2. Have another person move across the desired
perimeter of the area to be scanned and slowly
adjust the SENS knob until the unit activates.
Note reducing SENS will reduce both normal and
occupancy zones
3. To set the light level at which the lights will
automatically switch “on” at night, turn the LUX
control knob from daylight () to night ( ). If the
lights are required to switch on earlier, e. g. Dusk,
wait for the desired light level, and then slowly turn
the LUX control knob towards daylight while someone walks across the center of the area to
be detected. When the lights activate, release the LUX control knob. You may need further
slight adjustments to achieve your ideal light level setting
4. Once LUX and SENS are calibrated, adjust TIME to suit site requirements.
5. Duplicate these settings for similar locations
Model: LHT0179 360° PIR Sensor - Dual Mount
INSTALLATION INSTRUCTIONS
SIMX strongly recommend that this sensor is installed by a suitably qualified and registered
electrician.
Please read the entire Installation Instructions and Calibration Settings before installing this
product.
All electrical work must be carried out in accordance with local and national electrical codes as
applicable.
Always switch power off prior to installation.
A means of power isolation must be installed on the circuit for the purpose of safe access for any
internal cleaning, recalibration or maintenance.
This appliance is not intended for installation or calibration by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience or knowledge, unless they
have been given supervision or instruction concerning its use by a person responsible for their
safety.
There are no user-serviceable parts in this product.
Any changes or modifications made or attempted to this product without the prior written approval
of the manufacturer will void any and all stated warranties. This excludes normal calibration of the
Sens, Time and Lux control setting knobs as described in these installation instructions.
IMPORTANT
!
Thank you for purchasing this SIMX PIR Sensor. This sensor is suitable for indoor use, and restricted
outdoor applications only. Please read this manual thoroughly before installation and retain for future
reference.
DETECTION RANGE
This Triple PIR sensor has a normal detection range
in open space of max 22 meters diameter. As this
detection zone is circular, please ensure an adequate
overlap in your layout to eliminate dead-zones.
OCCUPANCY ZONE
This PIR Sensor has a high sensitivity
Occupancy Zone of 6 meters diameter. In
this zone, the sensor will detect small
movement to activate lights or keep
those lights illuminated.
Max.11m Max.11m
Fig 1
TECHNICAL SPECIFICATIONS
!
PUB1162 iss02 08/13
Power supply: 220~240V AC 50 Hz
Wattage: Max. 2000Watt~ incandescent bulb (Resistive)
Max. 600Watt ~ fluorescent lamps (Inductive)
Max. 200Watt ~ light emitting diode (LED)
Detection range: 360° Max. 22 meters diameter for normal detection
Max. 6 meters diameter for occupancy detection
Delay time: From (10±5) seconds to (40±5) minutes adjustable
Lux control level: Adjustable Daylight to Night 2-2000lux
Auto/Manual: Yes (Off/On/Off/On) within 3 secs
IP Rating: IP44 - Surface Mounted
IP20 - Recess Mounted
Due care during installation will maintain the IP Ratings
Intended use of this product is ceiling orientation only.

Distributed by: Simx Limited
Ph: +64 9 259 1660 | Technical Support Ph: +64 9 259 1662
Email: sales@simx.co.nz | www.simx.co.nz
Simx reserves the right to alter technical specications without prior warning
1. The circuit can be switched on for an 8 hour period by using the Manual override. Operation
in this mode bypasses the PIR sensor. This can be activated at any time by using the internal
wall switch or circuit breaker.
2. Toggle the internal wall switch/circuit breaker twice (off/on/off/on) within 3 seconds. The circuit
will now be switched on continuously for 8 hours or until switched back to Auto mode.
3. To switch the unit back to Auto mode, toggle the internal wall switch/circuit breaker twice (off/
on/off/on) within 3 seconds (Same operation as activating Manual Override). The unit will return
to Auto mode.
MANUAL OVERRIDE MODE
Fig 3
TIME SETTING:
The duration time is the length of time the circuit stays ‘on’ after activation. The duration time can be
adjusted from (10±5) seconds to (40±5) minutes. Rotating the TIME knob from (+) to (-) will reduce
the duration time. Note: Once the circuit has been triggered by the PIR sensor any subsequent
detection will start the timed period again from the beginning.
SENSITIVITY SETTING (REACH): The sensitivity set to (+) provides the maximum distance
which PIR Sensor can be triggered by body movement. Turning the SENS knob from (+) to (-) will
decrease both the sensitivity and activation zone.
B: RECESS MOUNTING TO CEILING (FIGURE 2B)
1. Unscrew the Cable Clamp, remove the Junction Box and Terminal Block.
2. Discard the Base piece for recess mount applications – not required
3. Connect circuit wiring to the terminal block as labelled.
4. Refit the Terminal Block, Junction Box and Cable Clamp.
5. Fit springs, carefully lift the spring clips into the 82-88mm diameter hole, and recess the
PIR to the ceiling. The spring clips will secure the unit. Refit the front cover.
1. Remove the front cover
2. Unscrew the cable clamp, and remove the Junction Box and Terminal Block
3. Use the Base as a template to mark the screw holes into the ceiling. Pre-drill the lining to
depth of 35mm and fit the plastic plugs, and then affix the Base securely. Care should be
taken to avoid drilling or screwing any concealed services inside the ceiling void.
4. Connect circuit wiring to the terminal block as labelled.
5. Secure the Junction box & Terminal block to the PIR and tighten cable clamp over Mains
Cable.
6. Carefully align the male terminal pins, click the PIR body onto the Base then re-fit the front
cover.
INSTALLING THE SENSOR
Before commencing any electrical work, ensure the mains supply is isolated by switching off
and removing the relevant fuse.
Exceeding the maximum rated load may cause overheating and probable failure of this sensor.
Please exercise care!


LIGHT CONTROL SETTING:
The Lux control is a built-in sensing device (photocell) that detects daylight and darkness.
() position denotes the light can activate during daylight and night. ( ) position denotes
the light can activate only at night. You can set the unit to operate at the desired switch on
level by adjusting the LUX knob
A: SURFACE MOUNTING TO CEILING (FIGURE 2A)


Fig 2B
CALIBRATION SETTINGS (Figure 3)

Fig 2A
SETTING THE CONTROLS
1. Put the LUX control knob to light () position, turn the wall switch on and wait half a minute
for the control circuit to stabilize. At this stage ensure that the TIME control knob is set at
minimum duration time (-) position. The connected circuit will now switch on and remain on
for about 30 seconds (within 60 seconds).

Other SImx Accessories manuals

SImx LHT0182 User manual

SImx

SImx LHT0182 User manual

SImx LHT0179 User manual

SImx

SImx LHT0179 User manual

SImx LHT0120 User manual

SImx

SImx LHT0120 User manual

SImx LED MAX User manual

SImx

SImx LED MAX User manual

SImx LHT0268 User manual

SImx

SImx LHT0268 User manual

SImx LHT0119 User manual

SImx

SImx LHT0119 User manual

SImx LHT0244 User manual

SImx

SImx LHT0244 User manual

SImx LHT0238 Manual

SImx

SImx LHT0238 Manual

Popular Accessories manuals by other brands

GOLDENSEA UV UVS4 user guide

GOLDENSEA UV

GOLDENSEA UV UVS4 user guide

PFlow Industries 21 Series owner's manual

PFlow Industries

PFlow Industries 21 Series owner's manual

Lambrecht rain[e]H3 user manual

Lambrecht

Lambrecht rain[e]H3 user manual

Waterpik WP-360 manual

Waterpik

Waterpik WP-360 manual

Nyce NCZ-3011 installation guide

Nyce

Nyce NCZ-3011 installation guide

Altec 731B HF DRIVER manual

Altec

Altec 731B HF DRIVER manual

ECO Sensors C-21 Instructions for use

ECO Sensors

ECO Sensors C-21 Instructions for use

Smart Technologies Hawkeye 480C Installation and user guide

Smart Technologies

Smart Technologies Hawkeye 480C Installation and user guide

Jenile CBM14 instruction manual

Jenile

Jenile CBM14 instruction manual

PCB Piezotronics P112A05 Installation and operating manual

PCB Piezotronics

PCB Piezotronics P112A05 Installation and operating manual

Crestron GLS-ODT-C-2000 Operations & installation guide

Crestron

Crestron GLS-ODT-C-2000 Operations & installation guide

Flavor Burst CTP 80SS-INT Operation manual supplement

Flavor Burst

Flavor Burst CTP 80SS-INT Operation manual supplement

nedis WIFICDPC10 Series quick start guide

nedis

nedis WIFICDPC10 Series quick start guide

SkyBound 2 ARCH TRAMPOLINE NET Assembly and installation manual

SkyBound

SkyBound 2 ARCH TRAMPOLINE NET Assembly and installation manual

Nortel 1000BASE-XD Using

Nortel

Nortel 1000BASE-XD Using

Mammut PULSE Barryvox user manual

Mammut

Mammut PULSE Barryvox user manual

Alarmcom ADC-VDB780B manual

Alarmcom

Alarmcom ADC-VDB780B manual

Promate bluPen.2 user guide

Promate

Promate bluPen.2 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.