12. Testing and Powering up Sol-Ark 8K
a. Check Voltage of each PV input circuit
i. Should be no higher than 500Vdc open circuit.
ii. DO NOT connect PV+ OR PV- to GND.
iii. Good to verify polarity.
b. Check Grid Input Voltage (voltages shown are for North America)
i. Ensure 120Vac L1 to Neutral and L2 to Neutral.
ii. Ensure 240Vac L1 and L2.
iii. Check Neutral and Ground are ~0V AC.
c. Check Battery voltage
i. Turn on battery switch (if using a Lithium battery).
ii. Voltage should be 45Vdc-57Vdc.
d. If all checks out, Turn on Breakers for Grid and Load, Turn PV Disconnect knob to “On”
e. System will boot up with power from PV, Grid, or ON/Off Batt.
f. Press the ON/OFF Button on the front, light should come on.
g. If you installed limit sensors for Limited To Home selling mode, it is critical you verify the
proper sensor and direction. (if MCU SW = 1654 or higher, an auto learn function avoids all
this).
i. Using AC multi-meter, verify L1 voltage on AC in/out is 0Vac with main L1 connection in
panel. Same for L2.
ii. To verify sensor connections to Sol-Ark, try removing one sensor from the main L1
connection. The power should drop to 0W.
iii. To verify proper sensor direction, with any loads in the home, the HM: +watts will be
positive. If you turn on solar panels and turn enable Grid Sell, you should see HM: -watts
if you are producing more power than the loads are consuming. And if you turn on
limited power to Home mode, then HM: ~0 watts to zero the meter (system matches
the loads to within 99%).
13. Basic Setup
a. Display: Auto dim must be enabled for LCD screen to be covered by warranty. Color LCD screens
dim if left on continuously for years.
b. Time: Set date and time for the system
14. Programming Battery Settings
a. Battery Size
i. This allows Sol-Ark to know the size of the battery bank. The system is also self-learning as
batteries age.
ii. Main Menu →System Settings →Battery Setup →Batt →Batt Capacity
b. Use Battery Voltage or % Charged
i. Use whatever you are comfortable with. Most installers prefer voltage, while most
homeowners prefer % Charged.
c. Battery Charge & Discharge Current
i. For AGM and Flooded, we recommend Ah battery size x 20% = Charge/Discharge amps
ii. For Lithium, we recommend Ah battery size x 50% = Charge/Discharge amps
iii. For Gel, follow manufacturer’s instructions.