Schako BKP-EN Operating instructions

Fire damper BKA-EN
SCHAKO | Ferdinand Schad KG Phone +49 (0) 7463-980-0
Steigstraße 25-27 Fax +49 (0) 7463-980-200
Fig.: BKP-EN with X14 actuator + accessories
USABILITY CERTIFICATES
• Declaration of Performance
DoP-BKP-EN-2020-09-01
CLASSIFICATION AND STANDARDS
• Classification
according to EN 13501-3, depending on the
installation situation EI 90 (ve, ho i↔o) S to
EI 1 2 0 (ve, ho i↔o) S
• Product standard
EN 15650
• Test standard
EN 1366-2
PERFORMANCE DATA
• For automatic locking of fire lobbies
SPECIAL FEATURES
•
ATEX
version (at an extra charge)
• Extensive uses and applications
• Housing leakage class C according to EN 1751
BKP-EN
Fire damper
Additional operating instructions according to
ATEX 2014/34/EU

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Table of Contents
Construction subject to change
No return possible Version: 2020-09-01 | Page 2
TABLE OF CONTENTS
Table of Contents ........................................................ 2
General conditions ...................................................... 3
Description .................................................................. 4
Models and dimensions .............................................. 5
Type plate ................................................................... 9
Order code ................................................................ 10
Certificate of conformity........................................... 11
Foreign branch offices .............................................. 13
List of figures/tables ................................................. 14

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
General conditions
Construction subject to change
No return possible Version: 2020-09-01 | Page 3
GENERAL CONDITIONS
GENERAL DESCRIPTION AND INSTRUCTIONS
These additional operating instructions must be observed
prior to mounting and commissioning the device.
These additional operating instructions contain basic infor-
mation regarding its use in areas subject to explosion hazards
to be observed during assembly, operation and functional
check.
Prior to mounting and commissioning and during functional
check, the present additional operating instructions must be
read by the installer and the responsible skilled person-
nel/system operator!
The non-observance of the proper assembly and safety in-
structions will result in the loss of any claims for damages!
PERSONNEL QUALIFICATION AND TRAINING
The personnel for assembly, inspection and functional check
must have the relevant qualification for this work. The area of
responsibility, competence and monitoring of the personnel
must be exactly regulated by the system operator. If the per-
sonnel does not have the required knowledge, it must be
trained and instructed. Moreover, the system operator must
ensure that the contents of the additional operating instruc-
tions are completely understood and adhered to by the per-
sonnel.
SAFETY-CONSCIOUS WORK
The safety instructions given in these additional operating in-
structions, the existing national and international regulations
on explosion protection, accident prevention and the system
operator's internal work, operating and safety regulations
must be observed.
DESIGNATED USE
The devices have been designed for use in ventilation systems
in areas subject to explosion hazards according to the ATEX
marking "Device group II, Zones 1, 2 and 21, 22.
These devices are not suitable for use in unreleased Ex zones.
The operating safety of the delivered devices is only guaran-
teed when used in accordance with their designated use. The
fire damper shall only be used for media that do not exceed a
temperature of 72°C.
DELIVERY AND STORAGE
Upon receipt, the devices must be checked for completeness
and transport damage. If the device was delivered incom-
pletely or damaged, the forwarding company and the SCHAKO
KG have to be informed immediately.
The fire dampers must not be exposed directly to weather,
solar radiation and moisture (see also "General information").
MOUNTING INFORMATION
Mounting, electrical connection work and commissioning
must be carried out by skilled personnel only and in accord-
ance with the recognised technical rules and the safety and
accident prevention regulations. In order to avoid the risk of
static charges, the fire damper must be connected to the on-
site equipotential bonding on the grounding connection pro-
vided for this purpose.
FUNCTIONAL TEST
Only a device subjected to proper check and kept in perfect
condition can guarantee safe and reliable operation.
When defective parts are replaced with spare parts, only
SCHAKO KG original spare parts may be used. The SCHAKO KG
cannot be held liable for any damage caused by using spare
parts that are not original and will not give any warranty.
HAZARD CAUSED BY NON-OBSERVANCE OF THE
SAFETY INSTRUCTIONS
Non-observance of the safety instructions can result both in
putting persons and the environment and operating units at
risk.
Likewise, non-observance of the safety instructions will result
in the loss of any claims for damages.

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Description
Construction subject to change
No return possible Version: 2020-09-01 | Page 4
DESCRIPTION
Fire dampers, installed in ventilation ducts (air conditioning
systems), serve for the automatic locking of fire lobbies. The
fire damper BKP-EN conforms to EN 15650, EN 13501-3 and
EN 1366-2. The BKP-EN has been tested according to EN
1366-2 in compliance with Declaration of Performance No.
DoP-BKP-EN-2020-09-01. Its classification according to EN
13501-3 is EI 90 (ve, ho i↔o) S to EI 120 (ve, ho i↔o) S.
According to Directive 2014/34/EU, EC Certificate of Conform-
ity Number EPS 13 ATEX 2 610 X, its use in areas subject to
explosion hazards is permitted, not only with spring return ac-
tuator ExMax-5.10-BF (X14/X15), including safety tempera-
ture limiter (ExPro-TT), but also with mechanical release via
fusible link (manual actuation with or without ATEX limit
switch ES-Ex). The fire damper is marked as follows according
to ATEX:
II 2 G Ex h IIC T6 Gb EPS 13 ATEX 2 610 X
II 2 D Ex h IIIC T80°C Db
The national standards and guidelines must be observed in
connection with these additional operating instructions.
For functional test, service, retrofitting, etc., inspection open-
ings must be provided on site in suspended ceilings, shaft
walls, connected ventilation ducts etc., if necessary. They
must be built in in sufficient numbers and sizes and must not
impair the functioning of the fire dampers.
The fire dampers must be connected to the ventilation system
by means of ventilation ducts either on one or on both sides.
When connected on one side, security grille made of non-
flammable building materials (EN13501-1) must be provided
on the opposite side. The fire dampers can be connected to
non-flammable and flammable ventilation ducts as well as to
flexible spigots.
The fire damper complies with the regulations of the ATEX di-
rectives and may be used in supply and return air installations
of ventilation systems in areas subject to explosion hazards.
The fire damper is certified for device group II, Zones 1, 2 and
21, 22.
Zones 1 and 2 represent the application range containing
gases/vapours, while Zones 21 and 22 represent the applica-
tion range containing dusts.
Classification by zone must be established by the system op-
erator or planner in compliance with current standards.
Note:
In explosion-protected zones, only devices that have an ATEX
approval for this use may be used. It rests with the operator
to ensure that the products are only used in zones specified
by the product marking.
SPECIAL CONDITIONS
The attached and installed electrical devices must have a suit-
able explosion-proof design.
It must be ensured that all metal components are properly
and permanently connected to the ground potential.
TYPE OF IGNITION PROTECTION
The type of ignition protection of the fire dampers is guaran-
teed by their safe design.
QUALITY ASSURANCE
The SCHAKO production facilities are certified according to
the QM procedure EN ISO 9001.
To ensure that the defined product features are adhered to
during the production, a factory production control is carried
out at regular intervals. In addition, a notified body carries
out an external audit once a year.

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Models and dimensions
Construction subject to change
No return possible Version: 2020-09-01 | Page 5
MODELS AND DIMENSIONS
Dimensions
Figure 1: Dimensions BKP-EN
Figure 2: Dimensions of BKP-EN with actuator ExMax-5.10-
BF (X14/X15)
1 Housing
2 Damper blade
3 Hand lever
4 Locking profile
5 Release device
6 Fusible link
7 Inspection opening from B ≥ 200, for B < 200 no inspection
opening possible.
200 ≥ B < 600 x = B/2
B ≥ 600 x
~
125mm
y
~
100 mm from the connection flange
Arranged at the bottom (standard)
8 Actuator unit
9 Earthing connection
10 Actuator ExMax-5.10-BF (X14/X15)
11 Safety temperature limiter
Available sizes [mm]
Breite (B) Höhe (H)
100 100
150 125
200 150
250 160
300 175
400 200
500 225
600 250
700
800
Table 1: Available sizes [mm]
Housing length L = 330 mm.
(Exclusively) right-hand design
All heights and widths which can be combined are
available!
Trigger device always on H side
Inspection opening from B ≥ 200, always on B side
(bottom)
Intermediate sizes on request

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Models and dimensions
Construction subject to change
No return possible Version: 2020-09-01 | Page 6
Weight table [kg]
BKP-EN with mechanical-thermal release
(manual release)
(added weight for actuator ExMax-5.10-BF (X14/X15) max. approx. 4.5 kg)
Table 2: Weight tables [kg]
Electric spring return actuator ExMax-5.10-BF
(X14/X15)
ExMax-5.10-BF (X14/X15)
Figure 3: Circuit diagram actuator ExMax-5.10-BF (X14/X15)
Connection ExMax-5.10-BF (X14/X15)
Open/closed 1-wire spring return + Ex-i circuit SB 7.0
integrated, permanently set auxiliary
switch, max. 24V/3A, 240V/0.5A switching
at an angle of rotation 5° and 85°. The volt-
age on the auxiliary switch must be identi-
cal to the supply voltage and protected by
an identical fuse.
Ex-i circuit for
passive, potential-free
pushbuttons provided by the cus-
tomer and
thermally activated safety release
device
(type ExPro-TT)
BSK
24…240 VAC/DC
Standard connection = spring return in ~ 10 sec.
Heating
But-
! Attention!
For a 1-wire control,
the heating is not ac-
tive
when the contact is
100 150 200 250 300 400 500 600 700 800
100 3.3 3.6 4.1 4.4 4.9 5.5 6.5 7.4 8.2 9
125 3.4 3.8 4.3 4.8 5.2 6.1 7.1 7.7 8.8 9.6
150 3.6 4.1 4.6 5 5.4 6.4 7.3 8.3 9.1 9.8
160 3.7 4.2 4.7 5.1 5.5 6.6 7.6 8.7 9.4 10.1
175 3.9 4.3 4.8 5.2 5.6 6.8 7.8 8.9 9.6 10.4
200 4.1 4.6 5 5.6 6 7.2 8.2 9.2 10.2 11
225 4.3 4.8 5.2 5.9 6.3 7.5 8.3 9.4 10.5 11.8
250 4.4 4.9 5.3 6.1 6.4 7.6 8.4 9.7 10.8 12.7
Breite [mm]
Höhe [mm]

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Models and dimensions
Construction subject to change
No return possible Version: 2020-09-01 | Page 7
Electric explosion-protected spring return actuators
with safety temperature limiter (ExPro-TT).
Release temperatures 72 °C.
Operating position (damper "OPEN") and tension-
ing of the return spring by applying the supply volt-
age (universal power supply 24 - 240 VAC/DC)
Safety position (damper "CLOSED") through spring
force when supply voltage is interrupted or the tem-
perature fuses (room temperature or internal duct
temperature) respond. A response of the thermal
fuses will interrupt the sensor circuit permanently
and irrevocably.
End position signalling by integrated auxiliary
switches, switching at an angle of rotation of 5° and
85°.
An on-site functional check is possible by means of
the control key of of the safety temperature limiter
Attention!
Safety function is only guaranteed if the actuator has been
connected to the supply voltage in accordance with regula-
tions.
Technical data actuator ExMax-5.10-BF
(X14/X15)
Power supply 24…240 V AC/DC, ± 10% each,
self adaptable
Frequency 50...60 Hz ± 20%
Power consumption
Holding max. 20 W
Heating capacity approx. 16 W
Current on making approx. 2.0 A at 24 V for approx. 1
sec.
Running time Motor 30s
Spring return 10s
Auxiliary switch 2 integrated, permanently set, po-
tential-free auxiliary switches with
changeover contact
Switching voltage 24 V DC / 230 V AC
Switch voltage 0.5 mA - 3 A
Switching points Angles of rotation: 5° / 85°
Protection class I (earthed)
Protection type according
to DIN 60 529
IP66
Tested according to EMC 2004/108/EC
Safety tested 2006/95/EC
Ambient temperature
(operation)
-40 ... +40°C
Ambient humidity ≤ 95%, non-condensing
Table 3: Technical data actuator ExMax-5.10-BF (X14/X15)
LIMIT SWITCH TYPE ES-EX
Limit switch for application in areas subject to explosion haz-
ards
II 2G Ex d IIC T6/T5 Gb,
II 2D Ex tb IIIC T 80°C/ 95°C Db
IP65; 250V / 6A AC15; 230V / 0.25A DC13; -20°C ≤ Ta ≤ +65°C
Figure 4: Circuit diagram limit switch type ES-Ex
Damper positions that can be displayed:
EXZ (type ES-Ex-Z: "CLOSED")
EXA (type ES-Ex-A: "OPEN")
EX2 (type ES-Ex-2: "OPEN" and "CLOSED")
General information
During mounting or installation, there is a risk of injuries.
To avoid any possible injuries, personal protective equip-
ment (PPE) must be worn.
Fire dampers must be installed such that external forces
do not impair their permanent functioning.
Ventilation ducts must not exert significant forces on
walls, supports or ceilings and thus also on fire dampers
as a result of thermal expansion (in case of fire).
Appropriate compensation measures, such as the ar-
rangement of flexible spigots (SCHAKO type FS) or a suit-
able duct routing (duct angles and distortions), must be
taken as required. National regulations must be observed
and implemented
Prior to installing the fire damper, the possible connec-
tions of the ventilation ducts must be checked. Extension
parts (on site or as accessories SCHAKO type VT) might be
necessary, e.g. for large wall and ceiling thicknesses.
When connecting duct components, a fastening type
must be selected that causes no damage to the fire
damper or its accessories.
During mounting it may be required to provide reinforce-
ments for the housing or the like.
The requirement of statically load-bearing lintels may
have to be taken into consideration.
If a fire damper is not filled with mortar on all four sides,
installation and mounting aids on site must be removed.

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Models and dimensions
Construction subject to change
No return possible Version: 2020-09-01 | Page 8
Improper transport/handling may result in damage/func-
tional impairment. In addition to that, the film of the
transport packaging must be removed and the delivery in-
spected for completeness.
In storage, fire dampers must be protected from dust,
dirt, moisture and the effects of temperature (e.g. direct
sunlight, heat-emitting light source, etc.). They must not
be exposed to direct effects of the weather and must not
be stored below -20 °C or above 50 °C.
The fire damper must be protected from dirt and damage.
After installation is complete, any dirt must be removed
immediately.
Enough space must be provided for installation, mortar
lining, etc.
Carry out a functional check of the fire damper before and
after mounting and ensure ready access.
Electrical installations or work on electrical components
may only be carried out by skilled electricians. The supply
voltage must be switched off when performing this work
and secured against being switched on again.
We would like to point out that only suitable cleaning ma-
terials may be used for cleaning fire dampers in stainless
steel design!
Information regarding assembly and commissioning
Prior to being installed in the ventilation system, the fire
damper must be checked for damage. Damaged fire dampers
must not be installed.
The device may only be used in accordance with its desig-
nated use in air ventilation systems for supply air and return
air.
Use only approved fastening material for mounting.
No additional parts may be
fastened to the fire damper.
The fire damper must be connected to the ventilation duct
network on both sides in electrically conducting fashion.
In order to avoid the risk of static charges, the fire damper
must be connected to the on-site equipotential bonding on
the grounding connection provided for this purpose.
Make sure that the ventilation systems are not subjected to
any anomalous operating conditions, such as vibrations, pres-
sure surges or high proportions of solids in the medium.
Information regarding functional check and inspec-
tion
Proper functional check increases operational safety and the
service life of the device. This is why the devices should be
subjected to regular inspection.
If inspection dates are prescribed by law, they must be com-
plied with.
The operating personnel must be informed, prior to starting
functional check and inspection work.
The personal safety measures must be looked up in the safety
data sheet. Hazard caused by contact or inhaling hazardous
substances must be excluded by taking appropriate safety
measures.
Prior to functional check or inspection, all system components
up- and downstream of the device must be switched off and
secured against being switched on again.
The following inspection criteria must be observed:
Visual inspection of the device
Check the fastening of the device
Check the electrical connections
Check the grounding connection for tight fit and good
contact
Functional control
For additional inspections, please refer to the technical
documentation or additional instructions for functional
check
Use and electrical connection of actuators in areas
subject to explosion hazards
Only ATEX-approved electrical equipment according to ATEX
Directive 2014/34/EU for the zones 1, 2, 21, 22, such as actu-
ators, terminal boxes and thermocouples according to our
specifications may be used for SCHAKO KG devices.
The connection lines must be installed for permanent use and
in such a way that they are sufficiently protected from me-
chanical and thermal damage.
Devices with explosion-protected actuators and terminal
boxes have to be attached over the external potential con-
necting terminal to the potential equalisation provided by the
customer with at least 4 mm² cooper solid-core.
The electrical connection lines of the actuators
must be connected in a terminal box according to ATEX Di-
rective 2014/34/EU for the zones 1, 2, 21, 22, if the electrical
connection is made in an explosive area.
The dimensioning of the conductor cross-sections must be ob-
served.
The actuators are maintenance-free with respect to their
function, but the test specifications according to ATEX direc-
tives
or factory regulations must be observed.

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Type plate
Construction subject to change
No return possible Version: 2020-09-01 | Page 9
TYPE PLATE
Figure 5: BKP-EN type plate

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Order code
Construction subject to change
No return possible Version: 2020-09-01 | Page 10
ORDER CODE
01 02 03 04 05 06
Type Width Height Length Material (housing) Coating (housing)
Example
BKPEN -800 -250 -330 -V2 -1
07 08 09 10 11
Damper blade version Release temperature Actuator type Accessories Additional frame
-2 -72 -X15 -KK2 -R05
EXAMPLE
BKPEN-800-250-330-V2-1-2-72-X15-KK2-R05
Type BKPEN = fire damper BKP-EN | Width = 800 mm | Height = 250 mm | Length = 330 mm | Material (housing) V2 = stainless steel
material no. 1.4301 (V2A) | Coating (housing) 1 = DD coating inside | Damper blade version 2 = coated with DD paint | Release
temperature 72 = 72 °C | Actuator type X15 = type ExMax-5.10-BF (housing V4A) | Accessories KK2 = terminal box (V4A) with
mounting console | Additional frame R05 = installation frame ER-P1
ORDER DETAILS
01 - TYPE
BKPEN = BKP-EN
02 - WIDTH
100 - 150 - 200 - 250 - 300 - 400 - 500 - 600 - 700 - 800
in mm - always three digits
03 - HEIGHT
100 - 125 - 150 - 160 - 175 - 200 - 225 - 250
in mm - always three digits
04 - LENGTH
330
in mm - always three digits
05 – MATERIAL (HOUSING)
SV = Galvanised sheet steel (standard)
V2 = Stainless steel material no. 1.4301 (V2A)
06 – COATING (HOUSING)
0 = without paint (standard)
1 = DD coating, inside (RAL7035)
3 = DD coating inside and outside (RAL7035)
07 - DAMPER BLADE VERSION
0 = without coating (standard)
2 = DD coating
08 – RELEASE TEMPERATURE
72 = 72 °C (standard)
09 - ACTUATOR TYPE
HAX = thermo-mechanical manual release *(standard)
X14 = ExMax-5.10-BF + safety temp. limiter (ExPro-TT) 72 °C *
X15 = ExMax-5.10-BF (housing made of stainless steel V4A) +
safety temp. (ExPro-TT) 72 °C *
* suitable for all dimension combinations
10 - ACCESSORIES
Z00 = without accessories (standard)
EXZ = ES-Ex-Z (limit switch Closed; suitable for HAX)
EXA = ES-Ex-A (limit switch Open; suitable for HAX)
EX2 = ES-Ex-2 (limit switch Open/Closed; suitable for HAX)
KK1 = terminal box with mounting console;
suitable for X14
KK2 = terminal box with mounting console
(housing made of stainless steel V4A); suitable for X15
11 – ADDITIONAL FRAME
R00 = without additional frame (standard)
R05 = installation frame ER-P1 II)
R06 = installation frame ER-P1 I)
I) Additional frame supplied loose
II) Additional frame mounted ex works

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Certificate of conformity
Construction subject to change
No return possible Version: 2020-09-01 | Page 11
CERTIFICATE OF CONFORMITY

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Certificate of conformity
Construction subject to change
No return possible Version: 2020-09-01 | Page 12

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
Foreign branch offices
Construction subject to change
No return possible Version: 2020-09-01 | Page 13
FOREIGN BRANCH OFFICES
Belgium Denmark England France
SCHAKO S.A.R.L. Venti AS SCHAKO Ltd. SCHAKO s.a.r.l.
165, rue des Pommiers Banevænget 3 Index House 16 Boulevard de la Croix Rousse
L-2343 Luxembourg 8362 Hørning St Georges Lane, Ascot F-69001 Lyon
Phone: +352 / 403 157 1 Phone: +45 / 86 92 22 66 SL5 7EU Berkshire Phone: +33 / 4 / 78 34 97 34
Fax: +352 / 403 157 66 Fax: +45 / 86 92 22 26 Phone: +44 / 13 44 63 63 89 Fax: +33 / 4 / 78 34 97 31
www.schako.be www.venti.dk admin@schako.uk.com www.schako.fr
www.schako.co.uk
Greece Israel Italy Croatia
EUROPERSIS Insupco Industrial Supply Ltd. SCHAKO Italia S.r.l. Intel Trade
Odisea Androutsou 2 40 Hayarkon St. Via XXV Aprile, 17 Dr. Ante Mandica 10
GR-56224 Evosmos/Tessaloniki Yavne 811 00 20097 S.Donato Milanese-MI HR-51410 Opatija
Phone: +30 / 310 / 68 57 79 Phone: +972 / 8 / 94 20 080 Phone: +39 / 02 / 51 64 02 01 Phone: +385 / 51 741 100
Fax: +30 / 310 / 75 76 13 Fax: +972 / 8 / 94 20 311 Fax: +39 / 02 / 51 62 09 46 Fax: +385 / 51 701 470
www.europersis.gr www.insupco.com www.schako.it www.intel-trade.hr
Luxembourg Netherlands Austria Poland
SCHAKO S.A.R.L. SCHAKO S.A.R.L. SCHAKO Vertriebs GmbH SCHAKO Polska Sp. z o.o
165, rue des Pommiers 165, rue des Pommiers Mariahilfer Straße 103/1/TOP 12 ul. Pulawska 38
L-2343 Luxembourg L-2343 Luxembourg A-1060 Wien PL-05-500 Piaseczno
Phone: +352 / 403 157 1 Phone: +352 / 403 157 1 Phone: +43 / 1 / 890 24 62 Phone: +48 / 22 / 7263570
Fax: +352 / 403 157 66 Fax: +352 / 403 157 66 Fax: +43 / 1 / 890 24 62 50 Fax: +48 / 22 / 7263571
www.schako.lu www.schako-nederland.nl www.schako.at www.schako.pl
Romania Sweden Switzerland Serbia & Montenegro
SCHAKO Klima Luft SRL EXOTHERM AB SCHAKO Suisse SA TERMOMEHANIKA d.o.o.
Str. Elena Caragiani nr.21 Box 60036 Rue Jean-Prouvé 28 Koste Glavinica 2
014212 Bucuresti, 21610 Limhamn 1762 Givisiez RS-11000 BEOGRAD
Phone: +40 / 0 / 21 / 232 13 75 Phone: +46 / 40 / 631 61 16 Phone: +41 / 26 / 460 88 00 Phone: +381 / 11 / 369 99 93
Fax: +40 / 0 / 21 / 232 13 75 Fax: +46 / 40 / 15 60 95 Fax: +41 / 26 / 460 88 05 Fax: +381 / 11 / 369 09 93
www.schako.ro www.exotherm.se www.schako.ch www.termomehanika.rs
Slovakia Spain Czech Republic Turkey
SCHAKO SK s.r.o. SCHAKO IBERIA S.L. SCHAKO s.r.o. EMO-SCHAKO Klima
Modrová 187 Departamento de Ventas Pred Skalkami II. 184/5 Havalandirma
91635 Modrová Pol. Ind. Río Gállego, CZ-10600 Praha 10-Zabehlice San. ve Tic. Ltd. Sti.
Phone: +421 / 337 / 774 1843 Calle B, nave 3 Phone: +42 / 02 / 727 680 43 Pursaklar Sanayi Sitesi,
Fax: +421 / 337 / 774 1843
50840 San Mateo de Gállego /
Zaragoza
Fax: +42 / 02 / 727 693 94 Karacaören Mah.1638.Cad.
No:98
www.schako.sk Fax: +34 / 976 / 690 709 www.schako.cz Phone: +90 / 312 527 16 05
www.emo-schako.com.tr
Hungary
SCHAKO Kft.
Tó Park 6
H-2045 Törökbálint
Phone: +36 / 23 / 445670
Fax: +36 / 23 / 445679
www.schako.hu

Fire damper BKP-EN
Additional operating instructions according to ATEX 2014/34/EU
List of figures/tables
Construction subject to change
No return possible Version: 2020-09-01 | Page 14
LIST OF FIGURES/TABLES
List of figures
Figure 1: Dimensions BKP-EN ....................................... 5
Figure 2: Dimensions of BKP-EN with actuator ExMax-
5.10-BF (X14/X15) ........................................... 5
Figure 3: Circuit diagram actuator ExMax-5.10-BF
(X14/X15) ........................................................ 6
Figure 4: Circuit diagram limit switch type ES-Ex ......... 7
Figure 5: BKP-EN type plate .......................................... 9
List of tables
Table 1: Available sizes [mm] ....................................... 5
Table 2: Weight tables [kg].......................................... 6
Table 3: Technical data actuator ExMax-5.10-BF
(X14/X15) ....................................................... 7
Other manuals for BKP-EN
1
Table of contents
Other Schako Fire And Smoke Damper manuals

Schako
Schako BKA-EN Operating instructions

Schako
Schako BSK-RPR Series Operating instructions

Schako
Schako ERK-MB Series Guide

Schako
Schako BSK-RPR Guide

Schako
Schako BKA-EN Service manual

Schako
Schako BSK-RPR-EU Series Guide

Schako
Schako BSK-RPR Service manual

Schako
Schako BKP-EN Service manual

Schako
Schako BSK-RPR-EU Service manual

Schako
Schako ERK-SO Guide