Controller ATyS
CONNECTIONS
41
SOCOMEC - Réf. : 532 929 B
Control circuits
Denomination
Terminals
Description Characteristics
Recommended
section
Power supply L3 (104) Phase 3 440 V ac (phase-phase) 1.5 mm2
Source L1 (106) Phase 1 maximum, 50/60 Hz
Power supply L1 (203) Phase 1 440 V ac (phase-phase) 1.5 mm2
Source L3 (205) Phase 3 maximum, 50 /60 Hz
Power supply DC
DC- Power supply 0 V From 9 V dc to 30 V dc 1.5 mm2
12Vdc, 24Vdc
DC+ Power supply + V dc maxi.
Genset 13 Genset start/ stop relay - 2 stable positions Dry contact 1.5 mm2
start signal(1) 14 Programmable state - factory setting = NO, close to start 5A AC1/250 V
Control 23 Impulse mode: order to close source 5 A AC1/ 250 V
(impulse, 24 Contactor mode: order to close contactor source
contactor Breaker mode: order to close breaker source
and breaker 33 Impulse mode: order to close source 5 A AC1 / 250 V 1.5 mm2
mode to 34 Contactor mode: order to close contactor source
programm) Breaker mode: order to open breaker source
43 Impulse mode: order to close position 0 5 A AC1/ 250 V 1.5 mm2
44 Contactor mode: programmable relay O1
Breaker mode: order to close breaker source
Genset 53 Genset start/ stop relay - 2 stable positions 5 A AC1/ 250 V 1.5 mm2
start signal(1) 54 Programmable state - factory setting = NO, close to start
Information 301 Auxiliary contact information position 1 CA1 Do not connect to 1.5 mm2
auxiliary 302 Programmable input 3 any power supply
contacts 303 Auxiliary contact information position 2 CA2
Programmable 304 Programmable input 1 Do not connect to 1.5 mm2
Inputs 305 Programmable input 2 any power supply
Common 316 Specifique voltage supply Do not connect to 1.5 mm2
input Common terminals 301 to 310 any power supply
(1) Refer to programming, Setup, to modify relay state.