socomec ATys C20 User manual

CONTROLLER
ATyS C20/C30
Notice d’utilisation - Operating instructions
FGB
SOCOMEC GROUP SWITCHING PROTECTION & UPS
MAKE YOUR BUSINESS SAFE
532_214_b-1 8/07/05 12:12 Page 1

SOCOMEC - Réf.: 532 214 B
2
LA GAMME ATyS _________________________________3
PRÉSENTATION GÉNÉRALE _______________________4
Présentation des produits ________________________4
INSTALLATION ___________________________________5
Montage _______________________________________5
Dimensions_____________________________________5
Caractéristiques_________________________________5
RACCORDEMENTS_______________________________6
Circuits de commande ___________________________6
Commande électrique __________________________11
FONCTIONNEMENT _____________________________12
Présentation___________________________________12
Modes d’utilisation _____________________________13
Programmation ________________________________14
Exploitation____________________________________24
Visualisation ___________________________________26
Séquences automatiques _______________________28
AIDE AU DÉPANNAGE ___________________________31
ANNEXES ______________________________________32
Typologie des réseaux __________________________32
Programmation et câblage ATyS__________________33
THE ATyS RANGE _______________________________35
GENERAL PRESENTATION _______________________36
Product introduction ____________________________36
INSTALLATION __________________________________37
Mounting _____________________________________37
Dimensions ___________________________________37
Characteristics_________________________________37
CONNECTIONS _________________________________38
Control circuits_________________________________38
Electrical operation _____________________________43
OPERATION ____________________________________44
Presentation___________________________________44
Operational modes _____________________________45
Programming __________________________________46
Operation _____________________________________56
Visualisation ___________________________________58
Automatic sequences___________________________60
TROUBLESHOOTING GUIDE _____________________63
ANNEXES ______________________________________64
Network analysis _______________________________64
Programming and connections ATyS C30__________65
Sommaire
F
Summary
GB
532_214_b-1 8/07/05 12:12 Page 2

35
SOCOMEC - Réf.: 532 214 C
The ATyS family proposes a complete motorised
changeover range including electrical and mechanical
interlocking. Manual operation is always possible on all
the products in case of emergency.
The electric command is realised via a motorised
module, electronically driven by 2 types of logic:
• Remote controlled: ATyS 3 products are controlled by
volt free contacts allowing the switch to be driven in 1,
0 or 2 position. These contacts can come from an
external control logic.
• Automatic control: AtyS 6 products integrate all
controls, timers and relays required to realise a
Normal/Emergency application.
ATyS 6e and 6m versions also integrate the remote
controlled feature.
The motorised and control modules can easily be
replaced without disconnecting the power cables.
Controller
ATyS
THE
ATyS
RANGE
>
This instruction manual applies to following
products:
• Controller ATyS C20/C30
>
Following products are delivered with their own
instruction manual:
• ATyS 3s
• ATyS 3e, 6s, 6e
• ATyS 6m
• Remote interfaces ATyS D10 & D20
• Centroller ATyS C40.
For personnel and product safety, please
read the contents of these operating
instructions carefully before connecting.
ATyS 3s ATyS 3e ATyS 6s ATyS 6e ATyS 6m ATyS C30 ATyS C20 ATyS C40
MOTORISED CHANGEOVER
Dual power supply
Metering
Remote interfaces ATyS D10 & D20
Changeover
controller Dual gensetIntegrated control relay
Communication option
Com option
2 I/2 O option 2 inputs/2 outputs option

ATYS 448 A ATYS 453 A
Product introduction
Controller
ATyS
GENERAL PRESENTATION
ATyS C20/C30
36 SOCOMEC - Réf.: 532 214 C
Product introduction
LCD
Voltage sensing and
power supply terminals Keypad
Control terminals Modular frame
ATYS C20
LCD
RJ45 terminal Voltage sensing and
power supply terminals Keypad
Control terminals Modular frame
ATYS C30

Mounting
>
DIN rail mounting
Dimensions
Characteristics
37
SOCOMEC - Réf.: 532 214 C
Controller
ATyS
INSTALLATION
ATyS C20/C30
Mounting
Dimensions
Characteristics
106
26,5
48
58
90
93
45
62
>
IP
IP2 and class II on front face
>
Operation
• Temperature: -20 °C to +60 °C
• Humidity: 80% at 55 °C
95% at 40 °C
>
Consumption
7.5 VA max
>
Measurement category
Cat III
ATYS 449 A NBATYS 437 A

Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
SWITCHING TYPE TECHNOLOGY
Controller
ATyS
CONNECTIONS
ATyS C20/C30
38 SOCOMEC - Réf.: 532 214 C
Control circuits
Electrical operation
13 14 23 24 33 34 43 44 53 54
CA1 CA0 CA2
I1 I2
301 302 303 304 305 306
DC-*
DC+*
103
F1, F2
Fuse protection
230 Vac 5 A
205
L3
203
L1
106
L1
105
L2
104
L3N
III0C
O2
GE
L1
L2
L3
1N
L1
L2
L3
N2
Cable
RJ45 8/8
ONLY ON ATyS C30
F2F1
remote interface
ATyS D10 or D20
LOAD
DPS Ph
Double Power
Power
230 Vac
Control
Supply option
N
Remote interfaces maximum connection
cable (RJ45) = 3 m.
Maximum control cables lenght = 10 m.
In case of longer distance, insert control
relays.
ATYS 426 A GB
* Only on DC versions.
• Configure the type of control logic in impulse mode
(see Programming chapter). • Automatic Power supply 203-205 or 104-106
(see power supply chapter).

Controller ATyS
CONNECTIONS
39
SOCOMEC - Réf.: 532 214 C
Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
CONTACTOR TYPE TECHNOLOGY
13 14 23 24 33 34 43 44 53 54
I1 I2
301 302 303 304 305 306
103
F1, F2
Fuse protection
230 Vac 5 A
LOAD
205
L3
203
L1
106
L1
105
L2
104
L3N
III
O1 O2
GE
L1
L2
L3
1N
L1
L2
L3
N2
Cable
RJ45 8/8
ONLY ON ATyS C30
F2F1
ATyS D10 or D20
remote interface
K1
K2 K1
DC-*
DC+*
K2
K1 K2
ATYS 438 A GB
Remote interfaces maximum connection
cable (RJ45) = 3 m.
Maximum control cables lenght = 10 m.
In case of longer distance, insert control
relays.
* Only on DC versions.
• Configure the type of control logic in contactor (see
Programming chapter). • Automatic Power supply 203-205 or 104-106
(see power supply chapter).

Controller
ATyS
CONNECTIONS
ATyS C20/C30
40 SOCOMEC - Réf.: 532 214 C
Control circuits
Electrical operation
Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
CIRCUIT BREAKER TYPE TECHNOLOGY
>
Electrical interlocking via external control relays
L1
L2
L3
1N
L1
L2
L3
N2
F2F1
13 14 23 24 33 34 43 44 53 54
AUXILIARY CONTACT
BRE. 1 BRE. 2
I1 I2
301 302 303 304 305 306
103
F1, F2
Fuse protection
230 Vac 5 A
LOAD
205
L3
203
L1
106
L1
105
L2
104
L3N
III
O1 O2
GE
Cable
RJ45 8/8
ONLY ON ATyS C30
ATyS D10 or D20
remote interface
K1
K2
POS 1
closing
POS 2
opening
POS 2
closing
POS 1
opening
K2
K1
DC-*
DC+*
ATYS 439 A GB
Remote interfaces maximum connection
cable (RJ45) = 3 m.
Maximum control cables lenght = 10 m.
In case of longer distance, insert control
relays.
* Only on DC versions.
• Configure the type of control logic in contactor (see
Programming chapter). • Automatic Power supply 203-205 or 104-106
(see power supply chapter).

Controller ATyS
CONNECTIONS
41
SOCOMEC - Réf.: 532 214 C
Control circuits
400 Vac (P-P) APPLICATION WITH NEUTRAL CONDUCTOR
CIRCUIT BREAKER TYPE TECHNOLOGY
>
Electrical interlocking not integrated
Breaker 1
OPENING
Breaker 2
13 14 23 24 33 34 43 44 53 54
I1 I2
301 302 303 304 305 306
103
F1, F2
Fuse protection
230 Vac 5 A
LOAD
205
L3
203
L1
106
L1
105
L2
104
L3N
GE
L1
L2
L3
1N
L1
L2
L3
N2
Cable
RJ45 8/8
ONLY ON ATyS C30
F2F1
ATyS D10 or D20
remote interface
Breaker 1
CLOSING
Breaker 2
DC-*
DC+*
This drawing is not including the electrical
interlock.
ATYS 440 B GB
Remote interfaces maximum connection
cable (RJ45) = 3 m.
Maximum control cables lenght = 10 m.
In case of longer distance, insert control
relays.
It might be necessary for some breakers not
to set up OMR and OMF timers to 0.
(refer to programming)
* Only on DC versions.
• Configure the type of control logic in breaker
(see Programming chapter) • Automatic Power supply 203-205 or 104-106
(see power supply chapter).

Controller
ATyS
CONNECTIONS
ATyS C20/C30
Control circuits
42 SOCOMEC - Réf.: 532 214 C
Control circuits
Electrical operation
Denomination
Terminals
Description Characteristics
Recommended
section
Power supply N (103) Neutral 440 V ac (phase-phase) 1.5 mm2
Source L3 (104) Phase 3 maximum, 50/60 Hz
L2 (105) Phase 2 254 V ac (phase neutre)
L1 (106) Phase 1 maximum, 50/60 Hz
Power supply L1 (203) Phase 1 440 V ac (phase-phase) 1.5 mm2
Source L3 (205) Phase 3 maximum
Power supply DC(1)
DC- Power supply 0 V From 9 V dc to 30 V dc 1.5 mm2
12Vdc, 24Vdc
DC+ Power supply +V dc
Genset(2) 13 Genset start/stop relay - 2 stable positions Dry contact 1.5 mm2
start signal 14 Programmable state - factory setting = NO, close to start 5A AC1/250 V
Control 23 Impulse mode: order to close source 5 A AC1/250 V 1.5 mm2
(impulse, 24 Contactor mode: order to close contactor source
contactor Breaker mode: order to close breaker source
and breaker 33 Impulse mode: order to close source 5 A AC1/250 V 1.5 mm2
mode to 34 Contactor mode: order to close contactor source
programm) Breaker mode: order to close breaker source
43 Impulse mode: order to reach position 0 5 A AC1/250 V 1.5 mm2
44 Contactor mode: programmable relay O1
Breaker mode: order to open breaker source
53 Impulse mode: programmable relay O2 5 A AC1/250 V 1.5 mm2
54 Contactor mode: programmable relay O2
Breaker mode: order to open breaker source
Information 301 Auxiliary contact information position 1 AC1 Do not connect to 1.5 mm2
auxiliary 302 Auxiliary contact information position 0 AC0 any power supply
contacts 303 Auxiliary contact information position 2 AC2
Programmable 304 Programmable input In1 Do not connect to 1.5 mm2
Inputs 305 Programmable input In2 any power supply
Common 306 Specific voltage supply Do not connect to 1.5 mm2
input Common terminals 301 to 306 any power supply
Remote interface
RJ Remote interface ATyS D10 or D20 Maximum connection RJ45 8/8
connection cable 3 m
(1) Only on DC version
(2) Refer to programming, Setup, to modify relay state.
2
1
2
2
2
1
1
1
2
1

Electrical operation
POWER SUPPLY
ATyS C20/C30 integrates 2 power inputs (104-106, 203-
205), and consider the available source to keep the
product operational. Product supplied when voltage on
terminals ≥100 Vac
For the DC version, these is only one power supply input
(DC-, DC+).
Controller ATyS
CONNECTIONS
43
SOCOMEC - Réf.: 532 214 C
AUT position
priority power source
backup power source
product ON
1
2
ATYS 444 A GB
: terminals 104-106 : terminals 203-205
21

Presentation
The product allows:
• sources control,
• automatic transfer control in AUT mode,
• parameters configuration,
• voltage and frequency metering,
• system state display,
• alarm or fault indication,
Controller
ATyS
OPERATION
ATyS C20/C30
44 SOCOMEC - Réf.: 532 214 C
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
7 digits + 14 pointers
LCD
Green led is on when product is
powered
POWER led
RJ45 terminal for
ATyS D10 or D20.
If connected, the
LCD is off
RJ45 connection*
Led is on when product is faulty.
Disconnect power supplies to reset
FAULT led
- Led is on: source = OK
- Led is off: source is not available
Sources state
2 green leds:
- switch I state
- switch II state
Switch state
- Automatic sequence simulator (test on load)
- Genset remote start (test off load)
- Changeover switch position control (local or remote)
Operational modes
Keypad
Escape Navigation
Validation
LCD & leds test
Operations
SOFTWARE VERSION
Displayed after reset.
(3 minutes power off action to allow reset).
Version
number
ATYS 428 A GB
ATYS 427 A GB
* only on ATyS C30.

Controller ATyS
OPERATION
45
SOCOMEC - Réf.: 532 214 C
PHASES ROTATION CONTROL
V1
V2V3
OK
V1
V3V2
NOK
Operational modes
VISUALISATION
Measured values & parametered timers display. Always
accessible without code.
PROGRAMMING
Parameters configuration. Password access (code 1000
from factory).
The manual mode must be programmed on an input if
required.
OPERATION
Test sequences. Password access (code 4000).
Available functions in mode
Available functions in “AUT ” mode
Programming Visualisation
Programming Visualisation
Loss of main
source
sequence
Main’s
return
sequence
Operation
Test off load Test on load
Operation
Test off load
Programming
Code Operation
Code
Programming
Code Operation
Code
Function available only on source in case of 3NBL,
4NBL and 41NBL network.
If a fault is detected, the source is not indicated as
available.
1
1
ATYS 219 A
ATYS 441 A
displayed according to faulty source.
1 2

Programming
Controller
ATyS
OPERATION
ATyS C20/C30
46 SOCOMEC - Réf.: 532 214 C
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
• This mode allows product parameters configuration
• Always accessible in mode (when programmed on
an input)
• Always accessible in AUT mode, changeover switch on
priority source, priority source being available
• Not accessible when “test off load”, “test on load”
functions are active or during automatic sequence.
Parameters requiring programming before
use:
• type of network
• nominal voltage
• nominal frequency
• control logic
• number of auxiliary contact.
>
Navigation in the menus
• Parameters access: Press “up”, “down”, “left” & “right” push buttons
• Parametermodification: press “left” & “right” push button to access the parameter to modify
Press “up’’ and “down” push buttons to modify the parameter
and “validate”
• Return to main menu: press “ESC” push button
Value is only modified after validation
+
or
+
>
Programming exit
• Press and hold for 5 s
“validation” push button
>
Programming access
• Step 1: press and hold for 5 s
“validation” push button
•Step 2: enter code (factory code = 1000)
using navigation push buttons
• Step 3: press validation
push button

Programming
Controller ATyS
OPERATION
47
SOCOMEC - Réf.: 532 214 C
PROGRAMMING MENU ARCHITECTURE
ESC ESC ESC ESC
Setup Voltage
Frequency
Timer 2I/ 2O
1 2
Type of network
1 2
Network 1 over
voltage
threshold
1 2
Network 1 over
frequency
threshold
1 2
Main Failure
Timer
1 2
1 2
Phase-Phase
nominal voltage
Nominal
frequency
1 2
Network 1 over
voltage
threshold
hysteresis
1 2
Network 1 over
frequency
threshold
hysteresis
1 2
Delay on
Transfer
Timer
1 2 1 2 1 2 1 2 1 2
1 2
Network 1
under voltage
threshold
1 2
Network 1
under frequency
threshold
1 2
O main failure
Timer
1 2
1 2
1 2
Network priority
selection:
or 21
Genset start
signal state
Manuel
retransfer
1 2
Network 1
under voltage
threshold
hysteresis
1 2
Network 1
under frequency
threshold
hysteresis
1 2
Main Return
Timer
1 2
Option 1
Input 1 (variable
selection)
1 2
Option 1
Input 1 (contact
state selection)
1 2
Option 2
Input 2 (variable
selection)
1 2
Option 2
Input 2 (contact
state selection)
1 2
Output 1*
1 2
Output 2*
1 2
Load shedding
timer**
1 2
Impulse,
breaker or
contactor logic
12
Number of
auxiliary contact
12
Return on
position 0
-> 2
1
12
Return on
position 0
-> 1
2
1 2
Network 2 over
voltage
threshold
1 2
Network 2 over
frequency
threshold
1 2
O main Return
Timer
1 2
Number of
permutation
counter Reset
1 2
Network 2 over
voltage
threshold
hysteresis
1 2
Network 2 over
frequency
threshold
hysteresis
1 2
Cool Down
Timer
1 2
Network 2
under voltage
threshold
1 2
Network 2
under frequency
threshold
1 2
Programming
code modification
See page 50 See page 51 See page 52 See pages 53 to 55See page 49
1 2
Network 2
under voltage
threshold
hysteresis
1 2
Network 2
under frequency
threshold
hysteresis
* Availability of output functions depending on control logic selection (impulse, breaker or contactor logic)
** Displayed if LS variable has been selected.
ESC

Programming
Controller
ATyS
OPERATION
ATyS C20/C30
48 SOCOMEC - Réf.: 532 214 C
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
PARAMETER MODIFICATION
>
Example:
Modify network nominal voltage from 400 to 230 V.
1
ATI 074 A
Press to access first digit (blinking)
Press
2X to display 2 (blinking)
Press
to access second digit (blinking)
Press
3X to display 3 (blinking)
Press to validate

Programming
Controller ATyS
OPERATION
49
SOCOMEC - Réf.: 532 214 C
Network
nominal
frequency
Network nominal frequency 50 Hz or 60 Hz 50 Hz
1 2
PARAMETERS CHARACTERISTICS
>
Menu Setup
LCD Denomination Definition Setting Default
range values
* Refer to annexes.
(1) It might be necessary for some breakers not to set up OMR and OMF timers to 0. (2 sec.)
1 2
Type of
network*
Number of active conductors of controlled network
(refer to annexes)
1BL, 2BL,
2NBL, 3NBL,
4NBL, 41 NBL
4NBL
Network
nominal voltage
Phase-Neutral voltage for 1BL & 41NBL
Phase-Phase voltage for others
from 100 V
to 400 V
400 V
Network priority
selection
Manual
Retransfer
Activation of the feature
Keypad selection (1 or 2)
Also possible via external contact using option
1 or 2
(or )
2
11 ()
1
Programming
code
modification
Possible to change the programming code from 0000 to
9999
Yes or No
1000
No
Number of
permutation
counter Reset
Allows source -> source automatic sequences
counter reset
21 Yes or No No
Type of control
logic selection
Impulse, contactor or breaker.
It might be necessary for some breakers not to set up
OMR and OMF timers to 0 (2 sec. for exemple).
Imp, con, brE Imp
1 2
1 2
1 2
1 2
1 2
Genset start
signal state
Normally opened or closed NO or NC NO
1 2
1 2
Number of
auxiliary contact
Depending on the number if available auxiliary contacts
(switch, contactor, breaker)
0, 2, 3 2
12
Parameter 1,
return in
position 0
Allows to go to position 0 in case of voltage or frequency
outage (out if the defined U, f range)
Yes or No No
12
Parameter 2
return in
position 0
Allows to go to position 0 in case of voltage or frequency
outage (out if the defined U, f range)
Yes or No No
12
1 2

Programming
Controller
ATyS
OPERATION
ATyS C20/C30
50 SOCOMEC - Réf.: 532 214 C
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
>
Volt Menu
Threshold detection starts from the loss of source
or source return sequence.
LCD Denomination/ Definition Setting Default
range values
t100
Available source
Controlled value (voltage)
Over voltage threshold (oU)
Under voltage threshold (uU)
Over voltage hysteresys
threshold (oUh)
Under voltage hysteresys
threshold (uUh)
%
ATYS 243 A GB
Network 1 over voltage threshold From 102
to 120%
115%
Network 1 over voltage threshold hysteresis From 101
to 119% (< oU)
110%
Network 1 under voltage threshold From 80
to 98%
85%
Network 1 under voltage threshold hysteresis From 81
to 99% (> uO)
95%
Network 2 over voltage threshold From 102
to 120%
115%
Network 2 over voltage threshold hysteresis From 101
to 119% (< oU)
110%
Network 2 under voltage threshold From 80
to 98%
85%
Network 2 under voltage threshold hysteresis From 81
to 99% (> uU)
95%
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
Values definition: % of nominal values
Hysteresis values range is limited by thresholds values.

Programming
Controller ATyS
OPERATION
51
SOCOMEC - Réf.: 532 214 C
>
Frequency Menu
Threshold detection starts from the loss of source
or source return sequence.
LCD Denomination/ Definition Setting Default
range values
t100
%
Available source
Controlled value (frequency)
Over frequency threshold (oU)
Under frequency threshold (uU)
Over frequency hysteresys
threshold (oUh)
Under frequency hysteresys
threshold (uUh)
ATYS 286 A GB
Network 1 over frequency threshold From 101
to 120%
105%
Network 1 over frequency threshold hysteresis From 100.5
to 119.5% (< oF)
103%
Network 1 under frequency threshold From 80
to 99%
95%
Network 1 under frequency threshold hysteresis From 80.5
to 99.5% (> uF)
97%
Network 2 over frequency threshold From 101
to 120%
105%
Network 2 over frequency threshold hysteresis From 100.5
to 119.5% (< oF)
103%
Network 2 under frequency threshold From 80
to 99%
95%
Network 2 under frequency threshold hysteresis From 80.5
to 99.5% (> uF)
97%
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2
Values definition: % of nominal values
Hysteresis values range is limited by thresholds values.

Programming
Controller
ATyS
OPERATION
ATyS C20/C30
52 SOCOMEC - Réf.: 532 214 C
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
>
Menu Timer
1 2
LCD Denomination Definition Setting Default
range values
Main Failure
Timer
Delays priority network failure detection
Delay on
transfer Timer
O Main failure
Timer
Main return
Timer
Standby network stability validation before transfer
Rest in O position when transferring
from main network to secondary network
Main network stability validation before re-transfer
from 0 to 60 s
from 0 to 60 s
from 0 to 20 s
from 0 to 30 min
5 s
5 s
0 s
2 min
1 2
1 2
1 2
O main return
Timer
Rest in O position when re-transferring from standby
network to main network
from 0 to 20 s 0 s
1 2
Cool down
Timer
Allows generator cooling down period after load’s
retransfer from standby source (generator) to Main source
from 0 to 30 min 4 min
1 2
1 2
This manual suits for next models
2