o. 30 The measured temperature value is displayed with the °C unit, during the device is running.
SET
SEt
hys
o.mIn
+
11 10
10
By holding down to SET key, the setpoint value flashes and can be adjusted between 0 and 60°C values. If any of the navigation keys
pressed continuously, the adjusted value changes rapidly.
SET
If SET key is pressed, SEt is displayed and the "Programming Mode" is entered. By using the increase/decrease navigation keys, desired
parameter can be selected and adjusted as following defines. If the increase and decrease keys are pressed together or no operation is
performed for 20 seconds, returned to the main display (Running Mode).
26 25
25
By holding down to SET key, the minimum output value flashes and can be adjusted between 0 and 60% values. If any of the
navigation keys pressed continuously, the adjusted value changes rapidly.
SET
26 25
25
By holding down to SET key, °C unit hysteresis value flashes and can be adjusted between 3 and 31°C values. If any of the navigation
keys pressed continuously, the adjusted value changes rapidly.
SET
Control with Phase Angle
Operation Principles
PROGRAMMING
Error Messages
100mm
111mm 46mm
9mm
INSTALLATION
DIMENSIONS
1 2
345
10 9
8
76
ENDA
ERFA
single - phase
fan speed controller
SET
MADE IN TURKEY SN : 140335044
ENDA
INDUSTRIAL ELECTRONICS
ERFA1-NTC-240
Single - Phase Fan Speed Controller
ENDA
ERFA
single-phase
fan speed controller
SET
NTC
8 6 8 0 4 0 7 7 1 3 9 8 1
180-280VAC
50/60Hz
LOAD
MAX. 40A
L N
To mount the device on rail :
By using a screwdriver, pull the lockplate
in direction 1 to lock it.
Assemble the device on the rail and push
it in the direction 2 (sideways).
To remove the device from the rail :
By using a screwdriver, pull the lockplate
in direction 1 to lock it. Remove device
from rail.
NTC Sensor Input
CONNECTION DIAGRAM
No communication with NTC sensor (Sensor and/or cable broken or not connected).
PFA message flashes and the output operates 100%.
NTC sensor or connection line short-circuited. PSC message flashes and the output operates
100%.
PFA
PSC
_ _ _ _ message flashes and the output operates 0% when the measured temperature value is
lower than 0°C.
____
____ message flashes and the output operates 100% when the measured temperature value is
higher than 95°C.
Power-up the device by pressing and holding down the key for factory defaults. d.PAr message will
be displayed if the operation success.
SEt = 10 , o.mIn = 25 , hys = 25
Factory Defaults
ERFA1-NTC-240
2
1
WARNING
Heatsink at
high temperature
1 2
345
10 9
8
76
ENDA
ERFA
single - phase
fan speed controller
SET
If the measured temperature < SEt , Output : 0%.
If the measured temperature = SEt , Output : Minimum oMin % set value.
If the measured temperature < SEt + HYS , Output : 100%.
The output will be scaled to the according to temperature value (Max. 100%), when the
measured temperature is reached to the SET + HYS parameter value.
The output will be equivalent to the oMin parameter when the temperature value is reached
to the SET value.
If the temperature value is lower than the SET value, no output operation will be performed. Output rate %20
Output rate %50
Output rate %80
It is a proportional control method used in
inductive and variable resistive loads (cosØ <1).
Runnig Mode
_ _ _ _
2/2 ERFA1-NTC-240-EN-02-210317
Fuse
Suply Voltage
90-250VAC
7VA
L N
Load
180-280VAC