General User Information
This manual describes how SICAM Q200 communicates with peripheral devices/systems. For detailed device
information, see the device manual.
Communication
The communication interfaces of SICAM Q200 make 4 communication types possible using the corresponding
communication protocols:
•Modbus TCP Server via Ethernet interface
•Modbus RTU (master and slave) via RS485 interface
•Modbus TCP to Modbus RTU Gateway
•IEC 61850 via Ethernet interface
To communicate with control systems and other process automation equipment and to transmit, for example,
operational measured values, metered values, indications, and load profiles, the device provides 2 switchable
Ethernet interfaces and an RS485 interface with 2 connectors for serial communication.
If parameterized accordingly, the device can communicate over the Ethernet interface and simultaneously
over the serial interface. It is possible, for example, to parameterize and retrieve data over the Ethernet inter-
face, while the serial interface handles the protocol traffic with a Modbus slave device.
Communication via Ethernet Interface
The device has 2 Ethernet ports which can be used seperately, or be combined to form a "Daisy-chain".
Via the Ethernet interface the following functions are supported:
•Parameterization, analysis and diagnosis with HTML pages
•DHCP (Dynamic Host Configuration Protocol)1 to assign the network configuration (IP address etc.) to
clients in an Ethernet network with DHCP server
•Time synchronization via NTP
•Data transfer (measured data, metered values, load profiles and indications/events) to connected devices
via Modbus TCP or IEC 61850-Server
•Data transfer to SICAM PAS/PQS for waveform record (COMTRADE IEEE...) and power quality and histor-
ical data (PQDIF IEEE...)
SICAM Q200 supports the following TCP/IP services (TCP/IP protocol stack):
•TCP/IP IPv4
•DHCP client (Dynamic Host Configuration Protocol)
•NTP (Network Time Protocol)
•HTTP
•SNMPv3 (Simple Network Management Protocol)
Communication via RS485 Interface
SICAM Q200 includes a serial interface, which communicates via two parallel switched RJ45 plug connectors.
The RS485 interface allows for Modbus RTU Master and Modbus RTU Slave functionality. This interface
supports the transmission of the measured data, metered values, load profiles, indications, and time synchro-
nization.
1.1
1 DHCP cannot be used with IEC 61850 enabled.