s SINAMICS PM230 (IP20) Power Module
Getting Started Guide
-1-
Warning
This equipment contains dangerous voltages and controls potentially dangerous
rotating mechanical parts.
The terminals can carry hazardous voltages even after the inverter has been switched
off. After disconnecting the line supply, wait at least 5 minutes until the drive unit has
discharged itself. Only then, carry out any installation work.
Read the instructions in the associated manuals under:
http://support.automation.siemens.com. Non-compliance or failure to follow the
instructions can result in loss of life, severe personal injury or serious damage to
property.
Only suitable qualified personnel should work on this equipment. Qualified persons are
defined as persons who are authorized to commission, ground and label systems and
circuits in accordance with established safety practices and standards.
The successful and safe operation of this equipment is dependent upon its proper
handling, installation, operation and maintenance.
Warnung
Das vorliegende Gerät führt gefährliche Spannungen und steuert rotierende
mechanische Teile, die gegebenenfalls gefährlich sind.
Die Klemmen können auch dann gefährliche Spannungen führen, wenn der Umrichter
außer Betrieb ist. Warten Sie nach dem Unterbrechen der Netzversorgung mindestens
5 Minuten, bis sich das Gerät entladen hat. Führen Sie erst dann Montagearbeiten aus.
Beachten Sie die Hinweise in den zugehörigen Betriebsanleitungen unter:
http://support.automation.siemens.com. Bei Missachtung oder Nichtbefolgen der
Hinweise können Tod, schwere Körperverletzungen oder erheblicher Sachschaden
eintreten.
Inbetriebsetzung und Betrieb dieses Geräts dürfen nur von qualifiziertem Personal
vorgenommen werden. Qualifiziertes Personal sind Personen, welche die Berechtigung
haben, Systeme und Stromkreise gemäß den Standards der Sicherheitstechnik in
Betrieb zu nehmen, zu erden und zu kennzeichnen.
Der einwandfreie und sichere Betrieb des Gerätes setzt sachgemäßen Transport,
ordnungsgemäße Installation, Bedienung und Instandhaltung voraus.
Attention
L' appareil présente des tensions dangereuses et contrôle des pièces mécaniques
rotation potentiellement dangereuses.
Les bornes peuvent présenter des tensions dangereuses, même lorsque le variateur est
à l'arrêt. Après coupure de la tension du réseau, il convient d'attendre au moins 5
minutes pour permettre la décharge de l'appareil. Procéder à une intervention
seulement après écoulement de ce délai.
Respecter les consignes figurant dans les instructions de service correspondantes et
disponibles sous le lien suivant : http://support.automation.siemens.com. Le non-respect
des consignes peut entraîner la mort, des blessures graves ou des dégâts matériels
importants.
La mise en service et l'utilisation de cette machine ne doivent être effectuées que par
des personnes qualifiées. Par personnes qualifiées on entend des personnes autorisées
à mettre en service, mettre à la terre et repérer les systèmes et les circuits électriques
dans le respect des règles de l'art en matière de sécurité.
L'exploitation sûre et sans défaut de l'appareil suppose un transport, un entreposage,
une installation, une conduite et une maintenance dans les règles de l'art.
Avvertenza
Questo apparecchio conduce tensioni pericolose ed aziona parti meccaniche rotanti
potenzialmente pericolose.
I morsetti possono condurre tensioni pericolose anche quando il convertitore è stato
spento. Dopo avere interrotto l’alimentazione di rete, attendere almeno 5 minuti finché
l’apparecchio non si è scaricato. Solo allora si possono eseguire interventi
sull’apparecchio.
Leggere le istruzioni riportate nei rispettivi manuali all’indirizzo:
http://support.automation.siemens.com. In caso di non osservanza o di mancata
applicazione delle istruzioni sussiste la possibilità di morte, gravi lesioni fisiche o ingenti
danni materiali.
Solo personale qualificato può essere addetto alla messa in servizio e al funzionamento
di questo apparecchio. Per personale qualificato si intendono persone autorizzate a
mettere in servizio, mettere a terra e contrassegnare sistemi e circuiti elettrici in
conformità agli standard della tecnica di sicurezza.
Il funzionamento corretto e sicuro dell'apparecchio presuppone un trasporto,
un’installazione, un utilizzo e una manutenzione appropriati.
Advertencia
El presente equipo está sometido a tensiones peligrosas y controla piezas mecánicas
rotación que también pueden ser peligrosas.
Los bornes o terminales de conexión pueden estar también bajo tensión eléctrica
peligrosa incluso aunque el convertidor o variador no esté funcionando. Tras
desconectar la alimentación de red, espere al menos 5 minutos para que el equipo
pueda descargarse. Sólo entonces proceda a realizar los trabajos de montaje.
Respete las indicaciones que se especifican en las instrucciones de servicio asociadas,
y que pueden consultarse en: http://support.automation.siemens.com. Si no se
observan las advertencias o no se siguen las indicaciones de las instrucciones, existe
peligro de muerte, graves lesiones corporales o considerables daños materiales
La puesta en marcha y el funcionamiento de este equipo debe encomendarse
exclusivamente a personal cualificado. Personal cualificado son personas autorizadas
para poner en servicio, conectar a tierra e identificar sistemas y circuitos eléctricos
conforme a las normas en materia de seguridad.
El funcionamiento correcto y seguro del equipo presupone un transporte, instalación,
montaje y puesta en marcha adecuados, así como un manejo y un mantenimiento
rigurosos.
Mounting hole for mounting frame
Panel template and mounting
holes for PT housing
Panel template and mounting
holes for PT housing
Mounting hole for mounting frame
Mounting hole for mounting frame
Cool air
Bottom
Side Side
Top Heated air PM + CU + OP
Power Module (PM)
Width
Height
Cool air
Bottom
Side Side
Top Heated air PM + CU + OP Width
Height
Drill Patterns and Dimensions for PM230 IP20 Power Modules Drill Patterns and Dimensions for PM230 IP20 Push-Through (PT) Power Modules
Push-Through mounting frame
It is recommended that the optional mounting frame
is used to install the Push-through Power Module in
a cabinet. This optional mounting frame is designed,
in conjunction with, the supplied seal to easily
maintain an IP54 rating of the enclosure (the seal is
delivered with the Power Module). If the Power
Module is mounted without using the optional
mounting frame, it is the user's responsibility to
ensure the correct IP protection rating is reached.
Dimensions (mm) Distances (mm)
3)
Frame Size
Height Width Depth
2)
a b c top bottom
FSA filtered /unfiltered 196 73 165 186 62.3 6 80 100
FSB filtered /unfiltered 292 100 165 281 80 6 80 100
FSC filtered /unfiltered 355 140 165 343 120 6 80 100
FSD unfiltered 419
1)
275 204 325 235 11 300 300
FSD filtered 512
1)
275 204 419 235 11 300 300
FSE unfiltered 499
1)
275 204 405 235 11 300 300
FSE filtered 635
1)
275 204 541 235 11 300 300
FSF unfiltered 634
1)
350 316 598 300 11 350 350
FSF filtered 934
1)
350 316 899 300 11 350 350
Fixing: FSA/FSB: Screws M4, 2.5 Nm (22 lbf.in)
FSC: Screws M5, 2.5 Nm (22 lbf.in)
FSD/FSE: Screws M6, 6 Nm (53 lbf.in)
FSF: Screws M8, 13 Nm (115 lbf.in)
1)
plus 123 mm using a screen termination kit
2)
plus 58 mm using a CU230, plus 40 mm using a CU240, plus another 10 mm or 25 mm using a BOP-2 or an IOP as Operator Panel (OP)
3)
The Power Modules can be mounted side-by-side. Due to tolerance reasons, we recommend a lateral distance of about 1 mm
Dimensions (mm)Frame Size
Height Width Depth
2)
D1 D2 a b c d e
FSA filtered /unfiltered 238 125.9 170.8 117.7 53.1 103 106 88 198 27
FSB filtered /unfiltered 345 153.9 170.8 117.7 53.1 147.5 134 116 304 34.5
FSC filtered /unfiltered 410.5 200 170.8 117.7 53.1 123 174 156 365 30.5
Fixing: FSA/FSB/FSC: Screws M5, 6 Nm
1) plus 123 mm using a screen termination kit
2)
plus 58 mm using a CU230, plus 40 mm using a CU240, plus another 10 mm or 25 mm using a BOP-2 or an IOP as Operator Panel (OP).
The Power Modules require a distance of 80 mm above and 100 mm below. They can be mounted side-by-side. Due to tolerance reasons, we
recommend a lateral distance of about 1 mm
D1 D2
PM230 IP20 Push-Through mounting sequence
Mounting Frame
Cabinet
Seal
Mounting Frame
SINAMICS PM230 (IP20) Power Module
Getting Started Guide
Fitting CU to PM
Mains and Motor terminals FSA ... FSC Screening methods
Access to motor and mains terminals FSD ... FSF
Motor and mains terminals FSD ... FSF
Maximum cable lengths
Components for United States / Canadian installations (UL/cUL)
Star and Delta connection
Using Maximum cable
length
EMI Level
Screened cables, filtered units (class A) 25 m Second Environment, C2*
Screened cables, filtered units (class A) 50 m Second Environment, C3*
Screened cables, unfiltered units, 50 m EMI Standard not fullfilled
Unscreened cables, filtered or unfiltered units 100 m EMI Standard not fullfilled
Inside the terminal box of Siemens motors
is a diagram showing both methods of
connections:
● Star connection (Y)
● Delta connection (∆)
The motor rating plate provides information
for each method of connection.
The Power Modules are fitted
with two-part-connectors. The
removable part of the connector
can be unplugged from the
Power Module by pressing the
release catch. The connectors
are not interchangeable.
Tightening torques:
● FSD 6 Nm (53 lbf.in)
● FSE 6 Nm (53 lbf.in)
● FSF 13 Nm (115 lbf.in)
2
1
6
9
2
33
10
5
8
8
12
5
1
7
84 4
①Line connection ⑦Steel band
②Motor connection ⑧Cable strap
③Unshielded cable for line connection ⑨Metal back plate
④Shielded cable for motor connection ⑩ Shielding plate
⑤Cable screen
⑥Suitable clip to fix motor cable screen securely to metal back plate
Standards
European Low Voltage Directive
Europäische Niederspannungsrichtlinie
Directive européene basse tension
Directiva europea “Baja tension”
Direttiva europea sulla bassa tensione
ISO 9001
Siemens plc operates a quality management
system, which complies with the requirements
of ISO 9001
Siemens plc
Industry Sector
Drives Technology
Motion Control Systems
Varey Road
Congleton, CW12 1PH
United Kingdom
© Siemens AG, 2011
Subject to change without prior notice
Printed in the United Kingdom
Issue: 06/2011
*Only if EMC compliant connections are used.
Typical rating label
E060 5/04 96 382 02 001
660-725
44 0-48 0
38 0-420
1LE1 002-1DB 43 - 4 AA0
kW
15
A
Hz
V
690
400
Y
60
50
50
17,1
29, 5
D-91056 Erlangen
3~ Mot.
1/min
co s φeta
89,4%
89,4%
0,8 2
0,8 2
0,8 2
17,3 1760
146 0
A
V
30,0 -30,2
IEC / EN 6 003 4 160L IMB 3 IP55
73 kg
29, 5
15 89,4% 146 0
Bea ri ng
DE
NE 620 9-2ZC3
6209 -2ZC 3
460
17,4-17,5
30,2-29,8
Th.Cl. 155 (F)
Tightening torques:
● FSA 0.4 Nm ... 0.5 Nm (3.5 ... 4.4 lbf.in)
● FSB 0.55 Nm ... 0.6 Nm (4.7 ... 5.3 lbf.in)
● FSC 1.2 Nm ... 1.5 Nm (10.6 ... 13.3 lbf.in)
CAUTION - Cable cross-section for grounding: The earth cable must be at least as big as the power cables.
In order that the system is UL/cUL-compliant, use UL/cUL-certified J-type fuses, overload circuit-breakers or intrinsically
safe motor protection devices. Use class 1 75° C copper wire only. Install the inverter with any external recommended
suppressor with the following features:
● Surge-protective devices; device shall be a Listed Surge-protective device (Category code VZCA and VZCA7)
● Rated nominal voltage 480/277 VAC, 50/60 Hz, 3-phase
● Clamping voltage VPR = 2000 V, IN = 3 kA min, MCOV = 550 VAC, SCCR = 65 kA
● Suitable for Type 1 or Type 2 SPD application
● Clamping shall be provided between phases and also between phase and ground.
Feature Specification
Line voltage
3 AC 380 V … 480 V ± 10% - The permissible voltage depends on the installation altitude
Output voltage
3 AC 0 V … input voltage * 0.95 (max)
Input frequency
50 Hz … 60 Hz, ± 3 Hz
Output frequency
0 Hz … 650 Hz, depending on the control mode
Power factor λ
0.9
Line impedance
Uk ≤1 %, no line reactor must be used
Inrush current
Less than rated input current
Pulse frequency (factory setting)
4 kHz - Can be increased up to 16 kHz (up to 8kHz for 55 kW, 75 kW, 90 kW) in 2 kHz steps. Increasing the pulse frequencies leads to an output current reduction.
Electromagnetic compatibility
Filtered Units are suitable for environmental classes category C2 in accordance with IEC61800-3. For details, see the Hardware Installation Manual, Appendix A2.
Braking methods
DC braking
Protection level
IP20 built-in units
Operating temperature (LO operation)
0 °C … +40 °C (32 °F … 104 °F) without derating / up to 60 °C (140 °F) with derating
Operating temperature (HO operation)
0 °C … +50 °C (14 °F … 122 °F) without derating / up to 60 °C (140 °F) with derating
Storage temperature
-40 °C … +70 °C (-40 °F … 158°F)
Installation altitude above sea level
Up to 1000 m (3300 ft) without derating / Up to 4000 m (13000 ft) with derating
Humidity
< 95% RH - non-condensing
Environmental requirements
Protected according to environmental class 3C2 to EN 60721-3-3 against damaging chemical substances
Pollution
According pollution degree level 2 - Do not install the inverter in an environment which contains atmospheric pollutants such as dust and/or corrosive gases.
Shock and vibration
Do not drop the inverter or expose to sudden shock. Do not install the inverter in an area where it is likely to be exposed to constant vibration.
Electromagnetic radiation
Do not install the inverter near sources of electromagnetic radiation.
Short Circuit Current Rating (SCCR)
65 kA

Other Siemens Control Unit manuals

Siemens ZAM-180 User manual

Siemens

Siemens ZAM-180 User manual

Siemens SIWAREX MS User manual

Siemens

Siemens SIWAREX MS User manual

Siemens SINUMERIK Series Parts list manual

Siemens

Siemens SINUMERIK Series Parts list manual

Siemens SPCW110 User manual

Siemens

Siemens SPCW110 User manual

Siemens SINUMERIK 840D sl User manual

Siemens

Siemens SINUMERIK 840D sl User manual

Siemens ASIsafe SIRIUS 3RK1205-0B.00-0AA2 User manual

Siemens

Siemens ASIsafe SIRIUS 3RK1205-0B.00-0AA2 User manual

Siemens SIMATIC S5 User manual

Siemens

Siemens SIMATIC S5 User manual

Siemens SIMOTION D4x5-2 User manual

Siemens

Siemens SIMOTION D4x5-2 User manual

Siemens SITOP PSE200U 3 A User manual

Siemens

Siemens SITOP PSE200U 3 A User manual

Siemens SIMATIC FM 351 User manual

Siemens

Siemens SIMATIC FM 351 User manual

Siemens WFZ661 Installation and operation manual

Siemens

Siemens WFZ661 Installation and operation manual

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens SITOP modular 6EP1961-3BA20 User manual

Siemens

Siemens SITOP modular 6EP1961-3BA20 User manual

Siemens simatic ET 200MP User manual

Siemens

Siemens simatic ET 200MP User manual

Siemens MXG461B Series Owner's manual

Siemens

Siemens MXG461B Series Owner's manual

Siemens SIMOTION D410 User manual

Siemens

Siemens SIMOTION D410 User manual

Siemens Simatic ET200pro User manual

Siemens

Siemens Simatic ET200pro User manual

Siemens 4AI RTD User manual

Siemens

Siemens 4AI RTD User manual

Siemens RDM-MXL User manual

Siemens

Siemens RDM-MXL User manual

Siemens COM060 User manual

Siemens

Siemens COM060 User manual

Siemens SIRIUS 3SF5811 A Series User manual

Siemens

Siemens SIRIUS 3SF5811 A Series User manual

Siemens Simatic S7-1500 User manual

Siemens

Siemens Simatic S7-1500 User manual

Siemens RUGGEDCOM RS900F User manual

Siemens

Siemens RUGGEDCOM RS900F User manual

Siemens NCU 7x0.3 PN Series User manual

Siemens

Siemens NCU 7x0.3 PN Series User manual

Popular Control Unit manuals by other brands

Emerson Fisher HP instruction manual

Emerson

Emerson Fisher HP instruction manual

Profort multiGuard Master IO Start-up

Profort

Profort multiGuard Master IO Start-up

Supermicro SBI-6119P-C3N user manual

Supermicro

Supermicro SBI-6119P-C3N user manual

Cross Technologies 1586-04-0431 instruction manual

Cross Technologies

Cross Technologies 1586-04-0431 instruction manual

Technische Alternative ESR 31 Operation & installation instructions

Technische Alternative

Technische Alternative ESR 31 Operation & installation instructions

FrSky FWTM instruction manual

FrSky

FrSky FWTM instruction manual

GEM B56 operating instructions

GEM

GEM B56 operating instructions

Vertiv Liebert MBSM user manual

Vertiv

Vertiv Liebert MBSM user manual

claber meteo 8323 manual

claber

claber meteo 8323 manual

Canford 58-321 Technical data sheet

Canford

Canford 58-321 Technical data sheet

Bose ControlSpace CC-64 Safety instructions & install guide

Bose

Bose ControlSpace CC-64 Safety instructions & install guide

Delta DVPEN01-SL Operation manual

Delta

Delta DVPEN01-SL Operation manual

Watermark Reefe rainpro RM1500-2 Installation and operating instructions

Watermark

Watermark Reefe rainpro RM1500-2 Installation and operating instructions

Adani Solar ASP-7-AAA Installation

Adani Solar

Adani Solar ASP-7-AAA Installation

Ensemble Designs Avenue 5030 user guide

Ensemble Designs

Ensemble Designs Avenue 5030 user guide

MTT MS3781 user manual

MTT

MTT MS3781 user manual

Zeta Alarm Limited SmartConnect Multiloop instruction manual

Zeta Alarm Limited

Zeta Alarm Limited SmartConnect Multiloop instruction manual

SMC Networks VQZ 1000 Installation and maintenance manual

SMC Networks

SMC Networks VQZ 1000 Installation and maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.