3 Product Overview SMA Solar Technology America LLC
User ManualSBxx-US-1XP-40-BA-en-1216
Energy meters in accordance with ANSI C12.20
The inverter type "SBx.x-1SP-US-40" can be retrofitted with the SMA Revenue Grade Meter Kit that
in accordance with ANSI C12.20 includes an energy meter. The inverter must be equipped either
with the SMA Cellular LTE Modem Kit or SMA RS485 Module to operate the SMA Revenue Grade
Meter Kit. The inverter type "SBx.x-1TP-US-40" is equipped with an energy meter as standard.
The energy meter fulfills the accuracy class 0.5 in accordance with ANSI C12.20. The energy
meter is a so called PV production meter intended to measure the generated energy of the inverter.
The measured values of the energy meter can be used for billing purposes.
Grid Management Services
The inverter is a grid support interactive inverter.
The inverter was tested in accordance with the UL1741 SA (2016-09-07) to be compliant with the
source requirements documents of the states available at the time. For connecting the inverter to the
utility grid, no additional grid monitoring equipment is necessary. A description of the tested
functions and instructions on the activation and setting of functions can be found in the technical
information "Grid Support Utility Interactive Inverters" at www.SMA-Solar.com.
PVRapidShutdownSystemEquipment
The inverter is a PVRapidShutdownSystemEquipment and performs the function of voltage
reduction according to UL 1741 CRD PV Rapid Shutdown Systems 2015. When a rapid shutdown
is triggered by disconnecting the utility grid, the inverter discharges independently on the AC side to
≤30 V within 30 seconds.
If a disconnection device is used in addition between the inverter and the PV array that disconnects
the PV array in the case of a rapid shutdown, the inverter discharges independently on the DC side
to ≤30V within 30 seconds.
The electric discharge on the DC side is deactivated by default and must be activated manually
after commissioning of the inverter via the user interface.
NOTICE - The Rapid Shutdown is tripped when opening the AC Disconnect. The AC Disconnect
must be clearly identified as Rapid Shutdown Initiator in accordance with National Electrical
Code®. The status of the Rapid Shutdown System is indicated depending on the On/Off position of
the AC Disconnect.
Parallel Operation of the DC Inputs A and B
The DC inputs A and B of the inverter can be operated in parallel and up to three strings can be
connected to it in parallel. As a result, as opposed to normal operation, up to three strings can be
connected directly to inverters with two DC inputs and up to four strings to inverters with three DC
inputs. The inverter automatically detects the parallel operation of the DC inputs A and B.
Secure power supply operation
You can connect an external outlet and a switch to the inverter in order to activate the outlet. In
case of a grid failure, the outlet supplies a load with current from the PV system. When the outlet is
activated via the switch, the load is supplied with current from the PV system. The inverter
automatically regulates the energy supply of the outlet depending on the solar irradiation on the PV
system. When the outlet is activated and a load is supplied with current from the PV system, the
inverter is disconnected from the utility grid and does not feed into the utility grid.