manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Control Unit
  8. •
  9. Siemens TRI-S User manual

Siemens TRI-S User manual

This manual suits for next models

2

Other Siemens Control Unit manuals

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens SINAMICS S110 User manual

Siemens

Siemens SINAMICS S110 User manual

Siemens FDCI723 User manual

Siemens

Siemens FDCI723 User manual

Siemens V P45 Series User manual

Siemens

Siemens V P45 Series User manual

Siemens SICAM A8000 Series User manual

Siemens

Siemens SICAM A8000 Series User manual

Siemens SIMATIC ET 200SP Technical Document

Siemens

Siemens SIMATIC ET 200SP Technical Document

Siemens AP 641 Service manual

Siemens

Siemens AP 641 Service manual

Siemens ZAM-180 User manual

Siemens

Siemens ZAM-180 User manual

Siemens 3AK User manual

Siemens

Siemens 3AK User manual

Siemens SIMATIC ET 200S User manual

Siemens

Siemens SIMATIC ET 200S User manual

Siemens SINUMERIK 808D Installation guide

Siemens

Siemens SINUMERIK 808D Installation guide

Siemens FS-TRI-M User manual

Siemens

Siemens FS-TRI-M User manual

Siemens 3VM9.88-0LB10 User manual

Siemens

Siemens 3VM9.88-0LB10 User manual

Siemens 3RA2816-0EW20 User manual

Siemens

Siemens 3RA2816-0EW20 User manual

Siemens LOGO! Series User manual

Siemens

Siemens LOGO! Series User manual

Siemens LYC11 User manual

Siemens

Siemens LYC11 User manual

Siemens TSM-1 User manual

Siemens

Siemens TSM-1 User manual

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Siemens XCI2001-U1 Guide

Siemens

Siemens XCI2001-U1 Guide

Siemens SIMATIC RF120C User manual

Siemens

Siemens SIMATIC RF120C User manual

Siemens SIMOTICS CONNECT 600 User manual

Siemens

Siemens SIMOTICS CONNECT 600 User manual

Siemens SINAMICS S120 Quick start guide

Siemens

Siemens SINAMICS S120 Quick start guide

Siemens OCC-1 User manual

Siemens

Siemens OCC-1 User manual

Siemens SIMATIC ET 200SP User manual

Siemens

Siemens SIMATIC ET 200SP User manual

Popular Control Unit manuals by other brands

Festo Compact Performance CP-FB6-E Brief description

Festo

Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

Elo TouchSystems

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation MPC3034A user manual

JS Automation

JS Automation MPC3034A user manual

JAUDT SW GII 6406 Series Translation of the original operating instructions

JAUDT

JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum Air Module System manual

Spektrum

Spektrum Air Module System manual

BOC Edwards Q Series instruction manual

BOC Edwards

BOC Edwards Q Series instruction manual

KHADAS BT Magic quick start

KHADAS

KHADAS BT Magic quick start

Etherma eNEXHO-IL Assembly and operating instructions

Etherma

Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations Attenuverter Assembly guide

PMFoundations

PMFoundations Attenuverter Assembly guide

GEA VARIVENT Operating	 instruction

GEA

GEA VARIVENT Operating instruction

Walther Systemtechnik VMS-05 Assembly instructions

Walther Systemtechnik

Walther Systemtechnik VMS-05 Assembly instructions

Altronix LINQ8PD Installation and programming manual

Altronix

Altronix LINQ8PD Installation and programming manual

Eaton Powerware Series user guide

Eaton

Eaton Powerware Series user guide

WAGO 750-407/040-000 manual

WAGO

WAGO 750-407/040-000 manual

Sony CCU-590 Operation manual

Sony

Sony CCU-590 Operation manual

Graco 25D614 instructions

Graco

Graco 25D614 instructions

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Task Force Tips

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Shini SPV-U Series manual

Shini

Shini SPV-U Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

P/N 315-096242-5
Installation Instructions
Models TRI-S, TRI-D, TRI-R
Addressable Interface Modules
Fire Safety
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN
The SIEMENS Model TRI Series Addressable modules,
shown in Figure 1, interface direct shorting devices to the
MXL System's ALD loop circuit.
Note: The TRI-S/-D/-R Series is not compatible with
the XL3 System or the XLD-1 loop circuit.
The TRI modules are available in three models. The
TRI-S and TRI-R can monitor a normally open or closed
dry contact. The TRI-S model can only monitor and
report the status of the contact, while the TRI-R incor-
porates an addressable Form C relay. The TRI-D is a
dual input module that supervises and monitors two
sets of dry contacts. It requires two address settings.
The TRI has a multi-color LED that flashes green when
operating normally, amber if the unit is in trouble
condition, and red to indicate a change of state. The
TRI-D flashes twice, once for each address. The TRI-R
red LED indicates a change of state in the relay.
PROGRAMMING INSTRUCTIONS
1. Refer to Figure 2 to locate the openings on the TRI
cover that allow access to the programming holes
which are on the TRI printed circuit board.
2. To connect the TRI to the SIEMENS FPI-32
Programmer/Tester, insert the plug from the FPI-32
cable provided with the Programmer/Tester into the
opening on the front of the TRI. Be sure to insert
the locating tab on the plug into the slot for the
locating tab on the TRI as shown in Figure 2.
CAUTION: TO PREVENT DAMAGE TO THE FPI-32,
DO NOT connect a TRI to the FPI-32 until
at least one wire is removed from terminals
1 or 2 of the TRI.
Note: Connection from the FPI-32 to the TRI is keyed.
Refer to Figures 5-8 for the proper connections to
the control panel. Figure 2
Inserting the FPI-32 Cable in the TRI Module
Figure 1
TRI Module
2
3. (Refer to Figure 3.) Follow the instructions in the
FPI-32 Programmer/Tester Manual (P/N 315-
090077) to program the TRI to the following:
a. Desired address
b. Desired application for fire or proprietary
burglary (security)
c. Normally open or normally closed switch
NOTES:
1. There can be any number of normally open switches.
2. The end of line resistor must be located at the last switch.
3. Do not wire a normally closed switch across the end of line
resistor.
Application
FPI-32
Switch Device Use
Fire Alarm Normally Open Alarm
Fire Trouble Normally Open Trouble
Fire Supervisory Normally Open Trouble
Figure 3
Wiring Normally Open Switches
4. Record the device address on the label located on
the TRI front panel. The TRI can now be installed
and wired to the system.
WIRING
(Refer to Figures 4-8)
Refer to the appropriate wiring diagram below and wire
the addressable interface module accordingly.
Note: Recommended wire size:
18 AWG minimum
14 AWG maximum
Wire larger than 14 AWG can damage the
connector.
POWER LIMITED WIRING FOR TRI-R
ADDRESSABLE INTERFACE MODULE
In compliance with NEC Article 760, all power limited
fire protective signaling conductors must be separated
a minimum of 1/4inch from all of the following items
located within an outlet box:
• electric light
• power
• Class 1 or non-power limited fire protective signal-
ing conductors
To meet the above the requirements, the following
guidelines must be observed when installing this
interface module.
NOTE: If power limited wiring is not used within this
outlet box, then the following guidelines do not
apply. In that case, be sure to follow standard
wiring practices.
TRI-R CONTROL MODULE BARRIER
The TRI-R Control Module Barrier must be used when
the TRI-R relay contacts are connected to non-power
limited lines. Install the barrier diagonally into the back-
box to create two separate compartments within the
backbox to separate the wires, as shown in Figure 4.
Backbox
TRI-R Control Module Barrier
TABS
FACE
OUT
Use P/N 330-096393 for
Double Gang Box
Use P/N 330-096384 for
4-inch Square Electrical Box
Figure 4
Installing the TRI-R Control Module Barrier
WIRING ENTERING OUTLET BOX
Power Limited Wiring
All power limited wiring must enter the outlet box
separately from the electric light, power, Class 1, or
non-powered limited fire protection signaling conduc-
tors. For the TRI-R, wiring to terminal block positions 1,
2, 3, 4, and 5 must enter the outlet box separately from
terminals 6, 7, and 8.
IMPORTANT:
Minimize the length of wire
entering the outlet box.
3
WIRING AT THE TERMINAL BLOCKS
Power Limited Wiring (Refer to Figure 5)
Wiring to positions 1, 2, 3, 4, and 5 is power limited.
Non-Power Limited Wiring
Wiring to positions 6, 7, and 8 is considered non-
power limited.
Note: Remove all slack from these wires by pulling
excess wiring back through the holes.
Figure 5
TRI-R Power Limited Wiring
Figure 8
Model TRI-D Wiring
Figure 7
Model TRI-S Wiring
NOTES:
1. All supervised switches must be held closed and/or
open for at least a quarter of a second to guarantee
detection.
2. Use ULI listed EOL Model EL-30/31 mounting plate
with 470 ohms, 1/4W resistor, P/N 140-82016485. Order
Model EL-30/31 separately.
3. The supervised switches have the following ratings:
Voltage maximum: 27 VDC
Current maximum: 3.5mA during polling
Contact resistance maximum: 10 ohms
Maximum cable length: 200 feet (18 AWG)
CLine to line: 0.02uF
CLine to shield: 0.04uF
Max line size: 14 AWG
Min line size: 18 AWG
4. Supervised switch S1 is on the first programmed
address, and Supervised switch S2 is on the second
programmed address.
5. Relay contacts are rated: 4A, 125 VAC resistive
4A, 30 VDC resistive
Inductive: 3.5A, 120 VAC (0.6P.F.)
3.0A, 30 VDC (0.6 P.F.)
2.0A, 120 VAC (0.4 P.F.)
2.0A, 120 VAC (0.35 P.F.)
2.0A, 30 VDC (0.35 P.F.)
The relay is shown in supervisory condition.
Figure 6
Model TRI-R Wiring
Figure 9
Mounting the TRI-S/-R/-D
MOUNTING SLOTS
FOR 4 INCH SQUARE
ELECTRICAL BOX
MOUNTING SLOTS
FOR DOUBLEGANG
ELECTRICAL BOX
MOUNTING
HOLES FOR
SWITCHPLATE
TRI-S/-D/-R
MODULE
P/N 315-096242-5
NOTES (Cont.):
CAUTION
Ground shield wire ONLY at the specified location
on the Control Panel.
6. If a Good Local Earth Ground is Available:
a. Terminal 5 must be connected to earth ground.
b. Use wire nuts to pass the shield wire through the
electrical box with NO connection to the device
terminal block or to local ground.
c. Use shielded wire to connect the switch wiring to the
TRI.
d. Tie the switch wiring shield to the ALD wiring shield.
Do not connect shield to terminal 5 or the local
earth ground.
7. If a Good Local Earth Ground is NOT Available:
Connect shield to terminal 5.
8. If ALD wiring is not shielded, the switch wiring must
be in metal raceway.
9. In supervisory:
TRI-S/-R draws 1.6mA
TRI-D draws 1.6mA
IMPORTANT
Terminal 5 of the TRI-S/-D/-R must be connected
to a known good
earth ground for
proper operation.
If the electrical box the TRI is installed in is
grounded, connect Terminal 5 to same.
MOUNTING
Addressable Interface Models TRI-S, TRI-D, and TRI-R
mount directly into a (user supplied) double gang or 4
inch square electrical box. Fasten the module to the
square box with the switchplate using the 2 screws
provided.
NOTE: Be sure to program the TRI before fastening
the switchplate to the unit.