SKF ST-1100s Manual

110s2AEN.doc 16.01.2013 Rev. 2A
SKF ST-1100s control center
(Original operating and maintenance instructions)

110s2AEN.doc 16.01.2013 Rev. 2A
TABLE OF CONTENTS
1 EC Declaration of conformity ........................................................................................................................1
2 General description ......................................................................................................................................2
3 Design..........................................................................................................................................................2
3.1 Cover ............................................................................................................................................................................................3
3.1.1 Indicator lamps....................................................................................................................................................................3
3.1.2 Buttons.................................................................................................................................................................................3
3.2 Control panel...............................................................................................................................................................................3
3.2.1 General .................................................................................................................................................................................3
3.2.2 Buttons.................................................................................................................................................................................3
3.2.3 LED-signals..........................................................................................................................................................................4
3.2.4 Display ..................................................................................................................................................................................4
4 Operation.....................................................................................................................................................5
4.1 Lubrication modes......................................................................................................................................................................5
4.1.1 Automatic lubrication (1)....................................................................................................................................................5
4.1.2 Automatic lubrication (2)....................................................................................................................................................6
4.1.3 Manual lubrication (1) ........................................................................................................................................................6
4.1.4 Manual lubrication (2) ........................................................................................................................................................6
4.2 Lubrication...................................................................................................................................................................................6
4.3 Alarms..........................................................................................................................................................................................7
4.4 Air blowing...................................................................................................................................................................................7
4.5 Power failure...............................................................................................................................................................................7
5 Settings .......................................................................................................................................................7
5.1 General.........................................................................................................................................................................................7
5.2 Entering password......................................................................................................................................................................8
5.3 Entering settings.........................................................................................................................................................................8
5.3.1 Lubrication counter.............................................................................................................................................................8
5.3.2 Lubrication interval.............................................................................................................................................................9
5.3.3 Link pins per rotation .........................................................................................................................................................9
5.3.4 Lubrication mode ................................................................................................................................................................9
5.3.5 Pressure control..................................................................................................................................................................9
5.3.6 Configuration settings ........................................................................................................................................................9
6 Start-up.....................................................................................................................................................10
7 Technical specifications ..............................................................................................................................11

110s2AEN.doc 16.01.2013 Rev. 2A
7.1 Technical data.......................................................................................................................................................................... 11
7.2 Connections.............................................................................................................................................................................. 11
8 Spare parts ................................................................................................................................................12
9 Contact information....................................................................................................................................12

110s2AEN.doc 16.01.2013 Rev. 2A 1 (12)
1 EC Declaration of conformity
Original Declaration of conformity according to EMC Directive 2004/108/EC and Low Voltage
Directive 2006/95/EC
Oy SKF Ab
Teollisuustie 6 (P.O. Box 80)
FIN-40951 MUURAME
FINLAND
herewith declares that the product:
SKF ST-1100s control center
conforms to the relevant requirements of EMC Directive 2004/108/EC. The product complies with the following
harmonized standards:
•EN 61000-6-4:2001, for emissions
•EN 61000-6-2:2001, for immunity
conforms to the relevant requirements of Low Voltage Directive 2006/95/EC. The product complies with the following
harmonized standards:
•IEC 61010-1:2001
Muurame 14.12.2012
Place Date
Tuomo Helminen
General Manager

110s2AEN.doc 16.01.2013 Rev. 2A 2 (12)
Warning Read and follow the safety precautions and general instructions in this manual and
also in the SKF manual
"Safety and general instructions for lubrication systems."
Failure to follow these
instructions could result in serious injury or damage to the lubrication system or the equipment that is
lubricated.
2 General description
SKF ST-1100s is a control center for a chain lubrication system. The system lubricates each link of the chain either
according to the settings in the automatic mode or manually. Lubrication interval can be set either on the basis of time
or number of chain rotations. The lubrication pulses are timed by means of an inductive sensor, which recognizes the
links of the chain.
3 Design
The main switch of the SKF ST-1100s control center is located at the bottom edge of the center enclosure. The
enclosure cover has a green indicator lamp for power and a red indicator lamp for alarm. The control panel of the
center is located inside the enclosure.
Figure 1 SKF ST-1100s control center design

110s2AEN.doc 16.01.2013 Rev. 2A 3 (12)
3.1 Cover
3.1.1 Indicator lamps
Indicator lamp Description
Power Green indicator lamp is lit when power is on.
Alarm Red indicator lamp is lit when control center is in alarm mode.
3.1.2 Buttons
The buttons on the cover are not in use in this application.
3.2 Control panel
3.2.1 General
Control panel is located inside the enclosure. The control panel has a 6-character display, three (3) buttons and LED-
signals for inputs and outputs. The display and buttons can be used for setting the parameters for lubrication program
and for operating the lubrication system manually.
3.2.2 Buttons
Button Description
Setting In setting mode and while entering password, pressing down the button enables changing of the
displayed value with the arrow buttons.
In normal mode, the button is used to start extra lubrication, to reset an alarm and to stop
lubrication.
The button can be used for scrolling to the previous parameter display.
In setting mode and while entering password, the button can be used for decreasing the displayed
value, if the Setting-button is pressed down.
The button can be used for scrolling to the next parameter display.
In setting mode and while entering password, the button can be used for increasing the displayed
value, if the Setting-button is pressed down.

110s2AEN.doc 16.01.2013 Rev. 2A 4 (12)
3.2.3 LED-signals
LED-signal Description
PULSE 1 The LED-signal is lit, when the sensor for the sensor input 1 is closed
PULSE 2 The LED-signal is lit, when the pressure switch is closed.
LOW LEVEL
Lubricant reservoir low level. The LED-signal is lit when the reservoir is empty i.e. the
low level switch is closed.
INTERLOCKING
Operation information of the equipment that is lubricated. The LED-signal is lit when the
equipment is not in operation (= no interval calculated) i.e. the interlocking switch is
closed.
LINE 1 The LED-signal is lit, when air blowing is active.
LINE 2 Pump control 2 (optional). The LED-signal is lit when the pump control is switched on.
PUMP Pump control. The LED-signal is lit when the pump control is switched on.
ALARM The LED-signal is lit when the center is in alarm mode.
OK The LED-signal is blinking, when the electronics operate normally.
3.2.4 Display
The control panel has a 6-character 7-segment display.
The display has been divided into two groups:
•2-character value display indicates the code for phase or value
•4-character time display indicates the value corresponding to the code
When the display shows a time value, the decimal point blinks at intervals of one (1) second.
The time is displayed as hours and minutes. For example, 12.34 indicates 12 h 34 min and 123.4 indicates 123 h 40
min.
When the control center is in normal or alarm mode, the code corresponding to the program phase is shown on the
value display.
Phase code Phase description Time display
Ct Interval, time counted Interval duration
Cr Interval, rotations counted Full chain rotations
Ht Manual operation, time displayed Interval duration
Hr Manual operation, number of rotations displayed Full chain rotations
P Lubrication Number of lubricated links
L Interlocking switch is closed or pulse time-out reached Interval duration
AL Lubricant reservoir low level alarm Elapsed alarm time
AP Pressure alarm Elapsed alarm time
AE Electronics error alarm
(Electronics alarm)
Error code
Buttons and can be used to browse the normal mode displays which show the lubrication program set values.

110s2AEN.doc 16.01.2013 Rev. 2A 5 (12)
Value display codes change in the following order when -button is pressed and vice versa, when -button is
pressed.
Display code Description
CC Lubrication counter
Lt Lubrication interval set value when interval is counted as time
Lr Lubrication interval set value when interval is counted as full chain
rotations.
LP Set value for link pins per rotation
Ld Selected lubrication mode
--Ct= automatic lubrication based on time
--Cr= automatic lubrication based on full chain rotations
--Ht= manual lubrication, time is displayed
--Hr= manual lubrication, number of chain rotations is displayed
Pr Pressure control with external pressure switch in use Yes/No
LF Operation mode of the center, configuration setting.
In this application the setting must be SPr.
PASS Entering password.
The password is displayed on time display.
The program returns to display program phase code (normal or alarm mode) in the following cases:
−Setting- or arrow button was last pressed more than three (3) minutes ago
−both arrow buttons are simultaneously pressed down for 3 seconds
−-button is used to browse the phase code on the display
−the center is restarted
4 Operation
4.1 Lubrication modes
Select the lubrication mode with the setting code L.d.
4.1.1 Automatic lubrication (1)
The lubrication interval is set as hours (0 ... 9999 h). The display code is Ct during the lubrication interval and the
elapsed interval time is displayed. Lubrication starts when the set interval time has elapsed. After the lubrication, the
system starts counting the interval again. Lubrication can also be started manually by pressing the Setting-button.
The interval counting can be interrupted by closing the interlocking input. If the configuration parameter
Timeout
is
not set at 0, interval counting is stopped also if no chain pulses have been received during the set time value.
If the interval counting has been stopped, the code displayed is Linstead of Ct.

110s2AEN.doc 16.01.2013 Rev. 2A 6 (12)
4.1.2 Automatic lubrication (2)
The lubrication interval is set as full chain rotations (0 ... 9999 r). The display code is Cr during the lubrication interval.
Lubrication starts when the set amount of full chain rotations has been reached. After the lubrication, the rotation
count is reset to 0. Lubrication can also be started manually by pressing the Setting-button.
4.1.3 Manual lubrication (1)
The code displayed is Ht. The display shows elapsed time as hours since the previous lubrication. Lubrication is started
by pressing the Setting-button.
4.1.4 Manual lubrication (2)
The code displayed is Hr. The display shows the number of chain rotations since the previous lubrication. Lubrication is
started by pressing the Setting-button.
4.2 Lubrication
Lubrication is performed the same way in all lubrication modes described above. Each link pin of the chain is lubricated
once during a lubrication phase. The number of link pins per rotation can be set by means of parameter
Link pins per
rotation.
The setting code is L.P.
Usually each link pin is lubricated one after another. If the parameter
Divider
(display code P.F.) is set to value > 1, a
lubrication pulse is sent when the chain pulse counter reaches the divider value. Lubrication pulses are sent according
to the parameter
Link pins per rotation
. For example, if the
Divider
= 3, a lubrication pulse is sent at every third chain
pulse and lubrication takes three (3) full chain rotations.
During lubrication phase, code Pis displayed as well as the number of lubricated link pins. The lubrication phase stops,
when the number of the lubricated link pins reaches the set value. Lubrication can be stopped by pressing the Setting-
button.
When lubrication stops, the reading of the lubrication counter is added by one unit. The counter reading does not
increase if the lubrication has been stopped prematurely.
In addition, there are two other parameters for controlling the lubrication pulse:
•Pulse length (display code P.L.) which is used to adjust the duration of the lubrication pulse
•Pulse delay (display code P.d.) which is used to adjust the delay time between the chain pulse and the lubrication
pulse
See also section 5.3.6 Configuration settings
.

110s2AEN.doc 16.01.2013 Rev. 2A 7 (12)
4.3 Alarms
The control center goes into alarm mode if the low level switch of the lubricant reservoir closes during lubrication.
Code AL is displayed as well as alarm duration in hours and minutes.
If the parameter P.r. has been set in status Yes, the pressure of the pump is monitored with an external pressure
switch. The control center goes into alarm mode if the switch is closed when the lubrication pulse starts or if the switch
is open when the lubrication pulse ends. Code AP is displayed as well as alarm duration in hours and minutes.
The Alarm indicator lamp on the cover is lit and the alarm relay goes into alarm mode.
The alarm can be reset with the Setting–button. An interrupted lubrication phase can be restarted manually by
pressing the Setting-button.
4.4 Air blowing
The purpose of air blowing is to clean the lubrication point before pumping the lubricant.
Air blowing starts in the beginning of the lubrication phase five (5) sensor pulses before the pump starts.
The sensor pulse starts air blowing during lubrication. The duration of the air blowing is set as seconds with parameter
A.b. If the value is set to 0, air blowing is not in operation.
4.5 Power failure
All settings are stored in the memory which is protected against power failures (EEPROM). If a power failure occurs,
the current status of the control center is stored in the memory: interval, alarm or lubrication. Once the power is back
on, the operation will resume from the status it was in before power failure occurred. An exception to this is the
lubrication phase. After the power failure, operation starts with interval counting.
5 Settings
5.1 General
Center settings can be divided into two groups:
•Set values
•Configuration settings
Set values are lubrication system basic values. For example, lubrication interval set values can be changed in settings
mode.
Configuration settings determine the center functions according to the lubrication system. These settings are usually
factory settings and there should not be any reason to change them during operation.
All settings are password-protected.

110s2AEN.doc 16.01.2013 Rev. 2A 8 (12)
5.2 Entering password
1Select code PASS at time display.
2Enter correct password using Setting- and arrow buttons.
3When Setting-button is released, the center goes into setting mode. The codes show now decimal points, for
example “C.C.”.
Note! The password for set values is 2.
5.3 Entering settings
1Select the code for the setting to be changed on the display. Value display codes change in the same order as in
the following table when -button is pressed and vice versa, when -button is pressed.
2Press Setting-button and keep it down.
3Use arrow buttons to select the desired setting on the display.
4Release Setting-button and the new setting is stored in the system memory.
5Exit setting mode by browsing the code PASS on the display by means of -button.
Note! If the arrow button is pressed down continuously, settings will change on the display at accelerating
speed.
Display code Description
C.C. Lubrication counter
L.t. Lubrication interval set value, when interval is counted as time
L.r. Lubrication interval set value, when interval is counted as full chain
rotations.
L.P. Set value for link pins per rotation
L.d. Selected lubrication mode
--Ct= automatic lubrication based on time
--Cr= automatic lubrication based on full chain rotations
--Ht= manual lubrication, time is displayed
--Hr= manual lubrication, number of chain rotations is displayed
P.r. Pressure control with external pressure switch in use Yes/No
5.3.1 Lubrication counter
Code C.C. displays the count of lubrications made.
The counter can be reset by setting the counter value to zero with Setting- and arrow buttons. The only changeable
counter setting is to reset the counter.

110s2AEN.doc 16.01.2013 Rev. 2A 9 (12)
5.3.2 Lubrication interval
Code L.t. or L.r. shows the lubrication interval set value on the display.
Enter desired lubrication interval value using Setting- and arrow buttons.
If the code is Lt:The time can be set within 0 h 00 min – 9999 h.
If the code is Lr:The time can be set within 0 - 9999 rotations.
5.3.3 Link pins per rotation
Code L.P. on value display shows the set value for link pins per rotation.
Enter desired value for link pins per rotation using Setting- and arrow buttons.
The value can be set within 0 … 9999.
5.3.4 Lubrication mode
The following lubrication modes are available:
•Ct= automatic lubrication based on time
•Cr= automatic lubrication based on full chain rotations
•Ht= manual lubrication, time is displayed
•Hr= manual lubrication, number of chain rotations is displayed
5.3.5 Pressure control
If the parameter P.r. has been set in status Yes, the pressure of the pump is monitored with an external pressure
switch.
5.3.6 Configuration settings
Configuration settings are factory settings. For a chain lubrication system, the settings are the following:
Display code Description
P.L. Duration of the pump control pulse 0000 ... 9999 ms.
Factory setting is 300 ms.
P.d.
Delay time between sensor pulse and pump control pulse 0000 .... 9999 ms.
Factory setting is 0.
P.F. Divider 000 ... 160. During lubrication, the system waits for the set amount of chain pulses
between each pump control pulse.
Factory setting is 3.
t.o Timeout value after which the interval counting is stopped if there are no sensor pulses.
Setting within 0000 ... 9999 s. If the value is set to 0, this function is not in operation.
See
also Interlocking
.
A.b. Pulse duration for air blowing 000 … 999 s. If the value is set to 0, this function is not in
operation.

110s2AEN.doc 16.01.2013 Rev. 2A 10 (12)
Note! Configuration settings can be accessed with password 22.
Note! There are several other settings in the configuration mode, but they are not documented in this
manual as the operator is not allowed to change them.
6 Start-up
The corresponding display code is in brackets.
6Ensure that the set operation mode (LF) is SPr. If this is not the case, please contact the manufacturer.
7Select the desired lubrication mode (Ld).
8Depending on the selected lubrication mode, set the lubrication interval time (Lt) or the number of full chain
rotations (Lr). In manual lubrication mode, these settings are insignificant.
9Set the value for link pins per rotation (LP).
10 Set the pressure switch control in use/out of use (Pr).
See also section 5.3.6 Configuration settings.
In configuration mode you can:
−change the duration of the pump control pulse
−divide the chain pulses for pump control
−adjust the delay time between sensor pulse and pump control pulse
−adjust the time-out value for pulse interval for interrupting the interval counting process
−set the pulse duration for air blowing

110s2AEN.doc 16.01.2013 Rev. 2A 11 (12)
7 Technical specifications
7.1 Technical data
Quantity Value Unit Description
t -20…+60 °C Operating temperature range
Uin 220 - 240, 50/60
100 - 130, 50/60
V AC, Hz
V AC, Hz
Power input, 160 VA max.
Voltage range is preset at factory and indicated in the type
plate of the control center.
Uout 24 V DC Control voltage, unregulated 5 A max.
Internal power supply for external lubrication system
components.
F1 1 (230)
2 (115)
AT (V AC)
AT (V AC)
Power input fuse, 20x5 mm glass tube fuse, slow
F2 5 AT Control voltage fuse, 24 V for I/O-voltage, 20x5 mm glass
tube fuse, slow
F3 2 AT Electronic system fuse, 15 V, 20x5 mm glass tube fuse, slow
200 x 300 x 120
(w x h x d)
mm Steel enclosure
IP65 Protection classification
7.2 Connections
All connections are measured for 2.5 mm2wire cross section area.
Inputs
•pulse sensor input for 2-wire sensor, NO, input voltage 22VDC (PS1)
•pressure switch input, optional (PS2)
•input for lubricant reservoir low level switch, NO (Level)
•interlocking, the equipment that is lubricated is in operation = switch open (Lock)
Outputs
•pump control, closing contact, connects 24V / 5 A max. (Pump)
•pump control 2, optional (Line 2)
•Control for air blowing (Line 1)
•alarm, 2 pcs potential-free changeover contacts, loading 50V / 1A max. (Alarm)
Cable channels in the casing
•5 pcs for 7-10 mm cable diameters
•1 pc for 10–14 mm cable diameters

110s2AEN.doc 16.01.2013 Rev. 2A 12 (12)
8 Spare parts
Table 1 Spare parts for SKF ST-1100s control center.
See Figure 2.
Item Description Order code
1 ST-1100 circuit board PCB+SWB ver 1.3 12501280
2 Indicator lamp green 15010251 T1 BI-PIN 10544083
3 Indicator lamp red 15010250 T1 BI-PIN 10544085
Figure 2 Spare parts for SKF ST-1100s control center
9 Contact information
Oy SKF Ab
P.O. Box 80 (Teollisuustie 6)
FI-40951 MUURAME
FINLAND
Tel. +358 (0) 207 400 800
Fax. +358 (0) 207 400 899
www.skf.com
Table of contents
Other SKF Controllers manuals

SKF
SKF Magforce DSP Series User manual

SKF
SKF Ecomag Installation and operating instructions

SKF
SKF Matrix User manual

SKF
SKF Magforce STD 10007 series User manual

SKF
SKF DU1-GKS EEX User manual

SKF
SKF 086501 User manual

SKF
SKF LMC 301 Series User manual

SKF
SKF CAHB-10 User manual

SKF
SKF CAHB-20E User manual

SKF
SKF IMx-M User manual