SolarEdge Firefighter Gateway User manual


Disclaimers
Firefighter Gateway Installation Guide MAN-01-00113-1.2
1
Disclaimers
Important Notice
Copyright © SolarEdge Technologies Inc. All rights reserved.
No part of this document may be reproduced, stored in a retrieval system or transmitted, in any form or
by any means, electronic, mechanical, photographic, magnetic or otherwise, without the prior written
permission of SolarEdge Technologies Inc. also efeed to heei as “olaEdge.
This document is solely for the use of SolarEdge customers and employees.
The material furnished in this document is believed to be accurate and reliable. However, SolarEdge
assumes no responsibility for the use of this material. SolarEdge reserves the right to make changes to the
material at any time and without notice. You may refer to the SolarEdge web site (www.solaredge.com)
for the most updated version of this and other documents.
All company and brand products and service names are trademarks or registered trademarks of their
respective holders.
Patent marking notice: http://www.solaredge.com/groups/patent
The general terms and conditions of purchase of SolarEdge products shall apply.
The content of these documents is continually reviewed and amended, where necessary. However,
discrepancies cannot be excluded. No guarantee is made for the completeness of these documents.
Please note: This product is intended to provide remote shutdown of the SolarEdge PV harvesting system,
to enable safer access to a building in the event of fire. This product DOES NOT reduce the risk of fire or
protect firefighters or others accessing a building in the event of a fire.
If the RS485 communication between the firefighter gateway and the SolarEdge inverter(s) is
disconnected for any reason (including fire), the firefighter gateway LCD will display "No
Communication" or "Partial Com.". In this case, the firefighter gateway cannot be relied upon to
disconnect the SolarEdge PV harvesting system.
FCC Compliance
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant
to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can
be determined by turning the equipment OFF and ON, you are encouraged to try to correct the
interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for compliance may void the
use’s authoity to opeate the euipet.

Contents
Firefighter Gateway Installation Guide MAN-01-00113-1.2
2
Contents
Disclaimers......................................................................................................................... 1
Important Notice ...............................................................................................................1
FCC Compliance .................................................................................................................1
Contents............................................................................................................................. 2
About This Guide................................................................................................................ 4
Support and Contact Information ....................................................................................... 5
Handling and Safety Instructions ........................................................................................ 6
Chapter 1: Introducing the SolarEdge Firefighter Gateway ................................................. 7
Overview............................................................................................................................7
Firefighter Gateway User Interfaces..................................................................................8
LCD and LCD-Menu Buttons...............................................................................................8
Communication Connectors ..............................................................................................9
Other Interfaces.................................................................................................................9
Chapter 2: Installing the SolarEdge Firefighter Gateway ................................................... 10
Safety...............................................................................................................................10
Transport and Storage .....................................................................................................10
Package Contents ............................................................................................................10
Installation Equipment.....................................................................................................10
Installation Guidelines .....................................................................................................11
Installation Workflow ......................................................................................................11
Mounting the Firefighter Gateway ..................................................................................12
Connecting the Firefighter Gateway to AC ......................................................................13
Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control ............................... 14
Overview..........................................................................................................................14
Connecting and Configuring an Emergency Stop Button to the Gateway .......................16
Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation ................... 18
Overview..........................................................................................................................18
Connecting and Configuring the RS485 ...........................................................................18
Verifying the Connection .................................................................................................22
Troubleshooting the RS485 Communication ...................................................................22
Chapter 5: Emergency System Shutdown ......................................................................... 24
Chapter 6: LCD –Status Screens and Setup Options.......................................................... 26
Status Screens..................................................................................................................26
Main Firefighter Gateway Status............................................................................................. 26
ID Status ..................................................................................................................................26
Server Communication Status .................................................................................................26
IP Status .................................................................................................................................. 27
ZigBee Status...........................................................................................................................27
Wi-Fi Status ............................................................................................................................. 28
Communication Ports Status ................................................................................................... 28

Contents
Firefighter Gateway Installation Guide MAN-01-00113-1.2
3
Setup Menu Options........................................................................................................29
Language ................................................................................................................................. 31
Communication.......................................................................................................................31
Remote Shutdown................................................................................................................... 33
Display.....................................................................................................................................33
Maintenance ...........................................................................................................................33
Information .............................................................................................................................34
Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional) ................. 35
Communication Dataflow ................................................................................................35
Communication Types .....................................................................................................35
Creating an Ethernet (LAN) Connection...........................................................................36
Overview ................................................................................................................................. 36
Ethernet Communication Configuration Options ....................................................................36
Connecting and Configuring LAN............................................................................................. 37
Troubleshooting Ethernet Communication .............................................................................39
Additional Connection Options........................................................................................40
Creating a Wireless ZigBee Connection................................................................................... 40
Creating a Wi-Fi Connection....................................................................................................40
Appendix A: Technical Specifications................................................................................ 41

About This Guide
Firefighter Gateway Installation Guide MAN-01-00113-1.2
4
About This Guide
This user guide is intended for Photovoltaic (PV) installers, technicians, maintainers and integrators who
use the SolarEdge power harvesting system.
This guide describes the process of installing and configuring the SolarEdge Firefighter gateway (also
referred to herein as the "gateway").
This guide assumes that the SolarEdge power harvesting system is already installed and commissioned. For
additional information about how to install and commission the SolarEdge power harvesting system, refer
to the relevant inverter or safety and monitoring system (SMI) installation guide.
The guide includes the following chapters:
Chapter 1: Introducing the SolarEdge Firefighter Gateway, page 7, introduces the SolarEdge
firefighter gateway.
Chapter 2: Installing the SolarEdge Firefighter Gateway, page 10, describes how to install the
SolarEdge firefighter gateway.
Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control, page 14, describes how to
connect and use an external emergency stop button.
Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation, page 18, describes how
to connect the firefighter gateway to inverters or Safety and Monitoring Interface (SMI) using the
RS485 bus connection.
Chapter 5: Emergency System Shutdown, page 24, describes how to use the emergency stop button
to stop the power production.
Chapter 6: LCD –Status Screens and Setup Options, page 26, describes how to configure the
SolarEdge gateway and how to identify its status.
Chapter 7: Setting Up Monitoring through the Firefighter Gateway (Optional), page 35, describes
how to set up communication through the SolarEdge firefighter gateway to the SolarEdge
monitoring portal
Appendix A: Technical Specifications, page 41, provides the electrical and mechanical specifications
of the SolarEdge Gateway device.
For further information, datasheets and the most up-to-date certifications for various products in different
countries, please visit the SolarEdge website: www.solaredge.com

Support and Contact Information
Firefighter Gateway Installation Guide MAN-01-00113-1.2
5
Support and Contact Information
If you have technical queries concerning our products, please contact us:
US & Canada
1877 360 5292
support@solaredge.us
Germany
+49 89-45459730
support@solaredge.de
France
0800917410
support@solaredge.fr
Belgium
080073041
support@solaredge.be
Italy
800 784 824
support@solaredge.it
Netherlands
08000221089
support@solaredge.com
United Kingdom
0800 028 1183
Greece
00800125574
Israel
+972 73 240-3118
Australia
1800 465 567
Worldwide
+972 73 240-3118
Fax
+972 73 240-3117
US: +1 (530) 273-2769
Before contacting SolarEdge, please ensure you have the following information readily available:
The communication method to the SolarEdge server
The product serial number as appears on its label. The serial number can also be viewed in the
ID Status screen, as described on page 26.
Your software version, which can be viewed in the ID Status screen, as described on page 26

Handling and Safety Instructions
Firefighter Gateway Installation Guide MAN-01-00113-1.2
6
Handling and Safety Instructions
During installation, testing and inspection, adherence to the following handling and safety instructions is
mandatory.
The following safety symbols may be used in this document. Familiarize yourself with the symbols and
their meaning before installing or operating the system.
WARNING!
Denotes a hazard. It calls attention to a procedure that, if not correctly performed or adhered to, could
result in injury or loss of life. Do not proceed beyond a warning note until the indicated conditions
are fully understood and met.
CAUTION:
Denotes a hazard. It calls attention to a procedure that, if not correctly performed or adhered to, could
result in damage or destruction of the instrument. Do not proceed beyond a caution sign until the
indicated conditions are fully understood and met.
NOTE:
Denotes additional information about the current subject.
IMPORTANT SAFETY FEATURE:
Denotes information about safety issues.

Chapter 1: Introducing the SolarEdge Firefighter Gateway
Firefighter Gateway Installation Guide MAN-01-00113-1.2
7
Chapter 1: Introducing the SolarEdge
Firefighter Gateway
Overview
The firefighter gateway provides centralized safety management of SolarEdge systems: If the firefighter
gateway is properly installed and fully functional, firefighters can halt production of a SolarEdge
photovoltaic (PV) power harvesting system and have visual acknowledgement that the installation outputs
a safe DC voltage. The power production can be stopped either manually through an emergency stop
button or automatically through a Fire Alarm Control Panel system. This stops the AC production and
reduces stig DC voltage to a safe voltage usig the uiue “afeDC™ featue.
The firefighter gateway can connect to SolarEdge inverters and to Safety and Monitoring Interfaces (SMIs).
Although DC voltage can be reduced directly from the inverter/SMI or by shutting off the AC voltage, using
the firefighter gateway provides a clear indication of DC voltage shutdown. The firefighter gateway
enables shutting off the installation from a distance of up to 1,000m, while getting visual feedback that the
PV installation is safe.
Figure 1: The SolarEdge Firefighter Gateway
Figure 2: The SolarEdge Firefighter Gateway Connections

Chapter 1: Introducing the SolarEdge Firefighter Gateway
Firefighter Gateway Installation Guide MAN-01-00113-1.2
8
Firefighter Gateway User Interfaces
Figure 3: Gateway Interfaces
LCD and LCD-Menu Buttons
The LCD screen displays status information of the SolarEdge firefighter gateway and various menus for
configuration options. The LCD panel and buttons are used during the following processes:
Operational Mode: The LCD panel allows checking that the gateway is working properly. Refer to
Status Screens on page 26 for a description of this option. Use the LCD user buttons to toggle
through the informative displays and select options.
Setup: After mounting the gateway, the installer may perform basic gateway configuration, as
described in Setup Menu Options on page 29.
Four buttons are used for controlling the LCD menus (see Figure 3).
Esc: Moves the cursor to the beginning of the parameter, goes to the previous menu, and cancels a
value change.
Up (1), Down (2): Moves the cursor between menu options, moves among the characters of a
parameter, and toggles between possible characters when setting a value.
Enter (3): Selects a menu option or accepts a value change. Also used to enable LCD backlight.
Esc
Up (1)
Down (2)
Enter (3)
LEDs DC Micro SD Ethernet
(power
supply
input) LCD User Buttons
LCD
Optional Optional
Antenna1 Antenna2 Control RS485-1 SW1 RS485-2 RS232 Mini-USB
(ZigBee, SW2
Wi-Fi)

Chapter 1: Introducing the SolarEdge Firefighter Gateway
Firefighter Gateway Installation Guide MAN-01-00113-1.2
9
Communication Connectors
Antenna1: Used for optional wireless antenna connection –ZigBee or Wi-Fi (refer to Creating a
Wireless ZigBee Connection on page 40 and Creating a Wi-Fi Connection on page 40)
Antenna2: Currently not installed
RS485-1 and RS485-2: Used for connecting external devices to the gateway (refer Chapter 4:
Connecting the Firefighter Gateway to the SolarEdge Installation on page 18)
RS232: Enables connection of the SolarEdge gateway to an external device using an RS232 interface
Mini-USB: Enables PC/laptop connection for using the SolarEdge configuration tool.
Ethernet: Enables connecting the SolarEdge gateway to the SolarEdge monitoring portal through an
Ethernet switch/router (refer to Creating an Ethernet (LAN) Connection on page 35). The Ethernet
switch/router should be connected to the Internet.
Other Interfaces
Control: Used for connection to an external emergency stop button (refer to Chapter 3: Connecting
Emergency Stop Button or Fire Alarm Control on page 14).
SW1/SW2: RS485-1/2 termination
DC: Used for the power supply input as described in Connecting the Firefighter Gateway to AC on
page 13
Micro SD: Used for field software upgrade
Sensors: Not applicable
LEDs: All LEDs are ON while the SolarEdge gateway is powered up or configured.

Chapter 2: Installing the SolarEdge Firefighter Gateway
Firefighter Gateway Installation Guide MAN-01-00113-1.2
10
Chapter 2: Installing the SolarEdge
Firefighter Gateway
Safety
CAUTION:
For North America only: The product’s communication with external devices must not use wires
that span more than one building, as per the UL 60950-2 standard.
Transport and Storage
Transport the SolarEdge gateway in its original packaging, without exposing it to unnecessary shocks. If the
original package is no longer available, use a similar box, which can be fully closed.
Store the SolarEdge gateway in a dry place where ambient temperatures are -40°C (-40°F) to
+60°C (140°F).
Package Contents
Firefighter gateway
100-240VAC to 12VDC power supply with an interchangeable AC plug (US, EU, AUS, UK)
Accessory kit including:
Three 3-pin terminal blocks
One 6-pin terminal block
Installation Equipment
Standard tools can be used during the installation of the SolarEdge gateway. The following is a
recommendation of the equipment needed for installation:
Emergency stop button (recommended: a button with a locking feature, which stays mechanically
locked in the off position until turning it clockwise to release it), or a fire alarm control system with
relay output interface
Allen screwdriver for M5/M6 screw types
Standard flat head screwdrivers set
Voltage tester screwdriver
Drill and 4mm diameter bits
Wire cutters
Wire strippers
Voltmeter
Three twisted wires or four-wire twisted pair cable
For installing the communication options: CAT5/6 Ethernet cable

Chapter 2: Installing the SolarEdge Firefighter Gateway
Firefighter Gateway Installation Guide MAN-01-00113-1.2
11
Mounting the firefigher safety gateway
Connecting an emergency stop button or a fire
alarm control system
Connecting the firefighter safety gateway to the
SolarEdge installation
Configuring the
firefighter safey gateway and inverters/SMI
Verifying PV system shutdown using the firefighter
gateway
Using the firefighter safety gateway to connect the
installation to the monitoring server (optional)
Installation Guidelines
The following requirements apply when locating and mounting the SolarEdge Gateway:
The SolarEdge gateway is suitable for mounting indoors. For outdoor installation, use an external
outdoor enclosure (not provided by SolarEdge).
The SolarEdge gateway must always remain in an ambient temperature of -20°C (-4°F) to
+60°C (140°F).
Cable specifications:
Connection Type
Cable Type
Maximum Length
RS485 communication bus
(per RS485 port)
Three twisted wires or 4-wire twisted pair
cable (two twisted pairs).
Recommended wire size: 20 AWG / 0.52 mm2
1,000m (3,330 ft)
Ethernet
CAT5/6
100m (325 ft).
The SolarEdge gateway power supply requires a socket outlet with a grid voltage of 100 V - 240 V
(50 Hz/60 Hz).
Protect the SolarEdge gateway from dust, wet conditions, corrosive substances and vapors.
Installation Workflow
The following provides an overview of the workflow for installing and setting up the firefighter gateway
Step 1
Page 12
Step 2
Page 16
Step 3
Page 18
Step 4
Page 18
Step 5
Page 24
Step 6
Page 26

Chapter 2: Installing the SolarEdge Firefighter Gateway
Firefighter Gateway Installation Guide MAN-01-00113-1.2
12
Mounting the Firefighter Gateway
The SolarEdge gateway can be installed on a wall or on a DIN rail.
►To mount the SolarEdge gateway on a wall:
1Determine the mounting location. Leave clearance from all sides of the SolarEdge gateway for cover
opening, cable connection and routing.
2Open the clips at the rear of the gateway by pushing the clips outwards.
Figure 4: Clips in Open Position
3Position the device on the wall with the open clips, as shown in Figure 4. Mark points through the
holes of the clips and drill holes using a 4mm diameter drill bit.
4Mount the unit using screw anchors and screws (use 3.5mm diameter screws, 20mm minimum
length, not provided by SolarEdge).
►To mount the SolarEdge gateway on a DIN rail:
1Ensure that the clips are closed, as shown below:
Figure 5: Clips in Closed Position
Wall mount
holes
Press here
Press here
Press here
Press here

Chapter 2: Installing the SolarEdge Firefighter Gateway
Firefighter Gateway Installation Guide MAN-01-00113-1.2
13
2Hook the two lower clips of the SolarEdge gateway onto the lower edge of the DIN rail.
3Press the SolarEdge gateway upwards and snap it into the upper edge of the DIN rail. When on the
rail, the clip "grips" the rail on both the top and bottom lips of the rail.
To remove the DIN clip from the rail, simply push upwards on the DIN clip (thereby compressing the
springs in the bottom), pivot the top of the clip off of the rail, and then move the whole clip down to
also release the bottom of the clip. No screwdrivers or special tools are required.
4The following figure shows the gateway’s rear side when mounted on a DIN rail.
Figure 6: Gateway Mounted on a DIN Rail
Connecting the Firefighter Gateway to AC
For connecting to power, use the supplied power supply:
1Insert the power supply DC connector to the SolarEdge gateway (see Figure 3).
2Connect the power supply to the AC mains. The LEDs are lit momentarily to indicate power
connection (see Figure 3)
CAUTION
If you use a non-SolarEdge power supply, check that it has 12Vdc/1A output ratings, and that it is
certified to UL/CSA/IEC60950-1 2ed standards. Limited Power Source output, NEC class 2.
Verify the power supply polarity as marked on the gateway.
DIN rail clips

Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control
Firefighter Gateway Installation Guide MAN-01-00113-1.2
14
Chapter 3: Connecting Emergency Stop
Button or Fire Alarm Control
Overview
An external emergency stop button (not supplied by SolarEdge) should be connected to the firefighter
gateway, in order to shut down the PV system in case of emergency. Pressing the emergency stop button
starts the shutdown sequence of the PV system. Preferably, use a button with a locking feature that stays
mechanically locked in the off position until you turn it clockwise a quarter turn to unlock and release it.
The firefighter gateway can also be connected to a fire alarm control unit that has a relay output. The relay
output of the fire alarm control has the same functionality as the button. You can connect both a stop
button and a relay together to the same firefighter gateway, or two stop buttons or two relays.
Figure 7: Example: Emergency Stop Button and Fire Alarm System Connection
The emergency stop button(s) or relay(s) connect to the L1 or L2 ports on the Control connector of the
gateway, between 5V and L1 / L2/both. In the following sections, the instructions refer to L1, however
applies to L2 as well.
Figure 8: Emergency Stop Button Connection

Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control
Firefighter Gateway Installation Guide MAN-01-00113-1.2
15
There are two types of contact states in Emergency Stop buttons/relays:
Normally open (NO) –the contacts are open until closed by operation of the switch. This type of
switch should be connected in the following manner:
This installation is safe when L1/L2 has 5V input, and active with L1/L2 is not connected. This is
considered Normal polarity in the configuration screen.
Normally closed (NC) –the contacts are closed until opened by operation of the switch. This type of
switch should be connected in the following manner:
This installation is safe when L1/L2 is not connected and active when L1/L2 is 5V. This is considered
Reverse polarity in the configuration screen.
If you connect more than one firefighter gateways to the same emergency stop button, they should
connect to the same grounding, as in the following example:
In some fire alarm control systems, the switch is grounded internally. This type of switch should be
connected in the following manner, sharing ground between the control system and the firefighter
gateway.
In these cases, a Normally Open relay will connect L1/L2 to ground for safety, and when active, L1/L2
is 5V. This will be configured as a reverse polarity switch.
Fire Alarm Control System

Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control
Firefighter Gateway Installation Guide MAN-01-00113-1.2
16
Connecting and Configuring an Emergency Stop
Button to the Gateway
1Depending on the button/relay type, connect L1/L2, 5V and Ground as described above. Use wire
size 20 AWG/ 0.52mm2: Insert the ends of wires into the ports of the supplied 6-pin terminal block.
Figure 9: 6-pin Terminal Block
2Insert the terminal block into the Control connector on the firefighter gateway.
3Verify that the SolarEdge gateway is connected to a power outlet.
4Press the Enter button until the following message is displayed:
P l e a s e ente r
P a s s w o r d
* * * * * * * *
The gateway is now in Setup mode and all its LEDs are lit.
5Use the three-right-most LCD buttons to type in the following password: 12312312. The following
menu is displayed:
L a n g u a g e < e n g >
Communication
Rem o t e S h u t d o w n
Display
Maintenance
Information
6Short-press the up/down buttons to scroll to the Remote Shutdown menu. Press the Enter key to
select it. The remote shutdown parameters are displayed:
L 1 P o l a r i t y < N o r m . >
L 2 P o l a r i t y < N o r m . >
S a f e V d c < 1 2 0 V >
C l r A l a r m M o d e < M >
C l e a r A l a r m
7Set the following:
L1/L2 Polarity: The lines polarity - Normal (default) or Reverse
Normal –safety will be activated when L1/L2 has 5V
Reverse –Safety will be activated when L1/L2 is connected to ground or not connected.
Safe Vdc: Threshold value for safe Vdc: When the maximum DC voltage (of all connected devices)
reaches this threshold, the PV system will be considered safe and the display will show Safe DC in
the main gateway status screen. You may set the threshold in the range between 30 -120V (default
120V)
G
5V
L1
L2

Chapter 3: Connecting Emergency Stop Button or Fire Alarm Control
Firefighter Gateway Installation Guide MAN-01-00113-1.2
17
Clr Alarm Mode: Select the method to return to normal operation as soon as the emergency stop
button is released:
Automatic (default) –when releasing the stop button or relay, the system immediately returns
to normal power production.
Manual –when releasing the stop button or relay, the system will not return to normal
operation unless the user manually clears the alarm by selecting Clear Alarm (below). Use this
option if the button does not have the locking feature, the relay in the control system may
open unexpectedly, or if the user requires this added step.
Clear Alarm: Used to allow normal operation. Appears only if the Clr Alarm Mode parameter (above)
is set to Manual, and the installation is in remote safety shutdown

Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation
Firefighter Gateway Installation Guide MAN-01-00113-1.2
18
Chapter 4: Connecting the Firefighter
Gateway to the SolarEdge Installation
Overview
The SolarEdge firefighter gateway connects to the PV system installation using the RS485 communication
option. The RS485 option enables creating a chain (bus) of up to 31 slave SolarEdge devices, connected to
one master, which can be another SolarEdge device or the SolarEdge firefighter gateway.
The following is an example of a slave gateway connected to a chain of slave inverters (one inverter is the
master).
Figure 10: Example of RS485 Connection
The following sections describe how to connect the RS485 bus and how to configure its components.
Connecting and Configuring the RS485
The RS485 bus uses a three-wire cable connecting the RS485-1/2 terminal blocks on the SolarEdge
gateway to the RS485 input of the inverters/SMI.
►To connect the RS485 communication bus between inverters/SMIs and
SolarEdge gateway:
1Use one of the supplied 3-pin terminal blocks: Loosen the screws and insert the wire ends into the
A, Band G pins. For connections longer then 10m use twisted pair wires for A and B wires.
Figure 11: 3-pin Terminal Block
G
B
A
Terminated
Terminated
Screws

Chapter 4: Connecting the Firefighter Gateway to the SolarEdge Installation
Firefighter Gateway Installation Guide MAN-01-00113-1.2
19
2Choose either RS485-1 or RS485-2 for connection. Connect the 3-pin terminal block to the
designated port on the gateway.
NOTE:
RS485-1 is configured as SolarEdge device by default, therefore RS485-1 is recommended as
the RS485 bus connection point.
3If the gateway is at the end of the RS485 chain, terminate the gateway by switching a termination
dipswitch to ON. The switches in the SolarEdge gateway are marked SW1 for the RS485-1 port
termination and SW2 for the RS485-2 port termination, as shown below:
Figure 12: RS485 Connectors and Termination Switches
4Open the inverter/SMI cover as described in their manual.
5Remove the seal from one of the openings in communication gland #2 of the inverter and insert the
cable through the opening.
6Pull out the 9-pin RS485/RS232 terminal block connector, as shown below:
Figure 13: The RS485/RS232 Block Terminal In the Inverter/SMI
7Loosen the screws of pins B, Aand Gon the left of the RS-485 block terminal:
For inverter: RS485-1 pins (left-most)
For SMI: RS485-1 (recommended, as this is the default configuration), or RS485-2
On Off
AB G
AB G
SW1 SW2
RS485- 2 RS485-1
Other manuals for Firefighter Gateway
1
Table of contents
Other SolarEdge Control Unit manuals