
6| Circular re damper user manual 05/2020
SOLID AIR
®
CLIMATE SOLUTIONS • T +31 598 36 12 21 • www.solid-air.nl •mail@solid-air.nl
4. S
As a safety element, the re damper must be stored, handled and installed carefully.
Pay attention to:
• unload in a dry area
• avoid any shocks
• do not use the damper as a workbench or scaolding
• do not t the small dampers in the large one
The damper must be stored in a dry place, and kept out of water and frost. It should not be
stacked beyond the original packaging. It must be properly stowed so as to prevent any damage or
deformation resulting from an impact or high humidity. It must not be exposed to direct sunlight to
prevent premature aging of the thermal fuse. Once the damper is installed, the mechanism should
be kept away from any projections (cement, paint, ocking, water, dust) that may harm its operation.
The damper must be protected against the risk of heavy condensation. The intumescent joints are
essential for the re resistance of the damper, all mechanical actions on the refractory parts are to
be excluded. All precautions shall be taken to ensure that premature aging of the damper does not
occur before it is actually installed. The actions of wedging and caulking during the sealing of the
dampers must not cause deformations that will alter the good functioning of the damper and in
particular the closing of the blade.
5.
5.1
• Mounting is possible with the blade axis in horizontal or in vertical position
• The installation must comply with the tests that were performed during certication,
as explained in 8.2
• Avoid any obstruction of the moving blade by the connected ducts
• The class of air-tightness is maintained in case the installation of the damper is made in
accordance with the technical manual
• Operating temperature: 50 °C max
• For indoor use only
The FDC25/FDC40 re damper is always tested in standardized support frames (both in a concrete
wall and in a exible wall) in accordance with EN 1366-2: 1999 table 3/4/5. The results obtained are
valid for all similar support frames which have a thickness and/or density and/or re resistance
similar or greater than the one of the test.
Minimum opening hole for re damper instalation:
Damper size - ØD [mm] Opening size - A (minimum)
ØD < 160 ØD + 85
180 < ØD < 315 ØD + 75
315 < ØD < 450 ØD + 65
ØD > 450 ØD + 55