–Outside air temperature
–Room air humidity
–Presence detector
–Condensation monitor. If the thermostat receives an input from a
condensation monitor, it will display a notification on the mobile app.
The thermostat does not alter operation based on this input.
–Room air quality
●Change input signal types based on the assigned input type. The following
signal types are supported:
NOTICE! If the corresponding application hasn't been configured, some
inputs may not be selectable.
–Digital input, normally open or closed
–1k Ohm @ 32 F Ni RTD (LG-Ni1000)
–1k Ohm Pt. RTD (385a)
–1k Ohm Pt RTD (375a)
–Type 2 Thermistor
–0 to 10 V*
●Set sensor evaluation mode if an external sensor is connected to either
terminal X1 or X2. You can use either the built-in and external sensors, or the
external sensors, for controlling and monitoring. The former is selected by
default. However, if no physical external sensors are connected to any
control inputs or if the input values are invalid, only the built-in sensors are
used instead to provide values for the thermostat. If external sensors are
connected and can provide valid values with the built-in sensors, the
thermostat reacts differently depending on the type of the external sensor:
–Displays the average value if it is an external temperature or humidity
sensor.
–Takes the higher value if it is an external VOC sensor.
–Enable presence detection related functions no matter whether it is the
external or the built-in presence detection sensor detects that someone
is in the room.
●If the selected equipment type is Heat pump, decide if the heat pump shall
be switched off below a certain outside air temperature. If yes, specify the
default temperature value. Note that an external outside air temperature
sensor is required to be connected with the thermostat to get the outside
temperature.
●If the selected equipment type is Heat pump and auxiliary heating is
allowed to operate when the heat pump is running, you can decide if the
auxiliary heating device shall be switched off above a certain outside air
temperature. If yes, specify the default temperature value. Note that an
external outside air temperature sensor is required to be connected with the
thermostat to get the outside temperature.
●Configure the output as a humidifier, humidifier free-standing, dehumidifier,
dehumidifier free-standing or an outside air damper.
●Activate or deactivate dehumidification. If the output is not configured as a
dehumidifier or dehumidifier free-standing, the thermostat takes use of the
heat pump or cooling system to dehumidify the space. However, the heat
pump turns off cooling (if cooling operation is running) whenever there is a
dehumidification command.
●Activate or deactivate ventilation. Only when the output is configured as an
outside air damper can the ventilation function be activated. The ventilation
function is mainly used to improve the room air quality when the room is