermocouple, RTD input
If the PV value exceeds [input range high limit + (50 or 100 )], “ ” blinks on the PV display
and control output is turned OFF (DC current output type: control output low limit setting value).
However, in the case of the range with a decimal point when PV exceeds 999.9 ( ), “ ” blinks
and control is carried out until the value becomes [Input range high limit + (50 or 100 )] or greater.
DC voltage and current input
If the PV value exceeds [scaling high limit value + (scaling span x 10% or greater)], “ ” blinks
on the PV display and the control output is turned OFF (DC current output type: control output low
limit setting value).
However, when PV value exceeds 9999, “ ” blinks on the PV display and control is carried out
until the value becomes [Scaling high limit + (scaling span x 10%)] or greater.
Thermocouple input
If the PV value exceeds [input range high limit - (50 or 100 )], “ ” blinks on the PV display
and control output is turned OFF (DC current output type: control output low limit setting value).
However, in the case of the range with a decimal point when PV exceeds -199.9 ( ), “ ”
blinks and control is carried out until the value becomes [-199.9- (50 or 100 )] or less.
RTD input
If the PV value exceeds [Input range low limit – (input span x 1)] “ ” blinks on the PV display
and control output is turned OFF (DC current output type: control output low limit setting value).
However, in the case of the range with a decimal point when PV exceeds -199.9 ( ), “ ”
blinks and control is carried out until the value becomes [-199.9- (input span x 1%)] or less.
DC voltage and current input
If the PV value exceeds [Scaling low limit value – (scaling span x 1%)] “ ” blinks on the PV
display and control output is turned OFF (DC current output type: control output low limit setting value).
However if the PV value exceeds –1999, “ ” blinks on the PV display and control is carried out until
the value becomes [Scaling low limit value setting value – (scaling span x 1%)] or less.

11
7. Action explanations
7.1 Standard action
7.2 ON/OFF action
part: Acts ON or OFF
Action Heating (reverse)action
Control action
Cycle action according to deviation
Relay contact
output
Non-contact
voltage output
Current output
Indicator (OUT)
Green Lit Unlit
ON
OFF
Main setting
Proportional band ON
OFF
0Vdc 0Vdc12/0Vdc
+
-
0/12Vdc12Vdc 12Vdc
+
-
20mAdc 20 to 4mAdc 4mAdc 4mAdc 4 to 20mAdc 20mAdc
Cooling (direct)action
Proportional band
Cycle action according to deviation
Cycle action according to deviation
Cycle action according to deviation
Cycle action according to deviation
Cycle action according to deviation
Unlit Lit
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
+
-
+
-
Main setting
part: Acts ON or OFF.
Action Heating (reverse) action Cooling (direct) action
Control action
Relay contact
output
Non-contact
voltage output
Current output
Indicator(OUT)
Green Lit Unlit
0Vdc
+
-
0Vdc
+
-
12Vdc
+
-
12Vdc
+
-
20mAdc
+
-
4mAdc
+
-
4mAdc
+
-
20mAdc
+
-
ON
OFF
ON
OFF
Hysteresis
Unlit Lit
Hysteresis
Main setting
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
3
4
Main setting

12
7.3 Alarm action
7.4 Heater burnout alarm action
Heater burnout
Alarm action
UnlitLit
ON
OFF
Heater burnout alarm
setting point
Load current
LargeSmall
Indication
(HB)
Red
High limit alarm
Alarm
action
Alarm
output + side
- side
High/Low limits alarm
High/Low limit range alarm
Low limit alarm
Process high alarm Process low alarm
High limit alarm with standby High/Low limit range alarmLow limit alarm with standby
OFF
ON
- Alarm setting
point
Alarm hysteresis
Main
setting + Alarm setting
point
OFF
ON
Main
setting
Alarm setting
point
OFF
ON
Alarm hysteresis
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Alarm
action
Alarm
action
Alarm
output
Alarm
output
Alarm hysteresis
+ Alarm setting
point
Main
setting
- Alarm setting
point Alarm setting
point
+ side
- side
Alarm hysteresis Alarm hysteresis Alarm hysteresis
Alarm hysteresis Alarm hysteresis Alarm hysteresis
Alarm setting
point
Alarm setting
point
Alarm setting
point
Alarm setting
point Main
setting
Main
setting
- Alarm setting
point + Alarm setting
point - Alarm setting
point Main
setting + Alarm setting
point Alarm setting
point Alarm setting
point
Main
setting
+ side
- side
+ side
- side
:Event (EVT) output terminal 8 and 9 is ON
: Standby function works here.
Event (EVT) output indicator lights when output terminal between 8 and 9 is ON, goes out when OFF
:Event (EVT) output terminal 8 and 9 is ON or OFF
:Event (EVT) output terminal 8 and 9 is OFF
:Event(EVT)output terminal between 8 and 9 is ON
:Event(EVT)output terminal between 8 and 9 is OFF
Event (EVT) output indicator lights when output terminal between 8 and 9 is ON, goes out when OFF

13
8. PID auto-tuning of the DCL-33A
In order to decide each P, I, D value and ARW automatically, this system gives a fluctuation
to the controlled object to get a optimal value.
3 types of fluctuation below are automatically selected.
[ When the difference between setting value and processing temperature is large in rising]
When AT bias is set to 20 ( ), a fluctuation is given at the temperature 20 ( ) lower than the setting value.
[When control is stable]
A fluctuation is given at the setting value.
[ When the difference between the setting value and processing temperature is large when
temperature falls]
When AT bias is set to 20 ( ), a fluctuation is given at the temperature 20 ( ) higher than the setting value.
Setting
value
Temp.
Time
AT
(1) (2) (3)
Temperature 20 ( ) lower
than the setting value
(4)
:
AT
Auto-tuning starting point
Calculating PID constant
PID contatnt calculated
Controlled by the PID
constant set by auto-tuning.
AT bias setting value
(1):
(2):
(3):
(4):
Temp.
Time
AT
(1) (2) (3)
:
AT
Auto-tuning starting point
Setting
value
Calculating PID constant
PID constant calculated
Controlled by PID constant
set by auto-tuning
(3):
(2):
(1):
Setting
value
Temp.
Time
AT
(1) (2) (3)
:AT
Auto-tuning starting point
(1): Calculating PID constacnt
(2): PID constant calculated
(3): Controlled by PID constant
set by auto-tuning
(4): AT bias setting value
(4)
Temperature 20 ( ) higher
than the setting value

14
9. Mounting to the control panel
9.1 Site selection
[Use this instrument in the following environment (IEC61010-1)]
• Overvoltage category
, Pollution degree 2
[Use this instrument under the conditions below.]
•
A minimum of dust, and an absense of corrosive gasses
•
No flammable, expolsive gasses
•
Few mechanical vibrations or shocks
•
No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 )
•
An ambient non-condensing humidity of 35 to 85%RH or less
•
The units away from large capacity electromagnetic switches or cables
•
No water, oil or chemicals or where the vapors of these substances can come
into direct contact with the unit.
9.2 External dimension
(Fig.9.2-1)
9.3 CT (Current transformer) External dimension
CTL-6-S (for 20A) CTL-12-S36-10L1 (for 50A)
(Fig.9.3-1)
9.4 Mounting to DIN rail
Caution
Mount the DIN rail horizontally.
When DIN rail is mounted vertically, be sure to use commercially available fastening plates at the end of
DCL-33A. Mount the DCL-33A to the DIN rail so that the DCL-33A cannot move.
However, if the DIN rail is mounted horizontally in a position susceptible to vibration or shock, the fastening
plates must be used as well.
22.5
75
97
100 4
DIN rail

15
* Recommended fastening plate
Omron corporation End plate PFP-M
IDEC corporation DIN rail stops BNL6, BNL8
Matsushita electric works, LTD Fastening plate ATA4806
(1) Hook (1) of DCL-33A on the upper side of the DIN rail. (Fig. 9.4-1)
(2) Making the (1) part of the DCL-33A as a support, fit the lower part of the DCL-33A to the DIN rail.
DCL-33A will be completely fixed to DIN rail with a “Click” sound. (Fig.9.4-1)
(Fig.9.4-1)
10. Wiring
Warning
Turn the power supplied to the instrument OFF before wiring or checking.
Working or touching the terminal with the power switched ON may result in an
Electric Shock which could cause severe injury or death.
Caution
• Do not
drop wire chips into DCL-33A when wiring, because they could cause fire, malfunction and trouble
• Insert the connecting cable into the designated connector securely to prevent malfunction, or it
may cause malfunction due to imperfect contact.
• Connect the AC power wiring to the designated terminal as is written in this Instruction manual, or
it may burn and damage
DCL-33A.
• Tighten
the terminal screw with the specified torque, o
r damage the terminal screw and deform the case.
• Use thermocouple
and compensating lead wire that fit sensor input specification of this unit.
• Use 3-wire RTD that fits sensor input specification of this unit.
• Do not
confuse the polarity when using DC voltage and current input in the case 24Vdc is used.
• Keep
input wire (Thermocouple, RTD) away from power source and load wire when wiring.
• To prevent the unit from harmful effects of the unexpected level noise, it is recommended that a
surge absorber to be installed between the electromagnetic switch coils.
• This
unit has neither built-in power switch nor fuse. Therfore it is necessary to install them in the circuit
near the external unit.
(Recommended fuse: Rated voltage 250Vac,Rated current: 2A,Fuse type: Time-lag fuse)
(1)
(2)

16
* Note
Tighten the terminal screw properly referring to the table below.
Terminal screw
Terminal No.
Torque
M2.6 (1) to (4) Max. 0.5N・m
M2.0 (5) to (9) Max. 0.25N・m
•
Terminal arrangement
(Fig.10-1)
•
R/ : Relay contact output
•
S/ : Non-contact DC voltage output
•
A/ : DC current output
•
Event output (Open collector output)
Outputs when alarm, Loop break alarm or
Heater burnout alarm [Option] is ON.
(Fig.10-2)
• Option: Heater burnout alarm output
This alarm is not available for detecting current under
phase control.
Use the current transformer (CT) provided, and pass
a lead wire of the heater circuit into a hole of the CT.
When wiring, keep the CT wire away from any AC
source or load wires to avoid the external interference.
(Fig.10-3)
11. Specifications
11.1 Standard specifications
Model name DIN rail mounting type indicating controller
Mounting method DIN rail mounting method
Setting method Membrane sheet key
Display PV display: Red LED 4-digit Character size: 7.5 x 4.1mm (H x W)
SV display: Green LED 4-digit Character size 7.5 x 4.1mm (H x W)
24Vac or
100 to 240Vac
Power
24Vdc
(1) (2)
+ - -A/
-S/
-R/
(3) (4)
+ -
(8) (9)(5) (6) (7)
+ - + -
A B B
+ -
TC
RTD
Vdc
mAdc
Event output
(EVT)
(1) (2) (3) (4)
(5) (6) (7)
(5) (6) (7)
CT input socket
Power
supply
Heater
CT
Lower part of main body
CTinputW
Communication
C5
(RS-485)
(1)
(2)
(3)
(4)
(5)
(6)
COM
NC
YA(-)
YB(+)
NC
COM
(1) (6)
(8) (9)
+ -

17
Input Thermocouple: K, J, R, S, E, T, N, PL- , C (W/Re5-26) External resistance: 100 or less
B thermocouple: External resistance: 40 or less
RTD : Pt100, JPt100 3-wire system
Allowable input wire resistance (10 or less per wire)
DC current : 0 to 20mAdc, 4 to 20mA input impedance 50
[Connect 50 shunt resistor (sold separately) between input terminal (5) and (6).]
Allowable input current: 50mA or less
DC voltage : 0 to 1Vdc
Input impedance: 1M or greater
Allowable input voltage: 5V or less
Allowable signal source resistance
: 2k or less
Accuracy (Indicating
•
Setting)
Thermocouple input: Within 0.2% of input span 1 digit or 2 (4 ) whichever is greater
R, S input 0 to 200 (0 to 400 ): Within 6 (12 )
B input 0 to 300 (0 to 600 ): Accuracy is not guaranteed.
RTD input: Within 0.1% of input span 1 digit or within 1 (2 ) whichever is greater.
DC voltage input : Within 0.2% of input span 1 digit
DC current input : Within 0.2% of input span 1 digit
Input sampling period : 0.25 seconds
Control Control action
•
PID action (with auto-tuning function)
•
PI action : When derivative time is set to 0
•
PD action (with manual reset function): When integral time is set to 0
•
P action (with manual reset function) : When derivative and integral time are set to 0
•
ON/OFF action : When proportional band is set to 0
Proportional band: 0.0 to 110.0% [Factory adjusted as 2.5%]
(ON/OFF action when set to 0.0)
Integral time : 0 to 1000 seconds (Off when set to 0) [Factory adjusted as 200 seconds]
Derivative time : 0 to 300 seconds (Off when set to 0)[Factory adjusted as 50 seconds]
Proportional cycle: 1 to 120 seconds [Factory adjusted as -R 30s, -S 3s, -A Not available]
ARW : 0 to 100% [Factory adjusted as 50%]
Manual reset : Proportional band converted value [Factory adjusted as 0.0]
Output limit : 0 to 100% (DC current output type: -5 to 105%)
(Not available for ON/OFF action)
[Factory adjusted as control output low limit setting value 0%
control output high limit setting value100%]
Hysteresis : Thermocouple and RTD input: 0.1 to 100.0 ( )
[Factory adjusted as 1.0 ]
DC voltage and current input: 1 to 1000
(Decimal point place follows the selection.)
[Factory adjusted as 10]
Control output (OUT)
•
Relay contact: 1a Control capacity 250Vac 3A (Resistive load)
250Vac 1A (Inductive load COS =0.4)
Electric life 100,000 times
• Non-contact voltage
(for SSR drive): 12
+2
,
-0
Vdc Max. 40mA (Short-circuit protected)
Shinko SSR (SA-200 series): 4 units connectable parallel
• DC current
: 4 to 20mAdc, Load resistance: Max. 550
Output accuracy: Within 0.3% of output span
Resolution : 12000
Alarm Alarm (EVT) output (Common output with Loop break alarm, Heater burnout alarm [Option: W])
When input exceeds the range in deviation setting (excluding Process alarm) to the main
setting, alarm (EVT) turns ON or OFF (High/Low limit range alarm), and when Deenergized
is selected in Energized/Deenergized selection, alarm (EVT) is activated conversely.

18
Setting accuracy: The same as indicating accuracy
Action: ON/OFF action
Hysteresis: Thermocouple and RTD input: 0.1 to 100.0 ( ) [Factory adjusted as 1.0 ]
DC voltage and current input: 1 to 1000 [Factory adjusted as 10]
(Decimal point place follows the selection.)
Output: Open collector Control capacity 24Vdc 0.1A (Max.)
Alarm (EVT) output action: Alarm action is selectable from below by front key operation.
One alarm is selectable from High limit, Low limit,
High/Low limits, High/Low limit range, Process high,
Process low, High limit w/standby, Low limit w/standby,
High/Low limits w/standby and No alarm action
[Factory adjusted as No alarm action]
Energized/Deenergized : Alarm (EVT) output Energized/Deenergized can be selected.
[Factory adjusted as Energized]
Energized Deenergized
Red (EVT) LED Lights Lights
Alarm output ON OFF
Alarm HOLD function selection: Once the alarm is activated, alarm output is remains
constant until power is turned off.
[Factory adjusted as: Alarm holding function Not used]
Loop break alarm (EVT) output
(Common output with Alarm, Heater burnout alarm [Option: W])
Detects heater burnout, sensor burnout, and abnormality at operation end.
Setting range: Loop break alarm time setting: 0 to 200 minutes
[Factory adjusted as 0 minutes]
Loop break alarm action span setting
Thermocouple and RTD input: 0 to 150 ( ) or 0.0 to 150.0 ( )
[Factory adjusted as 0 ]
DC voltage and current input: 0 to 1500
(Decimal point place follows the selection.) [Factory adjusted as 0]
Output: Open collector Control capacity 24Vdc 0.1A (Max.)
Converter function See “4. Converter function”
Isolation
• Dielectric strength
Circuit isolation structure
* When control output is non-contact
voltage or DC current, between
control output and communication
is not isolated.
Isolated resistance: 10M or greater at 500Vdc except the above
Dielectric strength : 1.5kVac for 1 minute between input terminal and power terminal
1.5kVac for 1 minute between output terminal and power terminal
Power consumption Approx. 6VA
Ambient temperature 0 to 50
Ambient humidity 35 to 85%RH (No condensing)
Weight Approx.150g
External dimension 22.5 x 75 x 100mm (W x H x D)
Material Case: Flame resistant resin
Event output
CT input
Input
(5) (6) (7)
CPU
Isolation
Control output
Power supply
(8) (9)
(1) (2) (3) (4)
Communi-
cation

19
Color Case: Light gray
Attached function Sensor correction, Setting value lock, Power failure countermeasure,
Self-diagnosis, Automatic cold junction compensation, Burnout, Input burnout
Accessories Instruction manual: 1 copy
When [Option: W] is added
Wire harness 3m : 1 set
W (5A), W (10A), W (20A): Current transformer: CTL-6S 1 set
W (50A) : Current transformer: CTL-12-S36-10L1 1 set
11.2 Optional specifications
Heater burnout alarm output (W)
Watches the heater current with CT (Current transformer) and detects the burnout.
When this option is added, alarm output and Loop break alarm will be common.
This option cannot be applied to the current output type.
Rating : 5A [W (5A)], 10A [W (10A)], 20A [W (20A)], 50A [W (50A)] (Must be designated)
Setting range : 5A [W (5A)] 0.0 to 5.0A (Off when set to 0.0)
10A [W (10A)] 0.0 to 10.0A (Off when set to 0.0)
20A [W (20A)] 0.0 to 20.0A (Off when set to 0.0)
50A [W (50A)] 0.0 to 50.0A (Off when set to 0.0)
Setting accuracy : 5% of the rated value
Action : ON/OFF action
Output : Open collector
Control capacity 24Vdc 0.1A (Max.)
Serial communication (C5)
Operates the following from the external computer.
(1) Reading and setting of main setting value, PID and each setting value
(2) Reading of input value and action status
(3) Function change
Communication circuit: Based on EIA RS-485
Communication method: Half-duplex start-stop synchronous
Data transfer rate: 2400, 4800, 9600 or 19200bps is selectable by key operation.
Data format: Start bit-----------------1
Data bit-----------------7
Parity------------------- Even
Stop bit-----------------1
Digital external setting: Receives digital setting value from the PC-900 series [Option: SVTC]
Select Lock3 from the setting value Lock selection.
Setting instrument number is not required.
When data from PC-900 series exceeds scaling high limit or scaling low
limit setting value, this instrument ignores the value and carries out control
at the scaling high limit or scaling low limit setting value.
When the value is set from SVTC bias setting of DCL-33A, the desired value
is the one that adds SVTC bias value to the received value from PC-900
series by external digital setting.
However, if the added value exceeds scaling high limit setting value or scaling
low limit value of the DCL-33A, it ignores the value and carries out control
at the scaling high limit setting value or scaling low limit setting value.

20
12. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power supply and wiring.
Indication
Phenomenon
Presumed cause and solution
“ ” is blinking on the PV
display.
•
Sensor
(Thermocouple, RTD and DC voltage
[0 to 1Vdc] input) is burnt out.
Change the sensor for new one.
• The lead wire of the sensor
(Thermocouple, RTD and DC
voltage [0 to 1Vdc] input ) is not securely connected.
Connect it to the terminal properly.
The indication on the PV display
does not change.
•
Sensor (DC current [0 to 20mAdc] and DC voltage
[0 to 10Vdc]) is burnt out.
Change the sensor for the new one.
• The
lead wire of the sensor (DC current [0 to 20mAdc] and
DC voltage [0 to 10Vdc] is not securely connected to the
terminal.
Connect the sensor lead wire securely to the instrument
terminal.
“ ” is blinking on the PV
display.
•
Sensor
(DC current [4 to 20mAdc] and DC voltage[1 to 5Vdc]
input) is burnt out.
Change the sensor for the new one.
• The sensor lead wire is not securely connected to the
terminal (DC current
4 to 20mAdc) and DC voltage
[1 to 5Vdc]
Connect the sensor lead wire securely to the terminal of
the instrument.
The indication on the PV display
is abnormal or unstable.
•
Designation
of the sensor (input) is incorrect.
Set the correct sensor (input).
• The
polarity of the sensor input is incorrect.
Wire it correctly.
• Temperature unit (
/ ) is mistaken.
Set the correct unit.
• AC
is leaking from controlled object to thermocouple or RTD.
Keep AC from leaking into the controlled object.
“ ” is indicated on the
PV display.
•
Internal memory is out of order.
Please contact our sales branch or the shop where you
purchased this unit.
Key operation
Phenomenon
Presumed cause and solution
• Setting values do not change
even if the or key is
pressed during setting mode
•
Mode1
or mode 2 is selected in setting value lock selection.
Cancel the Lock mode.
•
PID auto-tuning is performing.
Cancel PID auto-tuning.
•
Unable to set the value beyond
or below scaling high limit or low
limit within the rated scale range
even if the or key
is pressed.
•
The
value of scaling high limit setting or low limit setting in
auxiliary function setting mode 2 is set to still one.
Set the proper value.
• If you have any inquiries, please consult our agency or the shop where you purchased the unit.
SHINKO TECHNOS CO.,LTD.
OVERSEAS DIVISION
:
:
:
:
Reg. Office
Mail Address
URL
E-mail
2-48, 1-Chome, Ina, Minoo, Osaka, Japan
P.O.Box 17, Minoo, Osaka, Japan
http://www.shinko-technos.co.jp
overseas@shinko-technos.co.jp Tel :
Fax: 81-727-21-2781
81-727-24-1760
Other manuals for DCL-33A
7
Table of contents
Other Shinko Controllers manuals

Shinko
Shinko ACS-13A User manual

Shinko
Shinko ACD-13A User manual

Shinko
Shinko PCB1 User manual

Shinko
Shinko PCA1 User manual

Shinko
Shinko JCS-33A User manual

Shinko
Shinko JCD-33A-R/M User manual

Shinko
Shinko JCS-33A-R/M T6080 User manual

Shinko
Shinko PCB1 User manual

Shinko
Shinko FCR-13A User manual

Shinko
Shinko BCS2R Series User manual

Shinko
Shinko ACD-15A-R/M User manual

Shinko
Shinko BCD2R User manual

Shinko
Shinko ACS-13A Use and care manual

Shinko
Shinko PCA1 User manual

Shinko
Shinko ACS-13A User manual

Shinko
Shinko JCR-33A User manual

Shinko
Shinko DCL-33A User manual

Shinko
Shinko FCD-13A User manual

Shinko
Shinko ACD-13A Use and care manual

Shinko
Shinko PCD-33A User manual