
20 8011543/YU54/V4-1/2016-04 | SICKOPERATING INSTRUCTIONS | GM700
Subject to change without notice
3PROJECT PLANNING
3.2 Project Planning Checklist
▸Work through the checklist step by step during project planning.
Technical data and dimension drawing, see “Technical Data GM700 Cross-Duct system”,
page 83 and see “Dimension drawing”, page 87 ff.
Topic Task Measure/determination
Determine measuring point.
Observe national regulations
such as VDI 3950.
Provide for unhindered inlet and outlet paths:
●For round duct cross-sections: 3 times the duct diameter
●For rectangular cross-sections: Hydraulic diameter
●If these specifications cannot be met: Inlet section > outlet section,
e.g. 2/
3: 1/3; uniform concentration spread whenever possible.
Emission measuring
point
▸Obtain official approval for emission measuring point.
▸Provide for calibration openings at an easily accessible place.
▸Ensure the GM700 and calibration probe do not influence each
other; the calibration gland should be located at a minimum
distance of 0.5 m away from the measuring device, upstream.
Application conditions ▸Observe Technical Data for duct/ambient conditions!
▸Gas temperature above/below dew point (dry/wet).
Pressure conditions at
the measuring point
▸A fitting location with partial vacuum in the duct is ideal.
▸For duct pressures > 10 mbar, contact SICK on correct selection of
the purge air blower.
SR-unit, reflector
“Installation preparation at the mea-
suring point”, page 22
Select suitable flange
with tube
▸Flange fitting is planned in steel ducts as standard; corresponding
flanges with tube are normally included in the GM700 scope of
delivery.
▸Stone stacks or ducts with thick walls demand an onsite retaining
plate and, possibly, a longer version of the flange with tube; “Install-
ing the flanges with tube”, page 23.
“Dimension drawing flanges with tube (dimensions in mm)”, page 89.
Duct openings
selection
▸Provide an opening of suitable size for the flange tube.
▸Plan adequate clearance for installation and maintenance activities
for the duct insulation cutout.
▸Plan clearances for handling the SR-unit, reflector
▸Ensure the ambient temperature for the SR-unit and/or reflector is
within the specified range.
▸For installation outdoors, plan a weatherproof cover.
Tools for start-up and
maintenance
▸When working on the zero path; prerequisites: Clean ambient
atmosphere free from sample gas; weatherproof: Plan the zero
path or order from SICK.
Purge air unit
“Installation preparation for the
purge air units”, page 26
Fitting location
selection
▸Plan installation location on the duct in immediate vicinity (5 m) of
the GM700 SR-unit.
▸Keep purge air hoses to the respective purge air fixture (SR-unit,
reflector) as short as possible (pressure loss approx. 1.2 mbar per
meter). With only one purge air unit, the hose lengths to both purge
air fixtures should be equal when possible.
▸Allow for secure cable guidance.
▸Ensure dry and, whenever possible, dust-free intake air on the
purge air unit, use a preliminary filter as necessary.
▸The intake air temperature should be between 0 and 55 °C. Heat
the purge air for T < 0 °C; see air heater option (“GM700 options
and accessories”, page 17).
▸For installation outdoors, plan a weatherproof cover.
Table 2: Project Planning Checklist
D4F (Cross-sectional area)
U (Circumference)
-------------------------------------------------------------------------------------=