Smarteh Longo Modbus Products LMP-1.CA1M User manual

USER MANUAL
Longo Modbus Products
LMP-1.CA1M
Card Access module
Version 1
SMARTEH d.o.o. / Poljubinj 114 / 5220 Tolmin / Slovenia / Tel.: +3 6(0)5 3 44 00 / e-mail: info@smarteh.si / www.smarteh.si

Longo Modbus Products LMP-1.CA1M
Written by SMARTEH d.o.o.
Co yright © 2020, SMARTEH d.o.o.
User Manual
Document Version: 1
January, 2020
i

Longo Modbus Products LMP-1.CA1M
STANDARDS AND PROVISIONS: Standards, recommendations,
regulations and rovisions of the country in which the devices will
o erate, must be considered while lanning and setting u electrical
devices. Work on 100 .. 240 V AC network is allowed for authorized
ersonnel only.
DANGER WARNINGS: Devices or modules must be rotected from
moisture, dirt and damage during trans ort, storing and o eration.
WARRANTY CONDITIONS: For all modules LONGO LMP-1 – if no
modifications are erformed u on and are correctly connected by
authorized ersonnel – in consideration of maximum allowed
connecting ower, warranty of 24 months is valid from the date of
sale to the end buyer, but not more than 36 months after delivery
from Smarteh. In case of claims within warranty time, which are based
on material malfunctions the roducer offers free re lacement. The
method of return of malfunctioned module, together with descri tion,
can be arranged with our authorized re resentative. Warranty does
not include damage due to trans ort or because of unconsidered
corres onding regulations of the country, where the module is
installed.
This device must be connected ro erly by the rovided connection
scheme in this manual. Misconnections may result in device damage,
fire or ersonal injury.
Hazardous voltage in the device can cause electric shock and may
result in ersonal injury or death.
NEVER SERVICE THIS PRODUCT YOURSELF!
This device must not be installed in the systems critical for life (e.g.
medical devices, aircrafts, etc.).
If the device is used in a manner not s ecified by the manufacturer,
the degree of rotection rovided by the equi ment may be im aired.
Waste electrical and electronic equi ment (WEEE) must be collected
se arately!
LONGO LMP-1 com lies to the following standards:
•EMC: EN 61000-6-3:2007 + A1:2011, EN 61000-6-1:2007, EN 61000-
3-2:2006 + A1:2009 + A2: 2009, EN 61000-3-3:2013
•LVD: IEC 61010-1:2010 (3rd Ed.), IEC 61010-2-201:2013 (1st Ed.)
Smarteh d.o.o. o erates a olicy of continuous develo ment.
Therefore we reserve the right to make changes and im rovements to
any of the roducts described in this manual without any rior notice.
MANUFACTURER:
SMARTEH d.o.o.
Poljubinj 114
5220 Tolmin
Slovenia
ii

Longo Modbus Products LMP-1.CA1M
Longo Modbus Products LMP-1.CA1M
1 DESCRIPTION...................................................................................1
2 FEATURES.......................................................................................2
3 OPERATION.....................................................................................3
3.1 Modbus RTU variables.................................................................4
4 INSTALLATION..................................................................................6
4.1 Connection scheme....................................................................6
4.2 Mounting frame selection............................................................8
4.3 Mounting instructions.................................................................9
4.4 Module labeling.......................................................................10
5 TECHNICAL SPECIFICATIONS................................................................11
6 CHANGES .....................................................................................12
7 NOTES..........................................................................................13
iii

Longo Modbus Products LMP-1.CA1M
1 DESCRIPTION
LMP-1.CA1M RFID reader is intended to be used as an identity verification device at room entrance.
Module also rovides dis lay for four different messages and requests, usually activated from other
module inside the room. This messages are convenient to notify ersonnel (e.g. occu ied, do not
disturb, SOS, room service).
When RFID tag (key-card) is a roached to the reader, the green LED blinks and a short bee is
generated if code is successfully read out. In case key-card for corres ondent room is valid, the
green LED blinks again and a short bee is generated. Other devices can be activated at this event
like door lock o ening, turning light on... If the ID card number is not valid, the red LED blinks and a
longer bee is generated.
In case other (magnet or contact–chi ) card system is used for door unlock, LMP-1.CA1M module can
be used only to show messages.
LMP-1.CA1M module can be modified on customer request: custom front label, touch buttons added,
LEDs added, housing colour. Please contact manufacturer for more information.
LMP-1.CA1M reads unique ID (UID) from standard ISO/IEC 14443 A/MIFARE.
1

Longo Modbus Products LMP-1.CA1M
FEATURES
Figure 1: LMP-1.CA1M module.
Table 1: Features
RFID reader
LEDs for showing activated messages & requests: occu ied, do not disturb, room service, SOS
OK “ √ ” LED
FAULT “ X ” LED
Power LED
Internal fault LED
Internal built-in buzzer
2

Longo Modbus Products LMP-1.CA1M
3 OPERATION
O eration of the CA1M module is also de endent on arameters received on Modbus RTU
communication channel.
Reader RFID field is active always when module is owered u . If tag is ut inside RFID field, reader
tries to resolve RFID tag code. If code is read successfully, module activates status iIDNew,
generates a short bee , OK LED4 blinks and code is transmitted in iIDW1 - iIDW4 status fields. In
main module a lication this code can be read out and authenticated. If code has a ro riate
rights, main module should activate idCodeOK command. If code is not authorized, main module
a lication should activate idCodeFault command. Regarding command received, following action
are triggered on module:
idCodeOK ==> OK LED4 blink, short bee .
idCodeFault ==> FAULT LED3 blink, long bee .
Either command is received or not from main module a lication within 10 seconds, module clears
iIDNew status and waits for next RFID tag. While CA1M module is waiting for authorization res onse,
new RFID tags can not be read.
To check if communication is running, master toggles oCommToggleBit and then reads if
iCommToggleBit was toggled.
3

Longo Modbus Products LMP-1.CA1M
3.1 Modbus RTU variables
Do not use oll times smaller than 200 ms and greater than 4 s.
Table : 4xxxx, Holding registers
Reg. Name Description Raw → Engineering data
90 oSaveModbusSettings
Save EEPROM settings; change
the value from 0 to 12345 to
save settings
0, 12345
98 mbSlaveAddressMem Modbus Slave Address 1 .. 247 1 ..247→
99 mbBaudrateMem Modbus Baudrate
1 → 600 b s
2 →1200 b s
3 → 2400 b s
4 → 4800 b s
5 → 9600 b s
6 → 14400 b s
7 → 19200 b s
8 → 38400 b s
9 → 56000 b s
10 → 57600 b s
11 115200 b s→
other → 19200 b s (default)
100 mbParityMem Modbus Parity
0 none→
1 eve→n (default)
2 odd→
other none→
Table 3: 3xxxx, Input registers
Reg. Name Description Raw → Engineering data
1 iIDW1 RFID ID received word 1 0 .. 65535 0 .. 65535→
2 iIDW2 RFID ID received word 2 0 .. 65535 0 .. 65535→
3 iIDW3 RFID ID received word 3 0 .. 65535 0 .. 65535→
4 iIDW4 RFID ID received word 4 0 .. 65535 0 .. 65535→
6 iIDLength Lenght of ID code
0 →ID code not received
4 → 4 bytes
7 → 7 bytes
98 iFWver Software version 0 .. 65535 0 .. 65535→
99 iHWver1 Hardware version 1 0 .. 65535 0 .. 65535→
100 iHWver2 Hardware version 1 0 .. 65535 0 .. 65535→
4

Longo Modbus Products LMP-1.CA1M
Table 4: 0xxxx, Coils
Reg. Name Description Raw → Engineering data
1 oIDNewBee Dis Disable bee when new ID is
detected
0 Enabled→
1 Disabled→
2 oBuzz Set/Reset Buzzer 0 Reset→
1 Set→
3 oIDCodeFault ID code Fault confirm 0 Fault not confirmed→
1 Fault confirmed→
4 oIDCodeOK ID code OK confirm 0 OK not confirmed→
1 OK confirmed→
5 oIDFaultLedCmd Set/Reset Fault LED 0 Reset→
1 Set→
6 oIDOKLedCmd Set/Reset OK LED 0 Reset→
1 Set→
7 oLedOccu ied Set/Reset Occu ied LED 0 Reset→
1 Set→
8 oLedDoNotDisturb Set/Reset Do not disturb LED 0 Reset→
1 Set→
9 oLedRoomService Set/Reset Room service LED 0 Reset→
1 Set→
10 oLedSOS Set/Reset SOS LED 0 Reset→
1 Set→
11 oCommToggleBit Communication toggle bit loo 0, 1
Table 5: 1xxxx; Discrete inputs
Reg. Name Description Raw → Engineering data
1 iCommToggleBit Communication toggle bit loo
indicator 0, 1
2 iIDNew New ID detected 0 New ID not detected→
1 New ID detected→
5

Longo Modbus Products LMP-1.CA1M
4 INSTALLATION
4.1 Connection scheme
Figure : Connection scheme
6

Longo Modbus Products LMP-1.CA1M
Table 6: K1
K1.1 N.C. Not connected
K1.2 GND Ground
K1.3 7 .. 30 V DC Power su ly in ut
K1.4 Standard RS-485 A Data receive/send line A
K1.5 Standard RS-485 B Data receive/send line B
K1.6 N.C. Not connected
Table 7: LEDs & Buttons
LED1: red Communication On: RS-485 communication fault
Off: RS-485 communication OK
LED2: green Power su ly On: ower su ly OK
Off: ower su ly missing or ower off
LED3: blue Do not disturb On: request active
Off: no request
LED4: blue Room service On: request active
Off: no request
LED5: red FAULT “ X ” On: RFID key standard NOK or ID card number wrong
Off: No tag in roximity
LED6: green OK “ √ ”On: RFID key standard OK and ID card number valid
Off: No tag in roximity
LED7: blue SOS On: request active
Off: no request
LED8: blue Occu ied On: request active
Off: no request
Table 8: S1
SELECTOR Switch 1 Switch 2
User settings, from Modbus RTU registers OFF OFF
Not used OFF ON
Not used ON OFF
Default factory settings active,
19200b s/8 data bits/1 sto bit/EVEN ON ON
7

Longo Modbus Products LMP-1.CA1M
4. Mounting frame selection
Frame, suitable for CA1M module insertion, should be modular one at least 3 gang wide. Be careful
to have corres onding flush-mounting box rovided on the lace where module will be ositioned.
Smarteh has verified following lines to be com atible with LMP-1.CA1 module:
●Bticino – Living, Light
●Gewiss – Playbus, System
●Vimar – Plana, Idea
●Tem – Modul Soft, Modul Line
●Master
Frames of other vendors most robably suits as well, but they were not verified by Smarteh. Before
installation verify com atibility of non listed frames.
Module housing has a fin on each side, which can be easily removed with knife cutter or liers. This
ada tation enables housing to be build in various frame formats with two different de ths. With
regard to frame used you may remove fin for housing to fit in. RFID module should not be ositioned
close to conductive areas (e.g.: metal frames and metal cover late).
Figure 3: Module with
removable fin.
8

Longo Modbus Products LMP-1.CA1M
4.3 Mounting instructions
Figure 4: Housing dimensions
Dimensions in millimeters.
All connections, module attachments and assembling must be done while
module is not connected to the main ower su ly.
Module should not be mounted outdoors.
Several RFID anels should not be mounted close to each other. Minimum
distance to next anel is at least 30 cm. This restriction also a lies in case
of mounting anels on both sides of the same wall. Adequate shielding
material and rovisions could be used to avoid interference between
anels.
RFID anel should not be ositioned close to conductive areas (e.g.: metal
frames and metal cover late).
Mounting instructions:
1. Set the correct LMP-1.CA1M settings (refer to the Table 2 and Table 8).
2. Connect LMP-1.CA1M with a ro riate cable to the connector K1, Modbus RTU Master
equi ment and ower su ly source (refer to Table 6). Max. allowed tensile force is 30 N.
3. Put the LMP-1.CA1M in mounting frames.
4. Cover LMP-1.CA1M with cover late.
Modbus RTU settings source is set with DIP switch on the back of the LMP-1.MP1 module (Table 8).
NOTE: Signal wires must be installed se arately from ower and high voltage wires in accordance
with general industry electrical installation standard.
9

Longo Modbus Products LMP-1.CA1M
4.4 Module labeling
Figure 5: Label
Label (sam le):
Label description:
1. XXX-N.ZZZ - full roduct name.
◦XXX-N - Product family
◦ZZZ - roduct
2. P/N: AAABBBCCDDDEEE - art number.
▪AAA - general code for roduct family,
▪BBB - short roduct name,
▪CCDDD - sequence code,
•CC - year of code o ening,
•DDD - derivation code,
▪EEE – version code (reserved for future HW and/or SW firmware u grades).
3. S/N: SSS-RR-YYXXXXXXXXX - serial number.
◦SSS – short roduct name,
◦RR – user code (test rocedure, e.g. Smarteh erson xxx),
◦YY – year,
◦XXXXXXXXX– current stack number.
4. D/C: WW/YY - date code.
•WW – week and
•YY – year of roduction.
Optional
1. MAC
2. Symbols
3. WAMP
4. Other
10
XXX-N.ZZZ
P/N: AAABBBCCDDDEEE
S/N: SSS-RR-YYXXXXXXXXX
D/C: WW/YY

Longo Modbus Products LMP-1.CA1M
5 TECHNICAL SPECIFICATIONS
Table 9: Technical specifications
Power su ly from main module
Interconnection connector ty e RJ-12 6/6, 4/6
Power consum tion 1 W
RFID ty e ISO/IEC 14443 A/MIFARE
Max. reading distance 4 cm
Dimensions (W x H x D) 75 x 49 x 29 mm
Weight 40 g
Ambient tem erature 0 to 50 °C
Ambient humidity max. 95 %, no condensation
Maximum altitude 2000 m
Mounting osition horizontal
Trans ort and storage tem erature -20 to 60 °C
Protection class IP 20
11

Longo Modbus Products LMP-1.CA1M
6 CHANGES
The following table describes all the changes to the document.
Date V. Description
10.01.2020 1 The initial version, issued as LMP-1.CA1M module UserManual.
12

Longo Modbus Products LMP-1.CA1M
7 NOTES
13
Table of contents
Other Smarteh Control Unit manuals
Popular Control Unit manuals by other brands

rada
rada 566 Installation and Maintenance

Mitsumi
Mitsumi DWM-W016 user manual

Zonet
Zonet ZNS8030 Product data

VSpeak
VSpeak Electronic switch 20A (opto) manual

Technische Alternative
Technische Alternative ESR 31 Operation & installation instructions

Power integrations
Power integrations Scale-2 1SC0450E2B0 Applications manual