1.Tubing: The communication wires and power line should NOT be bound in the same conduit or tubing.
2.Wire selection:Use AWG 22-24 Shielded Twist Pair to avoid star wiring ,CAT 5 cable for TCP/IP connection. Don’t equip reader and lock with the same power
supply. The power for reader may be unstable when the lock is activating, that may make the reader malfunction.
3.Power supply:The standard installation: Door relay and lock use the same power supply, and reader use independent power supply.
Attach the water proof strip to the mounting plate.
Pull the cables from the square hole of the mounting plate.
Use a screwdriver to screw the base onto the wall.
Connect the terminal cables to the body and attach the body to the mounting plate.
Assemble the covers with the Allen key and screws (accessories supplied).
Turn on the power, the LED will light and hear the beep sound, you will see "Ready""
on LCD board.
1Products 2Terminal Cables 3Tools 4Optional
AR-721RB
Digital Relay
Water proof Strip
1Products 2Terminal Cables 3Tools 4Optional
AR-721RB
Digital Relay
TCP/IP Module
and Cable
Water proof Strip
3
1
2
5
4
3
1
2
4
5
Contents
AR-327-E:Touch-panel Metal Case
AR-727- E
Installation
Notice
AR-327-E
Pull the cables from the square hole of the mounting plate.
Use a screw to the mounting plate onto the wall.
Attach the water proof strip to the body, then connect the terminal cables to the body
and attach the body to the mounting plate.
Use the Allen key and screws (accessories supplied) to assemble the body onto the
mounting plate.
Turn on the power, the LED will light and hear the beep sound, you will see "Ready""
on LCD board.
AR-727- E

V230630
- 2 -
6
5
4
3
2
1
CN11
6
5
4
3
2
1
CN9
8
7
6
5
4
3
2
1
CN5
CN3
8
7
6
5
4
3
2
1
CN4
2
1
CN6
7
6
5
4
3
2
1
CN7
4
3
2
1
CN8
7
7
6
6
5
5
4
4
3
3
2
2
1
1CN18
CN2
CN18
327-E
327-E
727-E
727-E
注意事項
AR-327-E AR-727-E
40 mm
140 mm
78.5 mm
92 mm
57 mm
91 mm 46 mm
126 mm
83 mm
LCD Access Controller
Wire Application Wire Color Description
1 --- ---
2 --- ---
TCP/IP Module
Output
3Yellow Net - TX+
4Green Net - TX-
5Red Net - RX+
6Black Net - RX-
7 --- ---
Wire Application Wire Color Description
RS-485 for Lift
Controller
1Thick Green RS-485(B-)
2Thick Blue RS-485(A+)
Wire Application Wire Color Description
Anti-Tamper
Switch
1Red N.C.
2Orange COM
3Yellow N.O.
Wire Application Wire Color Description
Power 1 Red DC 12V Output
Security trigger signal
2Purple Security trigger signal Output
Arming 3 Red White Arming Output
Duress 4 Yellow White Duress Output
(AR-327-E By order)
Wire Application Wire Color Description
Lock Relay 1Blue White (N.O.)DC24V1Amp
2
Purple White
(N.C.)DC24V1Amp
Lock Relay COM 3White (COM)DC24V1Amp
Door Sensor 4Orange Negative Trigger Input
Exit Switch 5Purple Negative Trigger Input
Alarm Relay 6Gray N.O./N.C. Optional (by jumper)
Power 7Thick Red DC 12V
8Thick Black DC 0V
Wire Application Wire Color Description
Beeper 1Pink Beeper Output 5V/100mA, Low
LED 2Yellow Red LED Output 5V/20mA, Max
3Brown Green LED Output 5V/20mA, Max
Door Output 4Blue White Transistor Output Max. 12V/100mA
(Open Collector Active Low)
Wiegand 5Thin Green Wiegand DAT: 0 Input
6Thin Blue Wiegand DAT: 1 Input
WG Door Sensor
7Orange Negative Trigger Input
WG Exit Switch 8Purple Negative Trigger Input
(Optional)
(Optional) (Optional)
(Optional)
Main PCB
AR-727-E LCD-PCB
Connector Table
Cable: CN4
P1
Cable: CN6
P4
P2Cable: CN5
P6Cable: CN8
P5Cable: CN3
Cable: CN7
P3
INSTALLATION
Front View Front ViewSide view Side view
WG Port
Main Port

SOYAL
ACCESS CONTROL SYSTEM
®AR-327-E / 727-E V230630
- 3 -
AR-327-E AR-727-E
18/02 FRI Duty:0 18/02 FRI Duty:0
10:49:34 10:49:34
Ready...... Ready......
P
W
R
E
R
R
02
24
14 : 49 : 04
FRI
Duty
:
0
Door Sensor
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG
Port
Main Port
Sensor
CN3
P.T.Exit
GND
12V
+
–
+
–
E
COM
N.C.
N.O.
N.C.
N.O.
COM
ALM
N.C.
COM
12V
ALM
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG
Port
Main Port
CN3
P.T.Exit
GND
12V
SCADA
+
–
+
–
E
COM
N.C.
N.O.
DI
GND
Door Contact
N.C.
COM
PB
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG Port
Main Port
N.O.
COM
N.C.
V+
V-
N.O.
Sensor
GND
12V
N.C.
COM
PB
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG Port
Main Port
N.O.
+
–
Door Sensor
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG Port
Main Port
+
–
Sensor
N.C.
N.O.
COM
ALM
P.T.Exit
GND
12V
N.C.
COM
PB
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG Port
Main Port
N.O.
+
–
E
COM
COM COM
BP-W12-2000
BP-W12-2000
BP-W12-2000
BP-W12-2000
BP-W12-2000
BP-W12-2000
BP-W12-2000 BP-W12-2000
BP-W12-2000
BP-W12-2000
Optional Cables
Front Panel & Indicator
Wire Application Wire Color Description
TTL Port for
Lift Control or Voice
Module
(*Required speaker
8Ω / 1.5W (Max.
2W)
1Black DC 0V
2Yellow TX
3White TE
4Orange RX
5Red DC 5V
6 --- ---
Wire Application Wire Color Description
HID ProxII RF
Module
1Orange
ANT 1
2
Purple
ANT 2
3Black DC 0V
4Red DC 5V
5Blue Wiegand DAT: 1 Input
6Green Wiegand DAT: 0 Input
7White --
Cable: AR-327-E: CN10 / AR-727-E: CN18
P8Cable: CN11(Optional:Lift Control w/ AR-725L485; SW:RS485-2)
P7
CN9 (Optional:Voice Module; SW:RS485-3)
P9
Data
Week
Work Status
Data [e.g.] 02/24←→02 24(Network Connected)
Week
Work Shift Status
Esc/Quit
Up
Down
Left
Right
Enter/OK
Power(Green)
Alarm(Red)
Arming (Green)
Esc/Quit
Up
Down
Left
Right
Enter/OK
OK(Green)
Error (Red)
In processing (Green)
Power(Green)
Alarm(Red)
Arming (Green)
OK(Green)
Error (Red)
In processing (Green)
Wiring Diagram
Connect to Electric Bolt Connect to Magnetic Lock Connect to Electric Strike
Tamper-Switch Alarm Wiring Method Tamper-Switch Alarm Wiring Method
Controller
Controller Controller
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
Push Button
AR-PB5
Push Button
AR-PB5
Push Button
AR-PB5
Alarm
bell
Alarm
bell
Alarm
bell
Electric Bolt
AR-1207A
Electric Bolt
AR-1207A
Magnetic Lock
AR-0600M-270
Electric Strike
AR-YS-130NO
Electric Bolt
AR-1207A
Universal I/O Module
AR-403-IO
Central
Monitoring
System
Built-in
Tamper Switch
Built-in
Tamper Switch
Sensor
AR-MS-101-A
Sensor
AR-MS-101-A
※ Enable [Share Door Relay] & WG Port option
[Enable Force Alarm] via Parameter Setting of
701Server Software
※ Enable WG Port option [Enable Force Alarm]
via Parameter Setting of 701Server Software
Door Open Too Long Alarm Wiring
Method (External Sensor) (Connect to Central Monitoring System through Modbus
via Universal I/O Module)
(WG Port Sensor Wiring Method)

V230630
- 4 -
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
E
12V
GND
12V
GND
PB
PB
COM
COM
N.O.
N.O.
CN4
CN4
12V
GND
PB
COM
N.C.
CN4
7
6
5
4
3
2
1CN18
727-E
727-E
LCD-PCB
7
6
5
4
3
2
1
327-E
CN18
7
6
5
4
3
2
1CN18
727-E
727-E
LCD-PCB
7
6
5
4
3
2
1
327-E
CN18
7
6
5
4
3
2
1CN18
727-E
727-E
LCD-PCB
7
6
5
4
3
2
1
327-E
CN18
WG Port WG Port WG Port
WG Port WG Port WG Port
Main Port Main Port Main Port
V+
V-(GND)
V+
V-(GND)
V+
V-(GND)
N.O. N.O. N.O.
COM COM COM
BP-W12-2000 BP-W12-2000 BP-W12-2000
N.C.
N.O.
COM
12V
E
12V
GND
P.T.Exit
12V
GND
CN5
CN4
BZ
RLED
GLED
Door Output
WG 0
WG 1
WG-DS
WG-PB
BZ
RLED
GLED
WG 0
WG 1
12V
GND
WG Port
Main Port
E
1
2
3
4
5
6
7
8
CTL
1
2
3
5
6
7
8
4
BP-W12-2000
N.O.
COM
BP-W12-2000
12V
GND
12V
GND
N.O.
COM
12V
GND
CN4
N.C.
N.O.
COM
CTL
12V
GND
PB
12V
GND
DDR
CN8
3
4
5
6
7
8
2
1
4
1 2 3
BP-W12-2000
BP-W12-2000
LCD Access Controller
If any re emergency, the people can escape by press a switch to open all doors
POWER
12VDC
POWER
12VDC
Electric Strike
AR-YS-130NO
Fire Emergency
Transistor
IN4007
Transistor
IN4007
Transistor
IN4007
POWER
12VDC
Strengthen security with AR-721RB Connect to Reader
WG Mode / Controller Mode Setting Method
1. AR-327-E and AR-727-E can be set up as
WG26/WG34/WG64 while the Controller is in
WG Mode. These Controller can also be paired
with the Controller that has WG input function.
2. Networking Setting: Select E Series Controller
Parameter Edit in 701Server,tick up the function
“Ev5 WG out/Hv3 Lift out”
3. Please restart the controller after pressing
“Write to Controller”.
POWER
12VDC
WG Mode Controller Mode
701ServerSQL Parameter Setting701ServerSQL Parameter Setting
12V
GND
CN4
CN4
CN8CN5
CN5
DSS
PB
Duress
ARM
PB
V+
V-(GND)
V+
V-(GND)
3
4
5
6
7
8
3
4
5
6
7
8
1
2
3
5
6
7
8
1
2
3
5
6
7
8
AR-327-E / AR-727-E AR-327-E / AR-727-E
4
4
211
2
Magnetic Lock
AR-0600M-270
Push Button
AR-PB5
Push Button
AR-PB5
Push Button
AR-PB5
Electric Bolt
AR-1207A
Controller
POWER
12VDC
POWER
12VDC
Electric Bolt
AR-1207A
Push Button
AR-PB5
Relay Output Module
AR-721RB
Controller
Reader
POWER
12VDC
POWER
12VDC
Door Sensor
AR-MS-101-A
Push Button
AR-PB5
Relay Output Module
AR-821RB
Electric Bolt
AR-1207A Electric Bolt
AR-1207A
Enable "Share Door Relay" to open the same electronic lock regardless of whether it is triggered by the main controller or the Wiegand reader. This is achieved by using the NO contact of the blue-white wire in
CN4, suitable for systems where the controller and the reader control the same lock.
Disable "Share Door Relay" for card swiping on the main controller, triggering the NO contact of the blue-white wire in CN4. For card swiping on the Wiegand reader, triggering the NO contact of the blue-white
wire Door Output in CN5 WG Port. This allows the main controller and the reader to independently control two electronic locks.
※Please refer to the FAQ for software
conguration instructions:
How to set the E Series card reader to Wiegand
output mode?
Buzzer Output
RLED Output
GLED Output
Door Output
WG 0
WG 1
DSS(GLED Input)
WG PB(RLED Input)
(Buzzer Input)
(The main controller and reader must be grounded together.)
BP-W12-2000
WG Port
Main Port
1
2
3
4

V230630
- 5 -
EL
AC
PT
N.O.
COM
PB
V+
V-(GND)
N.C.
N.O.
COM
CTL
V+
EL
AC
PT
N.O.
COM
PB
V+
V-(GND)
N.C.
N.O.
COM
CTL
V+
LCD Access Controller
Traditional Electronic Door Lock wiring diagram
adopted with controller power supply
Traditional Electronic Door Lock wiring diagram
adopted with interphone power supply
POWER
DC12~24V
POWER
DC12~24V
POWER
AC18V
AR-821RB AR-821RB
Controller
Traditional
Electronic
Door Lock
Traditional
Electronic
Door Lock
Controller
(Controller power supply) (Controller power supply) (Interphone power supply)
※ This wiring diagram function is required to setup Door Relay Time in 1 sec, please refer to 02 TTT command.
Access programming mode → Add/Delete → Add -> RF-Learn → Input 5/6-digit user address
→ Input Tag Units(pcs) → Close Tag into RF Area
※ If adding a batch of Sequential tags, please input Tag Units(pcs) in the quantity of the tags and present the
tag with the lowest card code to the access controller.
1 2
Adding Tag by RF Learn Function Tag Information
SITE CODE
CARD CODE
SITE CODE
CARD CODE
※ User capacity: 16384 (00000~16383)
Access programming mode → Add/Delete → Add -> Card ID → Input 5/6-digit user address → Input Site Code → Input Card Code
11
Adding Tag by Tag ID
Access programming mode → Add/Delete → Delete -> Addr → Input Starting address → Input Ending address
1 5
Deleting User Address
Access programming mode → User Setting → Access Mode → Input User Address → 0: Invalid; 1: Card ; 2: Card or PIN; 3: Card & PIN
2 2
Setting up the access mode
Access programming mode → Add/Delete → Delete -> ID # → Input Site Code → Input Card Code
1 6
Deleting Tag by Tag ID
Adding and Deleting Tag
Programming
A. Keyboard Lock/ Unlock
Lock/ Unlock
Press and , and at the same time to lock keyboard. Press again to unlock.
B. Entering and Exiting Programming Mode
Entering
Input 123456 or PPPPPP
[e.g.] The Default Value= 123456. If already changed the Master Code= 876112, input 876112 → Access programming mode
P.S.If entering no instruction within 30 sec., it will automatically leave the programming mode.
Changing the Master Code
Access programming mode → Tools → Master Code → Input the 6-digit new master code → Succeeded
5 2
Exiting
Press the repeatedly → Quit or Quit and Arming (Please refer to alarm / arming setting)
6 7

SOYAL
ACCESS CONTROL SYSTEM
®AR-327-E / 727-E V230630
- 6 -
F. PIN Code
C. Initial setup
E. Duress Code
Access programming mode → User Setting → Password → Input 5/6-digit user address → Input 4-digit PIN (0001~9999) → Succeeded
Or via 701Client set it on Users screen
21
Node ID of Reader Setting
Access programming mode → Parameters[1] → Node ID → Input New Node ID : 1~254 (default value:001) → Main Door Number : 0~255 →
WG1 Door Number : 0~255 → Show WG Message (0=No,1=Enable) → Network setting → Succeeded
3 1
Language Setting
Access programming mode → Tools → Language → EN → Succeeded → Initial system...
5 1
G. Setting up the alarm / arming
Conditions: 1. Arming enabled 2.Alarm system connected
Application:
1. Door open too long: Door is open longer than door relay time plus door close time.
2. Force open (Opened without a valid user card): Access by force or illegal procedure.
3. Door position abnormal: When power is o and then on, reader on arming before power o.
1
2
3
Or via 701Server to set it on AR-829E-V5 screen
※Duress Code is only available in networking mode. It will substitute a personal pin code and send the message of Duress to computer as a
warning signal.
※The Duress Code 0000 means that disable Duress Function and the default value is set as 0000 already.
Access programming mode → Parameters[2] → Duress Code → 4 sets (select one) → Input 4-digit PIN (0001~9999) → Succeeded
4 7
D. PIN & UID Length setting
Access programming mode → Parameters[1] → PIN & UID format → User PIN Length Range:4~8(4 is default value)
;
Card PIN Length
Range:2~8(4 is default value)
39
0
H. Enable Voice Module (supporting version : F/w Ver 3.02 or later)
Software Setting 701 Server or
Step 1. Click "Read from Controller"
Step 2. Select "Card Reader / Voice Module" in RS485-2 section.
Step 3. Click "Write to Controller" to nish the setting.
Hardware setting
Access programming mode → Tools → Ext. Comm Port → Voice
552
Enable/Disable the arming status:
Standby Mode
Access Programming mode
Card only Card or PIN Card and PIN
Open the door
Present the tag to reader → Input
4 digits arming PWD →
Input user address → Input 4
digits individual PWD → →
Input 4 digits arming PWD →
Present the tag to reader → Input
4 digits individual PWD → →
Input 4 digits arming PWD →
Enable: Access programming mode → Quit & Arming
7Disable: Access programming mode → Quit
6
No open the door
→ Input 4 digits arming PWD
→ Present the tag to reader
E. Setting up the alarm / arming

V230630
- 7 -
RESET
LCD Access Controller
Restoring Factory Settings
Reset all device parameters and user card data
Reset IP Setting:
When the device's power is on, press the
【
RESET】
button the main board untill the ERR (Red) LED of
screen lights up. (Reference to picture)
※ After operation as above, you will hear the long reminder sound,and wait until the
sound disappear then reset the power of the controller,the device will restore factory setting.
Manu Tree
5. Tools
1. Language
2. Master Code
3. Master Range
4. Terminal Port
5. Ext.Comm Port
6. Open Time Zone
7. Informations
8. Clock Setting
9. Daily Alarm
0. UART Port
A. Event Logs
6. Quit
7. Quit & Arming
4. Parameters[2]
1. Auto Relock
2. Egress(R.T.E)
3. Miscellaneous
4. Force Open
5. Close & Stop
6. Anti-pass-back
7. Duress Code
8. Password Mode
9. Factory Reset
3. Parameters[1]
1. Node ID
2. OnO OpenZone
3. Door Relay Tm
4. Door Close Tm
5. Alarm Relay Tm
6. Alarm Delay Tm
7. Arming Delay Tm
8. Arming PWD
9. PIN&UID format
2. User Setting
1. Password
2. Access Mode
3. Extend Options
4. Single Floor
5. Multi Floor
1. Add/ Delete
1. Add > Card ID
2. Add > RF Learn
3. Suspend > Address
4. Suspend > ID #
5. Delete > Address
6. Delete > ID #
7. Recover > Address
8. Recover > ID #
9. Antipass Group
Reset all device parameters and user card data:
Access programming mode → Parameters2 → Factory Reset →0 : System Param ;
1 : User Setting ; 2 : System & User
94
IP Setting
Log-in User Password
When you choose the "Networking Setting" or "User Password" at rst.
Log-in window will pop out and please input
※ At the Factory Default User name: SuperAdm / Password: 721568
Open your Web Browser and input factory default IP
address: http://192.168.1.127
Networking Setting
You will nd initial IP Address 192.168.1.127 and check MAC Address is the
same as sticker on Ethernet Module device. Please revise IP address you
want, and then click “Update” button. After updating the IP, please re-connect
the Web Browser by new IP address.
User Password
The password composes of 10 characters at most, it can be
either A~Z or 0~9.
Change the log-in password to lock the IP setting of
Ethernet Module.
If the IP address of AR-327-E
/ 727-E has changed We must
enter the new IP address.
※ The full screen menu setting is on page7 - Full Function Command Menu Table
User Name is different from old and new version, password can be modify via [User Password] setting on the list but will not be
change from updating new version. If you forgot the password, the solution is pressing Reset Button to reset it as default value.
NOTE :
Firmware Version User name Password (changeable)
After 2020/01/21 SuperAdm Default Password : 721568 or self-denition
Before 2020/01/21 admin Default Password : admin/ password not required or self-denition

V230630
- 8 -
LCD Access Controller
Entering
Input 123456 or PPPPPP
[e.g.] The Default Value= 123456. If already changed the Master Code= 876112, input 876112
→ Access programming mode
P.S.If no instruction is entered within 30 sec., it will automatically leave the programming mode.
Up
Down
Enter/OKEsc/Quit
1. Add/ Delete
2. User Setting
1-4. Suspend > ID #
2-4. Single Floor
1-9. Antipass Group
1-4-1
2-4-1
1-9-1
1-4-2
2-4-2
1-9-2
Set Site:
00000:XXXXX
Range: (0-65535)
User Address:
F3: Prev F4: Next
Range (0-016383)
Input Start Address
Range: (0-16383)
Set Code:
00000:XXXXX
Range: (0-65535)
Set Single Floor
(Range: 01~64)
Clear the Others
Input End Address
Range: (0-16383)
1-5. Delete > Address
2-5. Multi Floors
1-5-1
2-5 -1
1-5-2
2-5-2
Input Start Address
Range: (0-16383)
User Address:
F3: Prev F4: Next
Range: (0-016383)
Input End Address
Range: (0-16383)
Select Range:
1: 01-16 2: 17-32
3: 33-48 4: 49-64
1-3. Suspend -> Address
2-3. Extend Options
1-8. Recover > ID #
1-3-1
2-3-1
1-8-1
1-3-2
2-3-2
1-8-2
Input Start Address
Range: (0-16383)
User Address:
F3: Prev F4: Next
Range (0-16383)
Set Site:
00000:XXXXX
Range: (0-65535)
Input End Address
Range: (0-16383)
Is Guard User
0: NO 1: YES
Set Code:
00000:XXXXX
Range: (0-65535)
1-1. Add -> Card ID
2-1. Password
1-6. Delete > ID #
1-1-1
2-1-1
1- 6 -1
1-1-2
2-1-2
1-6-2
1-1-3
User Address:
00000 XXXXX
Range: (0-16383)
User Address:
F3: PreV F4: Next
Range (0-016383)
Set Site:
00000:XXXXX
Range: (0-65535)
Set (User Address) Code:
00000 XXXXX
(1-10 Digital)
Input PIN Code
Rang: 0000~9999
Set Code:
00000:XXXXX
Range: (0-65535)
Set (User Address) Code:
00000:_XXXX
Range: (0-65535)
1-2. Add -> RF-learn
2-2. Access Mode
1-7. Recover > Address
1-2-1
2-2-1
1-7-1
1-2-2
2-2-2
1-7-2
1-2-3
2-3-3 2-5-3
1-9-3
User Address:
F3: Prev F4: Next
Range: (0-016383)
User Address:
F3: Prev F4: Next
Range (0-163833)
Input Start Address
Range: (0-16383)
Tag Uints (pcs)
Must be Sequence
Range: (1-016378)
0: Invalid 1: Card
2: Card or PIN
3: Card & Pin
Input End Address
Range: (0-16383)
Close Tag
Into RF Area
Enable Antipass
0: NO 1: YES
Data: 1
0->NO 1->YES
Current Setting:
1000000000000000
Enable Antipass
0: NO 1: YES
Data: 0
Full Function Command Menu Table

V230630
- 9 -
LCD Access Controller
Full Function Command Menu Table
3. Parameters [1]
4. Parameters [2]
3-3. Door Relay Tm
3-8. Arming PWD.
3-3-1
3-8-1
Main Door OpenTm
Range: 000~609
601~609=0.1~0.9
007
Input PIN Code
Range: 0000~9999
1234
3-4. Door Close Tm
3-9. PIN&UID format
3-7. Arming Delay Tm3-5. Alarm Relay Tm 3-6. Alarm Delay Tm
3-4-1
3-9-1 3-9-3 3-9-5 3-9-7
3-7-13-5-1 3-6-1
Main Door Close
delay time (Sec)
Range: 000~255
015
User PIN Length
Range: 4~8
4
Show UID :0=No
1=WG 2=ABA
3=HEX 4=WG26
5=ABA8
1
RFID 125KHz RF
0: Disable
1: Enable
1
User Capacity:
0: 16384 1: 32768
2: 65536 (0~2)
0
Enter armed sta.
Delay time (Sec)
Range: 000~255
001
Alarm Relay Time
Range: 000~609
601~609=0.1~0.9
015
Alarm Output
Delay time (Sec)
Range: 000~255
3-2. OnOff OpenZone
3-2-1
Main Controller
Auto Open Zone
Dis/Enable (0/1)
0
3-1. Node ID
4-1. Auto Relock 4-2. Egress(R.T.E) 4-3. Miscellaneous
3-1-1
4-1-1 4-2-1 4-3-1 4-3-4 4-3-7
3-1-2
4-1-2 4-2-2 4-3-2 4-3-5 4-3-8
4-3-3 4-3-6 4-3-9
3-1-6 3-2-2
3-3-2 3-4-2
3-9-2 3-9-4 3-9-6 3-9-8
3-7-2
3-1-3 3-1-5 3-1-7
3-1-4 3-1-8
Input New NodeID
Range: 001~254
Current Data: 001
Main Controller
Auto Relock Door
0: NO 1:YES
0
Main Controller
Request To Exit
0: Dis 1:Enable
0
Main Controller
TimeAttendance
0: YES 1: NO
0
WG1 Port
Skip PIN Check
0: NO 1: YES
0
WG1 Port
Share Main Relay
0: NO 1: YES
0
Main Door Number
Range: 000~255
WG Prot
Auto Relock Door
0: NO 1:YES
0
WG1 Port
Request To Exit
0: Dis 1:Enable
0
WG1 Port
TimeAttendance
0: YES 1: NO
0
Main Controller
Pass any Tags
0: NO 1: YES
0
Tag Second time
interval (10ms)
Range: 0000~9999
0100
Main Controller
Skip PIN Check
0: NO 1: YES
0
WG1 Port
Pass any Tags
0: NO 1: YES
0
Max error times
for lock keypad
Range: (0~9)
5
IP Address (IPv4)
192.168.001.127
192.xxx.xxx.xxx
WG1 Port Auto Open
Zone Dis/Enable (0/1)
0
WG1 Door OpenTm
Range: 000~609
601~609=0.1~0.9
007
WG1 Door Close
delay time (Sec)
Range: 000~255
015
Card UID Length
Range: 2~8
4
NFC 13.56MHz RF
0: Disable
1: Enable
1
'#' is Door Bell
0: Disable
1: Enable
0
Enable Buzzer
0: NO 1: YES
1
Armed Pulse out-
put time. (10ms)
Range:000~255
000
WG1 Door Number
Range: 000~255
Net Mask (IPv4)
255.255.255.000
255.xxx.xxx.xxx
Show WG Message
0: NO 1:Enable
1
Gateway (IPv4)
192.168.001.254
192.xxx.xxx.xxx
Enable DHCP
0: No 1: En 2: Exit
192.168.001.127*
0
※User PIN Length Range:4~8(4 is default value)
;
Card PIN Length Range:2~8(4 is default value)

V230630
- 10 -
LCD Access Controller
Full Function Command Menu Table
4. Parameters [2]
5. Tools
6. Quit
※More Details:Introduction of New Function Commands for Enterprise E Controller and Home H Controller
7. Quit & Arming
5-1. Language
5-2. Master Code
5-3. Master Range
5-6. Open Time Zone 5-9. Daily Alarm 5-0. UART Port CN9
5-A. Event Logs
5-8. Clock Setting5-7. Informations
5-4. Terminal RS485 5-5. Ext.Comm CN11
4-7. Duress Code 4-8. Password Mode 4-9. Factory Reset
5-1-1
5-2-1
5-3-1
5-6-1 5-9-1 5-0 -15-8-15-7-1
5-4-1 5-5-1
4-7-1 4-8-1 4-9-1
5-3-2
5-6-2 5-9-2 5-0-25-8-2
5-6-3 5-9-3
5-A-1
5-4-2 5-5-2
5-5-3
0: English (USA)
1: Chinese (TW)
0
Input MasterCode
000001~999999
123456
Input Start Addr
Range: (0-16383)
000000
Set <F1~F4,#>: 01
00:00~00:00 ..
SuMoTuWeThFrSaHo
0 0 0 0 0 0 0 0
Set <F1~F4,#>: 01
00:00 Sec.=000
SuMoTuWeThFrSaHo
0 0 0 0 0 0 0 0
0: Lift9600 1: PRN
2: LED 3: Voice
0
YY: XXXX MM: XX
Day: XX Hour: XX
Min: XX Sec: XX
F/w Ver: 4.4T
Users: 00000
Messages: 00000
Press any Key ...
0: Lift 1: Host
2:LED 3: PRN
1
0: Suspend 1:Lift
2: Voice 3: PRN
1
Input PIN Code
Range: 0000~9999
Password Mode
0: Addr. & PIN(M4)
1: PIN(M8) 2:M6
1
0: System Param.
1: User Setting
2: System & User
2
Input End Addr
Range: (0-16383)
000000
Time=00:00~00:00
Main Port (0/1):0
WG Port (0/1):0
Start Tm=00:00
Effect Sec.=000
Elevator oor
button available
Range: (1~600)
015
Month/Day Format
0: DD/MM 1: MM/
DD
Weekday: (0/1)
SuMoTuWeThFrSaHo
X X X X X X X X
0 0 0 0 0 0 0 0
Weekday: (0/1)
SuMoTuWeThFrSaHo
X X X X X X X X
0 0 0 0 0 0 0 0
20'06/04 2359:26
(M24)Controller
Power On 00000
Baud Selection
0: 9600 1: 19200
2: 38400 3: 57600
0: 4800 1: 9600
2: 19200 3: 38400
1
Elevator oor
button available
Range: (1~600)
000
4-3. Miscellaneous 4-4. Force Open .. 4-5. Close & Stop 4-6. Anti-passback
4-3-10 4-4-1 4-5-1 4- 6-14-3-12
4-3-134- 3-11 4-4-2 4-5-2 4-6-2
Main Controller
On Egress Beeps
0: NO 1: Bi 2: Bibb
2
Main Controller
Force Open Alarm
0: NO 1: YES
0
Main Controller
Close Door Stop
Alarm 0: NO 1:YES
0
Main Controller
Anti-passback
0: NO 1: YES
0
Lock Door Relay
0: NO 1: YES
0
Interlock to WG ?
0:NO 1:YES
0
WG1 Port
On Egress Beeps
0: NO 1: Bi 2: Bibb
2
WG1 Port
Force Open Alarm
0: NO 1: YES
0
WG1 Port
Close Door Stop
Alarm 0: NO 1:YES
0
WG1 Port
Anti-passback
0: NO 1: YES
0