Sigineer Power TPH Series User manual

- 2 -
Table of Contents
1. Important Safety Information............................................................................................................................................- 3 -
1-1. General Safety Precautions ............................................................................................................................................- 3 -
1-2. Precautions When Working with Batteries....................................................................................................................- 3 -
2. Introduction .......................................................................................................................................................................- 5 -
2-1. General Information.......................................................................................................................................................- 5 -
2-2. Application.....................................................................................................................................................................- 5 -
2-3 The Appearance and Mechanical Drawing of TPH Series..............................................................................................- 7 -
2-4 Features...........................................................................................................................................................................- 7 -
2-5 Electrical Performance....................................................................................................................................................- 7 -
2.5.1 Inverter .................................................................................................................................................................- 7 -
2.5.2 AC Charger...........................................................................................................................................................- 8 -
2.5.3 Transfer...............................................................................................................................................................- 10 -
2.5.4 Frequency adjust.................................................................................................................................................- 10 -
2.5.5 Power Saver Mode .............................................................................................................................................- 10 -
2.5.6 Protections..........................................................................................................................................................- 12 -
2.5.7 Remote control Module......................................................................................................................................- 12 -
2.5.8 LED Indicator & LCD........................................................................................................................................- 13 -
2.5.9 Audible Alarm....................................................................................................................................................- 13 -
2.5.10 FAN Operation.................................................................................................................................................- 13 -
2.5.11 DIP Switches....................................................................................................................................................- 14 -
2.5.12 Other features ...................................................................................................................................................- 15 -
3 Installation........................................................................................................................................................................- 16 -
3-1 Location ........................................................................................................................................................................- 16 -
3-2 DC Wiring recommendation .........................................................................................................................................- 16 -
3-3 AC Wiring .....................................................................................................................................................................- 18 -
3-4 Install Flange.................................................................................................................................................................- 19 -
4 Battery Information..........................................................................................................................................................- 21 -
4-1 Battery Type..................................................................................................................................................................- 21 -
4-2 Battery Capacity Rating................................................................................................................................................- 22 -
4.2.1 Battery Discharge Rate.......................................................................................................................................- 22 -
4.2.2 Depth of Discharge.............................................................................................................................................- 22 -
4.2.3 Understanding Amp-Hour Requirements...........................................................................................................- 22 -
4.2.4 Battery Configurations .......................................................................................................................................- 23 -
4.2.5 Wiring Batteries..................................................................................................................................................- 23 -
4.2.6 Batteries Maintenance ........................................................................................................................................- 24 -
5 Troubleshooting Guide.....................................................................................................................................................- 25 -

- 3 -
1. Important Safety Information
WARNING!
This manual contains important instructions for all TPH Inverter/Charger models that shall be followed
during installation and maintenance of the inverter.
1-1. General Safety Precautions
1. Before installing and using the TPH Inverter/Charger, read all instructions and cautionary markings on the
TPH Inverter /Charger and all appropriate sections of this guide. Be sure to read all instructions and
cautionary markings for any equipment attached to this unit.
2. This unit is designed for indoor use only. Do not expose the TPH Inverter/Charger to rain, snow, or spray.
3. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the TPH
Inverter/Charger in a zero-clearance compartment. Overheating may result.
4. Use only attachments recommended or sold by the manufacturer. Doing otherwise may result in a risk of
fire, electric shock, or injury to persons.
5. To avoid a risk of fire and electric shock, make sure that existing wiring is in good condition and that wire
is not undersized. Do not operate the TPH Inverter/Charger with damaged or substandard wiring.
6. Do not operate the TPH Inverter/Charger if it has received a sharp blow, been dropped, or otherwise
damaged in any way. If the TPH Inverter/Charger is damaged, see the Warranty section.
7. Do not disassemble the TPH Inverter/Charger. It contains no user-serviceable parts. See Warranty for
instructions on obtaining service. Attempting to service the TPH Inverter/Charger yourself may result in a
risk of electrical shock or fire. Internal capacitors remain charged after all power is disconnected.
8. The TPH Inverter contains more than one live circuit (batteries and AC line). Power may be present at
more than one source. To reduce the risk of electrical shock, disconnect both AC and DC power from the
TPH Inverter/Charger before attempting any maintenance or cleaning or working on any circuits connected
to the TPH Inverter/Charger. Turning off controls will not reduce this risk.
9. Use insulated tools to reduce the chance of short-circuits when installing or working with the inverter, the
batteries, or PV array.
1-2. Precautions When Working with Batteries
1. Make sure the area around the battery is well ventilated.
2. Never smoke or allow a spark or flame near the engine or batteries.
3. Use caution to reduce the risk or dropping a metal tool on the battery. It could spark or short circuit the
battery or other electrical parts and could cause an explosion.
4. Remove all metal items, like rings, brace lets, and watches when working with lead-acid batteries.
Lead-acid batteries produce a short circuit current high enough to weld metal to skin, causing a severe burn.
5. Have someone within range of your voice or close enough to come to your aid when you work near a
lead-acid battery.
6. Have plenty of fresh water and soap near by in case battery acid contacts skin, clothing, or eyes.
7. Wear complete eye protection and clothing protection. Avoid touching your eyes while working near
batteries.
8. If battery acid contacts skin or clot hing, wash immediately with soap and water. If acid enters your eye,
immediately flood it with running cold water for at least twenty minutes and get medical attention
immediately.

- 4 -
9. If you need to remove a battery, always remove the grounded terminal from the battery first. Make sure all
accessories are off so you don’t cause a spark.
10. Always use identical types of batteries.
11. Never install old or untested batteries. Check each battery’s date code or label to ensure age and type.
12. Batteries are temperature sensitive. For optimum performance, the should be installed in a stable
temperature environment.
13. Always recycle old batteries. Contact your local recycling center for proper disposal information.

- 5 -
2. Introduction
2-1. General Information
Thank you for purchasing the TPH Series three phase Inverter/Charger.
TPH Series Pure Sine Wave Inverter is a combination of an inverter, charger, solar power and Auto-transfer
switch into one complete system. It is packed with unique features and it is one of the most advanced
inverter/chargers in the market today.
There are two main voltage outputs: 120/208Vac for America, 230/400Vac for Europe.
The inverter features an AC pass-through circuit, powering your home appliances from utility or generator
power while charging the battery. When utility power fails, the battery backup system keeps your appliances
powered until utility power is restored. Internal protection circuits prevent over-discharge of the batteries by
shutting down the inverter when a low battery condition occurs. When utility or generator power is restored,
the inverter transfers to the AC source and recharges the batteries.
Accessories allow the TPH series to also serve as a central hub of a renewable energy system. Set the TPH
Series inverter to battery priority mode, designates the inverter-preferred UPS configuration. In this
configuration, the load power in normally provided by the inverter. However, if the inverter output is
interrupted, an internal transfer switch automatically transfers the load from the inverter to commercial AC
power. The transfer time between inverter and line is short(8ms typical), and such transfers are normally not
detected by even highly sensitive loads. Upon restoration of inverter power, the inverter will transfer back to
inverter power.
On the line priority mode, when utility AC power cuts off(or falls out of acceptable range), the transfer relay
is de-energized and the load is automatically transferred to the Inverter output. Once the qualified AC utility
is restored, the relay is energized and the load is automatically reconnected to AC utility.
It features power factor corrected, sophisticated multi-stage charging and pure sine wave output with
unprecedentedly high surge capability to meet demanding power needs of inductive loads without
endangering the equipment.
TPH Series Inverter is equipped with a powerful charger. The overload capacity is 300% of continuous
output for up to 20 seconds to reliably support tools and equipment longer
Another important feature is that the inverter can be easily customized to Battery priority via a DIP switch,
this helps to extract maximum power from battery in renewable energy systems. Thus, the TPH-PV Series
Pure Sine Wave Inverter is suitable for Renewable energy system, Utility, RV, Marine and Emergency
appliances.
To get the most out of the power inverter, it must be installed, used and maintained properly. Please read the
instructions in this manual before installing and operating.
2-2. Application
Power tools–circular saws, drills, grinders, sanders, buffers, weed and hedge trimmers, air compressors.

- 6 -
Office equipment –computers, printers, monitors, facsimile machines, scanners.
Household items –vacuum cleaners, fans, fluorescent and incandescent lights, shavers, sewing machines.
Kitchen appliances –coffee makers, blenders, ice markers, toasters.
Industrial equipment –metal halide lamp, high –pressure sodium lamp.
Home entertainment electronics –television, VCRs, video games, stereos, musical instruments, satellite
equipment.

- 7 -
2-3 TheAppearance and Mechanical Drawing of TPH Series
2-4 Features
Smart LED Remote Control
Battery Temperature Sensor (BTS)
Automatic Generator Start (AGS)
Designed For Harsh Environment Operation
DC Start & Automatic Self-Diagnostic Function
Easy to Install & Easy to Operate & Easy to Solve
Low DC Voltage Supports Home & Office Appliances
High Energy Charging Function, Selectable From 0%-100%
High Efficiency Design &“Power Saving Mode”to Conserve Energy
Battery Priority Mode, Designates the Inverter-Preferred UPS Configuration
26/52Vdc Battery Recover Point, Dedicated for Renewable Energy Systems
8 pre Set Battery Type Selector plus De-sulphation for Totally Flat Batteries
4-step Intelligent Battery Charging, PFC (Power Factor Correction) for Charger
Independently controlled three-phase output voltages & Load,100% Unbalanced load
0ms Transfer Time From Battery to Utility ;8ms Typical Transfer Time From Utility to Battery
15s Delay Before Transfer when AC Recover, Protection for Load when Used with Generator
2-5 Electrical Performance
2.5.1 Inverter
Topology
The TPH inverter/charger is built according to the following topology.
Inverter: Full Bridge Topology.
AC Charger: Isolate Boost Topology
Solar Charger: MPPT PV Controller
Because of high efficiency IGBT and 32bit, 30MHz microprocessor and heavy transformers, it outputs
PURE SINE WAVE Waveform with an average THD of 3% (Max 8%) depending of load connected and
battery voltage.
The peak efficiency of TPH-PV series is 88%.
Overload Capacity
The TPH series inverters have different overload capacities, making it ideal to handle demanding loads.
1 For 110%<Load<125%(±10%), no audible alarm in 14 minutes, beeps 0.5s every 1s in the 15th minute,
and Fault(Turn off) after the 15th minute.
2 For 125%<Load<150%(±10%), beeps 0.5s every 1s and Fault(Turn off) after the 1 minute.

- 8 -
3 For 300%≧Load>150%(±10%), beeps 0.5s every 1s and Fault(Turn off) after 20s.
2.5.2 AC Charger
TPH Series is equipped with an active PFC (Power Factor Corrected) multistage battery charger. The PFC
feature is used to control the amount of power used to charge the batteries in order to obtain a power factor
as close as possible to 1.
Unlike other inverters whose max charging current decreases according to the input AC voltage, TPH-PV
series charger is able to output max current as long as input AC voltage is in the range of 164-243VAC
(95-127VAC for 120V model), and AC freq is in the range of 48-54Hz(58-64Hz for 60Hz model).
The TPH-PV series inverter is with a strong charging current of 120Amp (for 4KW,12V), and the max
charge current can be adjusted from 0%-100% via a linear switch at the right of the battery type selector.
This will be helpful if you are using our powerful charger on a small capacity battery bank. Fortunately, the
linear switch can effectively reduce the max charging current to 20% of its peak.
Choosing “0” in the battery type selector will disable charging function.
There are mainly 3 stages:
Bulk Charging: This is the initial stage of charging. While Bulk Charging, the charger supplies the battery
with controlled constant current. The charger will remain in Bulk charge until the Absorption charge voltage
(determined by the Battery Type selection) is achieved.
Software timer will measure the time fromA/C start until the battery charger reaches 0.3V below the boost
voltage, then take this time asT0 and T0×2 = T1.
Absorb Charging: This is the second charging stage and begins after the absorb voltage has been reached.
Absorb Charging provides the batteries with a constant voltage and reduces the DC charging current in order
to maintain the absorb voltage setting.
In this period, the inverter will start a T1 timer; the charger will keep the boost voltage in Boost CV mode
until the T1 timer has run out. Then drop the voltage down to the float voltage. The timer has a minimum
time of 1 hour and a maximum time of 12 hours.
Float Charging: The third charging stage occurs at the end of the Absorb Charging time. While Float
charging, the charge voltage is reduced to the fl oat charge voltage (determined by the Battery Type
selection*). In this stage, the batteries are kept fully charged and ready if needed by the inverter.
If theA/C is reconnected or the battery voltage drops below 12Vdc/24Vdc/48Vdc, the charger will reset the
cycle above.
If the charge maintains the float state for 10 days, the charger will deliberately reset the cycle to protect the
battery. Table 2.5.1 Battery Charging Processes
Table 2.5.2 Battery Type Selector

- 9 -
Switch Setting
Description
Fast Mode / VDC
Float Mode / VDC
0
Charger Off
1
Gel USA
14.0
13.7
2
AGM 1
14.1
13.4
3
LiFePO4
14.6
13.7
4
Sealed Lead Acid
14.4
13.6
5
Gel EURO
14.4
13.8
6
Open Lead Acid
14.8
13.3
7
Calcium
15.1
13.6
8
De-sulphation
15.5 (4 Hours then Off)
9
Classic LFP
13.6
13.5
For 12Vdc Battery Mode (*2 for 24Vdc Mode ; *4 for 48Vdc Mode)
De-sulphation
The de-sulphation cycle on switch position 8 is marked in red because this is a very dangerous setting if you
do not know what you are doing. Before ever attempting to use this cycle you must clearly understand what
it does and when and how you would use it.
What causes sulphation? This can occur with infrequent use of the batteries(nor), or if the batteries have
been left discharged so low that they will not accept a charge. This cycle is a very high voltage charge cycle
designed to try to break down the sulfated crust that is preventing the plates taking a charge and thus allow
the plates to clean up and so accept charge once again.
Charging depleted batteries
The TPH series inverter allows start up and through power with depleted batteries.
For 12VDC model, after the battery voltage goes below 10V, if the switch is still (and always) kept in "ON"
position, the inverter is always connected with battery, and the battery voltage does not drop below 2V, the
inverter will be able to charge the battery once qualified AC inputs are present.
Before the battery voltage goes below 9VDC, the charging can be activated when the switch is turned to
“Off”, then to “ON”.
When the voltage goes below 9VDC, and you accidently turn the switch to OFF or disconnect the inverter
from battery, the inverter will not be able to charge the battery once again, because the CPU loses memory
during this process.
Table 2.5.3 AC Charging Current for TPH model
Model
Watt
Battery Voltage
AC Charger
Current
Max
Model
Watt
Battery
Voltage
AC Charger
Current
Max
1.000
12 Vdc
35 ±5 Amp
2.000
12 Vdc
60 ±5 Amp
24 Vdc
20 ±5 Amp
24 Vdc
30 ±5 Amp
48 Vdc
10 ±5 Amp
48 Vdc
15 ±5 Amp
3.000
12 Vdc
80 ±5 Amp
4.000
12 Vdc
100 ±5 Amp
24 Vdc
45 ±5 Amp
24 Vdc
55 ±5 Amp
48 Vdc
25 ±5 Amp
48 Vdc
35 ±5 Amp
5.000
24 Vdc
65 ±5 Amp
6.000
24 Vdc
80 ±5 Amp
48 Vdc
40 ±5 Amp
48 Vdc
50 ±5 Amp
8.000
24 Vdc
100 ±5 Amp
10.000
48 Vdc
80 ±5 Amp

- 10 -
The charging capacity will go to peak in around 3 seconds. This may cause a generator to drop frequency,
making inverter transfer to battery mode.
It is suggested to gradually put charging load on the generator by switching the charging switch from min to
max, together with the 15s switch delay, our inverter gives the generator enough time to spin up. This will
depend on the size of the generator and rate of charge.
2.5.3 Transfer
While in the Standby Mode, the AC input is continually monitored. Whenever AC power falls below the
VAC Trip voltage (154 VAC, default setting for 230VAC,90VAC for 120VAC), the inverter automatically
transfers back to the Inverter Mode with minimum interruption to your appliances - as long as the inverter is
turned on. The transfer from Standby mode to Inverter mode occurs in approximately 8 milliseconds.And it
is the same time from Inverter mode to Standby mode.
Though it is not designed as a computer UPS system, this transfer time is usually fast enough to keep your
equipment powered up.
There is a 15-second delay from the time the inverter senses that continuously qualified AC is present at the
input terminals to when the transfer is made. This delay is built in to provide time for a generator to spin-up
to a stable voltage and avoid relay chattering. The inverter will not transfer to generator until it has locked
onto the generator’s output. This delay is also designed to avoid frequent switching when input utility is
unstable.
The transfer time from DC to AC is 0ms.
The transfer time from AC to DC is typically 6-8ms, 10ms max.
2.5.4 Frequency adjust
The frequency of the inverter is arranged by the SW4. Refer to the Table 2.5.11.
The factory default configuration for 220/230/240VAC inverter is 50Hz, and 60Hz for 100/110/120VAC
inverter. While the output freq can be easily changed once a qualified freq is applied to the inverter.
2.5.5 Power Saver Mode
There are 3 different working status for TPH inverter: “Power Saver Auto” 、“Power Saver Off” and
“Power Off”.
When power switch is in “Unit Off” position, the inverter is powered off.
When power switch is turned to either of “Power Saver Auto” or “Power Saver Off”, the inverter is powered
on.Power saver function is designed to conserve battery power when AC power is not or rarely required by
the loads.
In this mode, the inverter pulses the AC output looking for an AC load (i.e., electrical appliance). Whenever
an AC load (greater than 25 watts) is turned on, the inverter recognizes the need for power and automatically
48 Vdc
65 ±5 Amp
12.000
48 Vdc
100 ±5 Amp
18,000
24Vdc
300 ±5 Amp
18,000
48 Vdc
150 ±5 Amp
24,000
48 Vdc
200±5 Amp
36,000
48 Vdc
300±5 Amp
45,000
48 Vdc
350±5 Amp

- 11 -
starts inverting and output goes to full voltage. When there is no load (or less than 25 watts) detected, the
inverter automatically goes back into search mode to minimize energy consumption from the battery bank.
In “Power saver on” mode, the inverter will draw power mainly in sensing moments, thus the idle
consumption is significantly reduced.
Power saver on
Power saver off
Power saver on (Load detected)
Note: The minimum power of load to take inverter out of sleep mode (Power Saver On) is 25 Watts.
Table 2.5.6 TPH Series Idle Power Consumption
Model
Power Saver Off
Power Saver Auto
Idle(Max)
3Secs(Max)
Stand-By Mode
1.0KW
18W
7.5W
2.5W
1.5KW
18W
7.5W
2.0KW
30W
10.0W
3.0KW
60W
15.0W
4.0KW
70W
20.0W
5.0KW
80W
25.0W
6.0KW
90W
25.0W
8.0KW
120W
30.0W
10.0KW
150W
35.0W
12.0KW
180W
40.0W
18KW
240W
60W
24KW
360W
80W
36KW
480W
120W
45KW
680W
150W
When in the search sense mode, the green power LED will blink and the inverter will make a ticking sound.
At full output voltage, the green power LED will light steadily and the inverter will make a steady humming
sound. When the inverter is used as an “Un-interruptible power supply” the search sense mode or “Power
Saver On” function should be defeated.
Exceptions
Some devices when scanned by the load sensor cannot be detected. Small fluorescent lights are the most
common example. (Try altering the plug polarity by turning the plug over.) Some computers and
sophisticated electronics have power supplies that do not present a load until line voltage is available. When
this occurs, each unit waits for the other to begin. To drive these loads either a small companion load must

- 12 -
be used to bring the inverter out of its search mode, or the inverter may be programmed to remain at full
output voltage.
2.5.6 Protections
The TPH series inverter is equipped with extensive protections against various harsh situations/faults.
These protections include:
AC Input over voltage protection/AC Input low voltage protection
Low battery alarm/High battery alarm
Over temperature protection/Over load protection
Short Circuit protection (1sec after fault)
Back feeding protection
When Over temperature /Over load occur, after the fault is cleared, the master switch has to be reset to
restart the inverter.
The Low batter voltage trip point can be customized from defaulted value 10VDC to 10.5VDC turn the SW1
on DIP switch.
The inverter will go to Over temp protection when heat sink temp. ≥105ºC, and go to Fault (shutdown
Output) after 30 seconds. The switch has to be reset to activate the inverter.
The TPH series Inverter has back feeding protection which avoids presenting an AC voltage on the AC input
terminal in Invert mode.
After the reason for fault is cleared, the inverter has to be reset to start working.
2.5.7 Remote control Module
Apart from the switch panel on the front of the inverter, an extra switch panel connected to the RJ11 port at
the DC side of the inverter thru a standard telephone cable can also control the operation of the inverter.
If an extra switch panel is connected to the inverter via “remote control port”, together with the panel on the
inverter case, the two panels will be connected and operated in parallel.
Whichever first switches from “Off” to “Power saver off” or “Power saver on”, it will power the inverter on.
If the commands from the two panels conflict, the inverter will accept command according to the following
priority:
Power saver on> Power saver off> Power off
Only when both panels are turned to “Unit Off” position will the inverter be powered off.
The Max length of the cable is 10 meters.
WARNING

- 13 -
Never cut the telephone cable when the cable is attached to inverter and battery is connected to the inverter.
Even if the inverter is turned off. It will damage the remote PCB inside if the cable is short circuited during
cutting.
2.5.8 LED Indicator & LCD
Table 2.5.7 TPH Series LED Indicators
LINE MODE
GREEN LED lit in AC Mode
Please refer to ‘Indicator and Buzzer’
for the detailed information.
INVERTER MODE
GREEN LED lit in Inverter Mode
FAST CHARGE
YELLOW LED lit in Fast Charging Mode
FLOAT CHARGE
GREEN LED lit in Float Charging Mode
ALARM MODE
RED LED lit in Error State
OVER TEMP TRIP
RED LED lit in Over Temperature
OVER LOAD TRIP
RED LED lit in Over Load
POWER SAVER ON
GREEN LED lit in Power Saver Mode
2.5.9 Audible Alarm
Table 2.5.9 TPH Series Audible Alarm Spec
Battery Voltage Low
Inverter green LED lit, and the buzzer beeps 0.5s every 5s.
Battery Voltage High
Inverter green LED lit, and the buzzer beeps 0.5s every 1s and Fault after 60s.
Invert Mode Over-Load
(1)110%<load<125%(±10%), No audible alarm in 14 minutes,
Beeps 0.5s every 1s in 15th minute and Fault after 15 minutes;
(2)125% <load<150%(±10%), Beeps 0.5s every 1s and Fault after 60s;
(3)Load>150%(±10%), Beeps 0.5s every 1s and Fault after 20s;
Over Temperature
Heat-sink temp. ≥105ºC, Over temp red LED Lighting, beeps 0.5s every 1s;
2.5.10 FAN Operation
For 1-3KW, there is one multiple controlled DC fan,For 4-6KW, there is two multiple controlled DC fan
which starts to work according to the following logic
For 8-12KW, there is two multiple controlled DC fan and one AC fan. The DC fan will work in the same
way as the one on 1-3KW, while the AC fan will work once there is AC output from the inverter.
So when the inverter is in power saver mode, the AC fan will work from time to time in response to the
pulse sent by the inverter in power saver mode.
The Operation of the DC fan at the DC terminal side is controlled by the following logic
(Refer to Table 2.5.10): Table 2.5.10 TPH Series Fan Operation Logic
Condition
Enter condition
Leave condition
Speed
HEAT SINK
TEMPERATURE
T ≤ 60℃
T > 65℃
Off
65℃≤ T <85 ℃
T ≤ 60℃ / T ≥ 85℃
50%
T > 85℃
T ≤ 80℃
100%
CHARGER
CURRENT
I ≤ 15%
I ≥ 20%
Off
20%< I ≤ 50%
I ≤ 15% / I ≥ 50%
50%

- 14 -
Allow at least 30cm of clearance around the inverter for air flow. Make sure that the air can circulate freely
around the unit.
Variable speed fan operation is required in inverter and charge mode. This is to be implemented in such a
way as to ensure high reliability and safe unit and component operating temperatures in an operating
ambient temperature up to 50°C.
Speed to be controlled in a smooth manner as a function of internal temperature and/or current.
Fan should not start/stop suddenly.
Fan should run at minimum speed needed to cool unit.
Fan noise level target <60db at a distance of 1m.
2.5.11 DIP Switches
On the front panel of inverter, there are 5 DIP switches which enable users to customize the performance of
the device. Table 2.5.11 TPH Series Dip Switch Function Setting
DIP Switch NO.
Switch Function
Position: 0
Position: 1
SW1
Low Battery Trip Volt
10.0Vdc
For Deep-Cycle Battery
10.5Vdc
For Starting Battery
*2 for 24Vdc, *4 for 48Vdc
SW2
AC Input Range / (AVR)
AC Source
For Utility Mode
For Generator Mode
230Vac HV
184-253Vac / (176-276Vac)
140-270Vac / (150-276Vac)
120Vac LV
100-135Vac / (92-144Vac)
90-135Vac / (78-144Vac)
SW3
Power Saver Auto Setting
Night Charger Function
Detect Load Per 3Secs
SW4
O/P Frequency Setting
50Hz
60Hz
SW5
Solar/AC Priority Setting
Utility Priority
Battery Priority
SW1: Low Battery Trip Volt:
For 12VDC model, the Low Battery Trip Volt is set at 10.0Vdc by typical deep cycle lead acid battery. It
can be customized to 10.5Vdc using SW1 for sealed car battery, this is to prevent batteries from
over-discharging while there is only a small load applied on the inverter.(*2 for 24VDC, *4 for 48VDC)
SW2: AC Input Range:
There are different acceptable AC input ranges for different kinds of loads.
For some relatively sensitive electronic devices, a narrow input range of 184-253VAC (100-135V for
120VAC model) is required to protect them.
While for some resistive loads which work in a wide voltage range, the input AC range can be customized to
140-270VAC (90-135V for 120VAC model), this helps to power loads with the most AC input power
without frequent switches to the battery bank.
In order to make the inverter accept dirty power from a generator, when the SW2 is switched to position“1” ,
the inverter will bypass an AC input with a wide voltage and frequency(40Hz-70Hz for 50Hz/60Hz).
Accordingly, the AC charger will also work in a wide voltage and frequency range (43Hz-67Hz for
I > 50%
I ≤ 40%
100%
LOAD%
(INV MODE)
Load < 30%
Load ≥ 30%
Off
30% ≤ Load < 50%
Load ≤ 20% / Load ≥ 50%
50%
Load ≥ 50%
Load ≤ 40%
100%

- 15 -
50Hz/60Hz). This will avoid frequent switches between battery and generator. But some sensitive loads will
suffer from the low quality power.
The pros and cons should be clearly realized.
SW3: Power Saver Auto Setting :
In Power Saver Mode, when the SW3 is switched to position“0”, inverter will work in Unit Off Charging
mode, it will stay in standby mode without sensing loads. It won’t output any power even if a load is turned
on. The inverter will not perform any function and only stay idle in this mode. When a qualified AC input
present, it will switch to AC input power to charge the battery and supply the load at the same time.
When the SW3 is switched to position“0”, the inverter is initially in standby mode and sends a pulse to
detect the presence of a load every 3 seconds. Each pulse lasts for 250ms. The inverter will remain in
standby mode until a load has been detected. Then it will wake up from standby mode and start to inverter
electricity from the battery bank to supply the load.
SW4: Frequency Switch:
The output frequency of the inverter can be set at either 50Hz or 60Hz by SW4.
SW5: Solar Mode/AC Mode Priority:
Our inverter is designed with AC priority by default. This means, when AC input is present, the battery will
be charged first, and the inverter will transfer the input AC to power the load. Only when the AC input is
stable for a continuous period of 15 days, the inverter will start a battery inverting cycle to protect the
battery. After 1 normal charging cycle ac through put will be restored.
The AC Priority and Battery Priority switch is SW5. When you choose battery priority, the inverter will
inverting from battery despite the AC input. Only when the battery voltage is reaches low voltage alarm
point(10.5V for 12V), the inverter transfers to AC Input, charge battery, and switch back to battery when
battery is charged full. This function is mainly for wind/solar systems taking utility power as back up.
2.5.12 Other features
Battery voltage recovery start
After low battery voltage shut off (10V for 12V model/20V for 24V model/40V for 48V model), the inverter
is able to restore operation after the battery voltage recovers to 13Vdc/26Vdc/52Vdc (with power switch still
in the “On” position). This function helps to save the users extra labor to reactivate the inverter when the
low battery voltage returns to an acceptable range in the renewable energy systems. The built in battery
charger will automatically reactivate as soon as city/generator ac has been stable for 15 seconds.
WARNING
Never leave the loads unattended, some loads (like a Heater) may cause accident in such cases.
It is better to shut everything down after low voltage trip than to leave your load on, due to the risk of fire.
Auto Generator Start (AGS)
The inverter can be customized to start up a generator when battery voltage goes low.
When the inverter goes to low battery alarm, it can send a signal to start a generator, and turn the generator
off after battery charging is finished.

- 16 -
The auto generator start feature will only work with generators designed to work with this feature. There is
an open/closed relay that will short circuit the positive and negative cable from a generator. The input DC
voltage can vary, but the Max current the relay can carry is 16Amp.
Battery temperature sensor (BTS)
A battery temperature sensor (BTS) option can easily be installed in the system to ensure proper charging of
the batteries based on temperature. Installing a BTS extends battery life by preventing overcharging in warm
temperatures and undercharging in cold temperatures.
To install the Battery Temperature Sensor:
1. Run the battery temperature sensor wire in the DC conduit (if used) and route the RJ11 connector end to
the BATTERY SENSE port located on the front of the inverter.
2. Secure the sensor to one of the batteries located in the center of the battery pack.
Conformal Coating
Entire line of TPH inverters have been processed with a conformal coating on the PCB making it water, rust,
and dust resistant.
3 Installation
3-1 Location
Follow all the local regulations to install the inverter.
Please install the equipment in a location that is Dry, Clean, Cool and that has good ventilation.
Working temperature: ‐10℃‐40℃
Storage temperature: ‐40‐70℃
Relative Humidity: 0%‐95%,non-condensing
Cooling: Forced air
3-2 DC Wiring recommendation

- 17 -
It is suggested the battery bank be kept as close as possible to the inverter. The following able is a suggested
wiring option for 1m DC cable.
Please find the following minimum wire size. In case of DC cable longer than 1m, please increase the cross
section of cable to reduce the loss.
Please note that if there is a problem obtaining for example 100mm²cable, use 2*50mm²or 3*35mm².
One cable is always best , but cable is simply copper and all you require is the copper, so it does not matter
if it is one cable or 10 cables as long as the square area adds up. Performance of any product can be
improved by thicker cable and shorter runs, so if in doubt round up and keep the length as short as possible.
Battery cables must have crimped (or preferably, soldered and crimped) copper compression lugs unless
aluminum mechanical lugs are used. Soldered connections alone are not acceptable. High quality, UL-listed
battery cables are available .These cables are color-coded with pressure crimped, sealed ring terminals.
Figure 3.2.1 Battery Cable Connections
Model
Watt
Battery Voltage
Wire Gage /Min
Model
Watt
Battery Voltage
Wire Gage /Min
0~1.0m
1.0~5.0m
0~1.0m
1.0~5.0m
1.000
~
1.500
12 Vdc
30mm²
40mm²
2.000
12 Vdc
60mm²
75mm²
24 Vdc
15mm²
20mm²
24 Vdc
30mm²
45mm²
48 Vdc
10mm²
15mm²
48 Vdc
15mm²
25mm²
3.000
12 Vdc
90mm²
120mm²
4.000
12 Vdc
120mm²
150mm²
24 Vdc
45mm²
60mm²
24 Vdc
60mm²
75mm²
48 Vdc
25mm²
30mm²
48 Vdc
30mm²
40mm²
5.000
24 Vdc
75mm²
95mm²
6.000
24 Vdc
90mm²
120mm²
48 Vdc
40mm²
50mm²
48 Vdc
45mm²
60mm²
8.000
24 Vdc
120mm²
150mm²
10.000
48 Vdc
75mm²
95mm²
48 Vdc
60mm²
75mm²
12.000
48 Vdc
90mm²
120mm²

- 18 -
CAUTION: Equipment Damage
The inverter is not reverse polarity protected. Reversing the battery polarity on the DC input connections
will cause permanent damage to the inverter which is not covered under warranty. Always check polarity
before making connections to the inverter.
WARNING: Shock Hazard
Ensure the inverter is off before disconnecting the battery cables, and that AC power is disconnected from
the inverter input.
Battery terminal must be clean to reduce the resistance between the DC terminal and cable connection. A
buildup of dirt or oxidation may eventually lead to the cable terminal overheating during periods of high
current draw. Use a stiff wire brush and remove all dirt and corrosion from the battery terminals and cables.
3-3 AC Wiring
We recommend using 10-5AWG wire to connect to the AC terminal block.
The three phase inverter only supports Y connection. It willn’t support delta connection.
There are 3 different ways of connecting to the terminal block depending on the model. All the wirings are CE
compliant, Call our tech support if you are not sure about how to wire any part of your inverter.
The TPH inverter will automatically bond the neutral with ground in DC toAC battery mode, and separate neutral with
ground inAC model.
3-Phase Wiring Mode
INPUT R
INPUT N
OUTPUT N
Battery
DC Power
Q1-R Q3-R
Q2-R Q4-R
MAIN TX-R
CT-R
Transfer SW-R R-CB
TPP Series Inverter&Charger Topology Diagram
Inverter Mode
In Ground
CHARGE INPUT
PROTECT BREAKER
Transfer SW-N
Discharger Mode
R
Phase
CHARGE INPUT
PROTECT BREAKER
CHARGE INPUT
PROTECT BREAKER
Q1-S Q3-S
Q2-S Q4-S
S
Phase
Q1-T Q3-T
Q2-T Q4-T
CT-S CT-T
T
Phase
INPUT S Transfer SW-S S-CB
INPUT T
AC Output
Transfer SW-T T-CB
Out Ground
MAIN TX-S MAIN TX-T
1 Phase Load * 3
120/230Vac
3 Phase Delta Load
Y- 220/400Vac
3 Phase
AC Circuit Breaker

- 19 -
INPUT R
INPUT N
OUTPUT N
Battery
DC Power
Q1-R Q3-R
Q2-R Q4-R
MAIN TX-R
CT-R
Transfer SW-R R-CB
TPP Series Inverter&Charger Topology Diagram
Bypass & Charger Mode
In Ground
CHARGE INPUT
PROTECT BREAKER
Transfer SW-N
Charger Mode
R
Phase
CHARGE INPUT
PROTECT BREAKER
CHARGE INPUT
PROTECT BREAKER
Q1-S Q3-S
Q2-S Q4-S
S
Phase
Q1-T Q3-T
Q2-T Q4-T
CT-S CT-T
T
Phase
INPUT S Transfer SW-S S-CB
INPUT T
AC Output
Transfer SW-T T-CB
Out Ground
MAIN TX-S MAIN TX-T
1 Phase Load * 3
120/230Vac
3 Phase Delta Load
Y- 220/400Vac
3 Phase
AC Circuit Breaker
3-4 Install Flange
TPH 3-18KW Model
Tower

- 20 -
TPH 24-36KW Model
TPH 45KW Model
This manual suits for next models
7
Table of contents
Other Sigineer Power Inverter manuals
Popular Inverter manuals by other brands

Sungrow
Sungrow SH4K6 Quick user manual

Innovatronix
Innovatronix Tronix Explorer Mini user guide

Studer
Studer AJ SERIES User's and installer's manual

Hoymiles
Hoymiles HM-800N Series Quick installation guide

Champion
Champion 200978 Operator's manual

MAER IDROPULITRICI
MAER IDROPULITRICI AVANT 120/11 Instructions for installation and use