SpectraLink Link 150 Owner's manual

The LinkWireless
Telephone System
Link 150 Installation and Operation
Part Number: 72-0021-01
Issue A
12/28/98

SpectraLink Link Wireless Telephone System Link 150 Installation and Operation
12/28/98 i
Trademark Information
Comdial is a Registered Trademark of Comdial Corporation
DEFINITY is a Registered Trademark of Lucent Technologies Inc.
MERLIN LEGEND is a Registered Trademark of Lucent Technologies Inc.
Meridian is a Registered Trademark of Northern Telecom Ltd.
Mitel SX is a Registered Trademark of Mitel Corporation
Norstar is a Registered Trademark of Northern Telecom Ltd.
ROLMphone is a registered trademark of Siemens Business Communication Systems Inc.
Strata is a Registered Trademark of Toshiba America Information Systems, Inc.

SpectraLink Link 150 Installation and Operation
12/28/98 ii
TABLE OF CONTENTS
1. ABOUT THIS DOCUMENT 1
1.1 Questions? 1
1.2 Icons and Conventions 1
1.3 Installation Overview 1
2. LINK 150 OVERVIEW 3
2.1 System Operation 3
2.2 The Front Panel of the MCU 5
2.3 The Rear Panel of the MCU 6
3. SITE PREPARATION 9
3.1 Required Materials 9
3.2 Determine Location of MCU 9
3.3 Plan Telephone System Programming 9
4. RUN WIRE FOR SYSTEM 11
4.1 Connections to the Telephone System 11
4.1.1 Connections for Wireless Telephones 11
4.1.2 Dedicated Line for Diagnostic Modem 11
4.2 Connections to Base Stations 11
4.2.1 Pull Wire to Base Station Locations 12
4.2.2 Terminate Wire to Base Stations 13
5. INSTALL SPECTRALINK SYSTEM 15
5.1 Survey Site 15
5.2 Check Components 15
5.3 Install MCUs 17
5.3.1 Connect Multi-Unit Systems 17
5.3.2 Connect MCU to Base Station Wiring 18
5.4 Install Base Stations 18
5.4.1 Mount Base Stations on Dropped Tile Ceilings 18
5.4.2 Mount Base Stations On Finished Ceilings 19
5.5 Install Outdoor Base Stations 19
5.5.1 Wire Outdoor Base Stations 20
5.5.2 Mount and Connect Outdoor Base Stations 20

SpectraLink Link 150 Installation and Operation
12/28/98 iii
6. CONNECT AND REGISTER WIRELESS TELEPHONES 21
6.1 Connect Wireless Telephones 21
6.2 Set Up Diagnostic Modem 21
6.3 Register Wireless Telephones 21
6.4 Unregister Wireless Telephones 23
6.5 Program Wireless Telephone Features 23
6.6 Test Wireless Telephones 23
7. SITE CERTIFICATION 25
8. SYSTEM ADMINISTRATION 27
8.1 Troubleshoot Error Codes 27
8.2 Troubleshoot Phone Features 27
8.2.1 MCU Error Codes 28
8.2.2 Wireless Telephone Display Messages 30
8.3 Replace a Wireless Telephone 30
8.3.1 Delete Old Wireless Telephone 30
8.3.2 Register New Wireless Telephone 31
8.4 Replace an MCU 31
8.5 Replace a Base Station 32
APPENDICES 33
A. Technical Parameters 35
1. Select Alternate Spread Spectrum Sequence 35
2. Change Companding 36
B. Connect The Alarm Relay 37
C. Program Analog System Functions 39
1. Plan The Features 39
2. Program The Features 39
D. ComdialDXP/DTS System 41
1. Comdial Wiring 41
2. Programming Considerations 41
3. Set Up Access to Diagnostic Modem 43
4. Program Comdial 43
5. Copy Programming 44
E. DEFINITYCommunications System 45

SpectraLink Link 150 Installation and Operation
12/28/98 iv
1. DEFINITY Wiring 45
2. Programming Considerations 47
3. Set Up Access to Diagnostic Modem 49
4. Program DEFINITY 49
5. Duplicate Programming on Wireless Telephones 50
F. MERLIN LEGENDPBX 51
1. LEGEND Wiring 51
2. Programming Considerations 51
3. Set Up Access to Diagnostic Modem 53
4. Program MERLIN LEGEND 53
5. Copy Programming 54
6. Assign Individual Intercom Lines and Features 54
G. MeridianPBX 55
1. Meridian Wiring 55
2. Programming Considerations 55
3. Set Up Access to Diagnostic Modem 57
4. Program Meridian 57
5. Copy Programming 58
H. NorstarKey System 59
1. Norstar Wiring 59
2. Programming Considerations 59
3. Set Up Access to Diagnostic Modem 61
4. Program the Norstar 62
5. Set Copy 63
I. Toshiba StrataDK Key System 65
1. Toshiba Wiring 65
2. Programming Considerations 65
3. Set Up Access to Diagnostic Modem 68
4. Program the Toshiba 68
J. ROLM System 70
1. ROLM Wiring 70
2. Programming Considerations 70
3. Set Up Access to Diagnostic Modem 72
4. Program the ROLM 72
K. Mitel System 74

SpectraLink Link 150 Installation and Operation
12/28/98 v
1. Mitel Wiring 74
2. Programming Considerations 74
3. Set Up Access to Diagnostic Modem 76
4. Program the Mitel 76
L. Wireless Telephone Planning Worksheet 78

SpectraLink Link 150 Installation and Operation
12/28/98 vi
FCC, UL and DOC Statements
FCC INFORMATION
This unit Complies with Part 68, FCC Rules
FCC Registration Number IYGUSA-21873-PX-E
Ringer Equivalence 0.3B
SpectraLink Corporation
Link 150 / PCS 150
Made in the USA
This equipment complies with Part 68 of the FCC Rules. On the rear panel of the Master Control Unit (MCU) is a label that contains, among
other information, the FCC Registration Number and Ringer Equivalence Number (REN) for this equipment. If requested, this information must
be given to the telephone company.
The REN is useful to determine the quantity of devices you may connect to your telephone line and still have all of those devices ring when your
number is called. In most, but not all, areas, the sum of the RENs of all devices connected to one line should not exceed five (5.0). To be certain
of the number of devices you may connect to your line, as determined by the REN, you should contact your local telephone company to
determine the maximum REN for your calling area.
If your telephone equipment causes harm to the telephone network, the telephone service may discontinue your service temporarily. If possible,
they will notify you in advance. But if advance notice isn’t practical, you will be notified as soon as possible. You will be informed of your
right to file a complaint with the FCC.
Your telephone company may make changes in its facilities, equipment, operations or procedures that could affect the proper functioning of your
equipment. If they do, you will be notified in advance to give you an opportunity to maintain uninterrupted telephone service.
If you experience trouble with this telephone equipment, please contact SpectraLink’s Customer Service department or your authorized
distributor for information on obtaining service or repairs. The telephone company may ask that you disconnect this equipment from the network
until the problem has been corrected or until you are sure that the equipment is not malfunctioning.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.
Caution: If the user makes changes or modifications not expressly approved by the party responsible for compliance could void the user’s
authority to operate the equipment.
UL INFORMATION
C
This symbol on the nameplate means that the product is listed by Underwriter’s Laboratories, Inc. It is designed and
manufactured to meet rigid UL safety standards against X-radiation, fire, casualty, and electrical hazards.
The following are statements required for UL certification, related to safety procedures that must be adhered to during installation.
If wiring for a Base Station exits a building—whether to reach an outdoor Base Station location or to reach a Base Station in another building—
the wiring must be protected at both ends by a Quick Clip Fuse from Reliable Electric, model number RSCP-2.
Followthese general precautions while installing telephone equipment:
• Never install telephone wiring during a lightning storm.
• Never install telephone jacks in wet locations unless the jack is specifically designed for wet locations.
• Never touch uninsulated telephone wires or terminals unless the telephone line has been disconnected at the network interface.
• Use caution when installing or modifying telephone lines.

SpectraLink Link 150 Installation and Operation
12/28/98 vii
CANADIAN DOC NOTICES
Avis du ministère des Communications du Canada
DOC CS03
Load Number: 4 Facteur de charge : 4
Certification Number: CANADA 2128 6468 A
Numéro de Certification: CANADA 2128 6468 A
The Load Number (LN) assigned to each terminal device denotes the percentage of the total load, to be connected to a telephone loop,
which is used by the device, to prevent overloading. The termination on a loop may consist of any combination of devices subject only to
the requirement that the total of the Load Numbers of all devices does not exceed 100.
Le facteur de charge (FC) attribué à chaque terminal représente le pourcentage de la charge totale, pouvant être attibuée à une boucle
téléphonique, qui est utilisée par le dispositif en question afin d'éviter la surcharge de ce dernier. La terminaison de la boucle peut
comprendre desdispositifs à charge variées à condition que le total du facteur de charge de ceux-ci ne dépasse pas 100.
Doc Notice to Canadian Customers
Avis du ministère des Communications (MDC) aux clients canadiens
The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets
certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment
will operate to the user's satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications
company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that
compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or
alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request
the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal
metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority,
or electrician, as appropriate.
L'étiquette émise par le ministère des Communications sert à identifier la cerification de l'équipement. Cette certification indique donc
que l'équipement satisfait aux exigences du réseau des télécommunications en ce qui a trait à la protection, aux mesures de sécurité et au
fonctionnement. Le ministère ne peut, toutefois pas garantir le bon fonctionnement de l'appareil.
Avant l'installation de l'équipement, l'usager doit s'assurer que son raccordement aux services téléphoniques locaux est permis. Cette
installation doit respecter les normes prescrites. Il est à souligner toutefois que même si les conditions ci-haut mentionnées sont
respectées, une détérioration du service peut parfois se produire.
Pour toute réparation de son équipement certifié, l'usager devrait faire appel aux services de maintenance canadiens désignés par le
fournisseur. Le fournisseur du service téléphonique pourrait demander la mise hors service de l'équipement suivant toute réparation
ou modification effectuée par l'usager, ainsi que suivant une défaillance de fonctionnement quelconque.
Pour des fins de protection, l'usager doit assurer l'interconnection du raccord électrique de mise à la terre des services d'électricité,
téléphonique et du réseau de tuyaux métalliques d'eau, au besoin. Il faut s'assurer de prendre cette précaution, surtout dans les
régions rurales.
Attention: Les usagers ne doivent pas tenter d'effectuer de tels raccordements. Ils sont priés de s'adresser à un service d'inspection
électrique ou à un électricien, selon le cas.
DOC Canadian Maintenance Facility
Service de maintenance canadien du MDC
Mitel
350 Legget Dr.
Kanada, Ont., CN K2K 1X3
Contact: Mike Branchaud
DOC EMC Class A
This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus as set out in the interference-
causing equipment standard entitled "Digital Apparatus", ICES-003 of the Department of Communications.
Cet appareil numérique respecte les limites de bruits radioélectriques applicables aux appareils numériques de Classe A prescrites dans la
norme sur le matériel brouilleur: "Appareils Numériques", NMB-003 édictée par le ministre des Communications.
Cet appareil numérique respecte les limites de bruits radioélectriques applicables aux appareils numériques de Classe A prescrites dans la norme
sur le matériel brouilleur: "Appareils Numériques", NMB-003 édictée par le ministre desCommunications. DOC Spread Spectrum Certification

SpectraLink Link 150 Installation and Operation
12/28/98 1
1. About This Document
This document explains installation and operation of SpectraLink’s Link Wireless
Telephone System (WTS), Link 150. The Link 150 adds wireless service to your existing
telephone system. The installation process connects the Link 150 to your telephone
system, and activates the Link Wireless Telephones.
1.1 Questions?
SpectraLink wants you to have a successful installation. If you have questions please
contact our Customer Support Hotline at (800) 775-5330. The Hotline is open
Monday through Friday, 7:00 AM to 6:00 PM Mountain Time.
1.2 Icons and Conventions
This manual uses the following icons and conventions.
Caution! Follow these instructions carefully to avoid danger.
Note these instructions carefully.
NORM This typeface indicates a key, label, or button on the MCU or wireless
telephone.
A
This font indicates a message on the MCU's seven segment display.
1.3 Installation Overview
Installation has three phases. In most cases, a separate person is responsible for each
phase.
•Site preparation and wire installation – this is usually done by a wire technician or
contractor.
•Installing the SpectraLink system – this is done by SpectraLink or one of our
certified distributors.
•Programming the customer's telephone system to work with the SpectraLink
system – this is usually done by the customer’s system administrator or technician.
Because these major steps require some parallel activities, it is important to coordinate the
activities among the persons involved.

SpectraLink Link 150 Installation and Operation
12/28/98 2
The following table lists the installation steps and the person responsible for each step.
9
9
Task
Description Wire
Contractor
Installer System
Admin
Site Preparation
Determine Location of MCU
9
Plan Telephone System Programming
9
Run Wire
Connections to Telephone System
9
9
Connections for wireless telephones
9
Dedicated Line for Diagnostic Modem
9
9
Connections to Base Stations
Pull Wire to Base Station Locations
Terminate Wire to Base Stations
9
Install SpectraLink System
Survey Site and Check Components
9
Install MCUs
9
Install Base Stations
9
Install Outdoor Base Stations
9
Connect and Register Wireless Telephones
9
Program Wireless Telephone Features
9
Test Wireless Telephones
9
Site Certification
9

SpectraLink Link 150 Installation and Operation
12/28/98 3
2. Link 150 Overview
Review this section if you are unfamiliar with the features and operation of the Link 150.
2.1 System Operation
SpectraLink's Link WTS is a wireless communication system that offers direct telephone
access for incoming and outgoing calls anywhere within a facility.
The Link WTS consists of three basic components: the Master Control Unit (MCU), the
Base Station and the Link Wireless Telephone. This diagram shows an overview of
system. Components are described below.
•Master Control Unit (MCU) – serves as the connecting point, or gateway, between
the Base Stations and the existing telephone system. One or more of these small boxes
(8 x 3 x 9 inches) are typically installed in the telephone equipment room and provide
connectivity from the telephone system to the wireless system. Each MCU is hard-
wired to one or more Base Stations, which in turn provides the wireless link to each of
the wireless telephones. The MCU establishes the connection from the telephone line
to the appropriate Base Station in order to reach a wireless telephone.
The MCU supports four Base Stations and up to 16 wireless telephones. Up to four
Link 150 MCUs can be chained together for extended coverage area. Chained MCUs
support up to 64 wireless telephones maximum.
SpectraLink offers an analog MCU that works with all premises telephone systems
(PBX or Key Systems) with analog (tip-ring or industry standard) ports. We also

SpectraLink Link 150 Installation and Operation
12/28/98 4
offer digital MCUs that work with certain brands of telephone systems' (PBX or key
systems) digital ports.
•Base Stations – act as a radio transceiver to provide the communications signal
between the wireless telephone and the MCU. Base Stations are slightly larger than a
smoke detector and are typically mounted on the ceiling, in strategic locations
throughout the facility. A single Base Station can provide radio coverage for an area
of 5,000 to 50,000 square feet depending on building obstructions. Base Stations may
be located up to 2,200 cable feet from the MCU.
When a wireless telephone user makes or receives a call, the wireless telephone and
Base Station establish a digital radio communication link. As the user moves around
the coverage area, calls are “handed off” to the Base Station that is able to provide the
best radio signal (typically the closest Base Station). These handoffs involve the
wireless telephone establishing a communication link with another Base Station and
dropping the previous link.
•Link Wireless Telephones – communicate with the Base Station using digital spread
spectrum transmission at 902-928 MHz. Employees can carry wireless telephones to
keep in contact as they move throughout the building. The wireless telephones use
on-premise wireless technology; they are not cellular or satellite phones. They are
connected to the facility's existing telephone system and, just like wired telephones,
can receive calls directly, receive transferred calls, transfer calls to other extensions,
and make outside and long distance calls (subject to the restrictions applied in your
facility.)

SpectraLink Link 150 Installation and Operation
12/28/98 5
2.2 The Front Panel of the MCU
The MCU's front panel functions as an operator's console to indicate the status of the unit.
1
2
4
35
6
7
8
1. Line Indicator LEDs – Indicate the line status of each wireless telephone:
ringing, in use, or not active.
2. Base Station LEDs – Indicate the status of each Base Station:
−Amber: a Base Station is operational and ready for a call.
−Green: one or more call is active on the Base Station.
−Red: an error on the Base Station.
−Alternating Red/Green: the Base Station is downloading or performing
start-up tests.
−Not lit: no Base Station is connected to that port.
3. STEP Button – Selects a specific line or Base Station during registration process.
4. Mode Switch – Selects the mode of operation for the Link 150 system.
−NORM: Normal mode, used during day-to-day operations.
−REGISTER: Registration mode, used to add or delete wireless telephones
and Base Stations from the system.
−ADMIN: Administration mode, used to set up system features to match
features on the telephone system.
5. DELETE Button – Removes a registered wireless telephone from the system.
6. Seven-Segment Display – Indicates the MCU number (1-4) or the error number if
a fault is detected. Refer to MCU Error Codes for more information.
7. Error LED – Flashes when the system has detected an error. When flashing,
check the seven-segment display for an error code.
8. Alarm Switch – When switch is ON and an error condition is detected, an audible
alarm sounds. When in the OFF position, no audible alarm is sounded.

SpectraLink Link 150 Installation and Operation
12/28/98 6
2.3 The Rear Panel of the MCU
The MCU's rear panel contains the ports that power the unit and connect it to the
telephone system, the Base Stations, and the alarm notification device.
34 5
6
7
1
2
1. Telephone Lines – A standard RJ-11 connector is used to connect each line from the
telephone system to the MCU. There are three sizes of MCU, each with a different
number of ports. The X in the following part numbers represents the type of interface
on the MCU.
−MCA-450 – no ports; used only to provide extra Base Stations on a
multiple MCU system
−MCX-452 – 8 ports
−MCX-454 – 16 ports
2. Serial Number and Model Number – SpectraLink Customer Support will request
the serial number when you call them. The model number indicates the MCU type.
MCA-450, 452, or 454 are analog units; all other model numbers are digital units.
3. Power Jack – Connects to the AC adapter to supply power to the system. The label
next to the power jack is color coded to the label at the end of your power supply.
Use only the provided Class II AC Adapter with
output 24VDC, 1A.
4. Base Station Ports – Provide connection for up to four Base Stations.
5. IPC IN Port – Used only in systems with more than one MCU. The first unit in a
chain of MCUs has no connection to the IN Port.
6. IPC OUT Port – Used only in systems with more than one MCU or with an Open
Applications Interface (OAI) Gateway. The first unit’s OUT Port connects to the

SpectraLink Link 150 Installation and Operation
12/28/98 7
second unit’s IN Port. The OUT Port of the last unit in a chain is only used if the
system has an OAI Gateway.
7. Alarm Out Connector – The connector receives a 3.5mm stereo plug to provide a
relay contact closure when alarms are active.
This relay is designed for low voltage alarm
signaling only. Do NOT connect any device to the
relay that is operated directly from 110V power.
The relay contact supports a maximum alarm load
of 1 amp at 24VAC or 24VDC.

SpectraLink Link 150 Installation and Operation
12/28/98 8

SpectraLink Link 150 Installation and Operation
12/28/98 9
3. Site Preparation
3.1 Required Materials
The following equipment must be provided by the customer.
1. MCU Shelf – The MCU is designed to be mounted on a customer-supplied shelf.
2. Outlet Strip – Recommended for installations with more than one MCU. This
will allow the MCUs to be turned on and off together.
3. RJ-11 6-pin phone line cord – Up to sixteen cords will be needed to connect
telephone lines to each MCU. On most systems only the two center pins are used.
Refer to the appropriate Appendix for your telephone system for more information
4. Base Station connection cable –Two to four pairs for each Base Station. These
cables need 8-pin RJ-45 modular connectors on each end. Refer to 4.2
Connections to Base Stations for more information.
5. 66 Block and Quick Clip Fuse – Required with an RCO410 Outdoor Base
Station or when a Base Station is located in a separate building from the Link 150.
Recommended Quick Clip Fuse is available from Reliable Electric, Model # RSCP-
2.
6. Mounting Hardware – If the Base Stations will be mounted on finished walls or
ceilings, a 4-5" long ¼" bolt, nuts, and washers will be required for each Base
Station mounted.
3.2 Determine Location of MCU
The MCU is approximately 8 inches wide, 3 inches high, and 9 inches deep, and weighs
about 3.5 pounds. The unit is designed to be mounted on a 24- inch by 12-inch shelf,
usually placed in the telephone equipment room.
Select a location for the MCU with sufficient backboard space and an available outlet.
Since the front panel is used as an operator's console, mount the unit so the front panel is
accessible.
If your system has more than one MCU, plan to install the MCUs
side by side, not on top of one other. Stacked MCUs cause
overheating and intermittent failure.
3.3 Plan Telephone System Programming
The wire contractor should inform the system administrator which port numbers have been
designated for the wireless telephones and the remote diagnostics modem line.
The system administrator must assign extension numbers to the wireless telephones and
plan the functions (trunk access, toll restrictions, system features, ringing options etc.) to

SpectraLink Link 150 Installation and Operation
12/28/98 10
be programmed for the wireless telephones. This programming will be done after the
wireless telephones are registered, but will be faster if it is planned in advance by verifying
the parameters and features on the current telephone system and wired phones.
One of these scenarios concerning how the wireless telephones are programmed should
apply to this site:
•All Wireless Telephones are Programmed Alike – All SpectraLink telephones will
be programmed exactly the same. Program one SpectraLink telephone and use it as a
model for all other telephones.
•Groups of Wireless Telephones are Programmed Alike – SpectraLink telephones
are grouped into classes that are programmed alike. Program the model SpectraLink
telephones then use them as a model to program the other telephones.
•All Wireless Telephones Different – All SpectraLink telephones are programmed
differently, so each telephone will be programmed individually.
For details, refer to the Appendix for the type of telephone system for the MCU you are
using.
Use the Wireless Telephone Planning Worksheet at the end of this document to track the
port numbers, extensions, users, and features assigned to your telephones.

SpectraLink Link 150 Installation and Operation
12/28/98 11
4. Run Wire for System
4.1 Connections to the Telephone System
4.1.1 Connections for Wireless Telephones
The MCU is connected to the existing telephone system using standard RJ-11 6-position,
2- or 4-conductor phone line cord. Up to sixteen cords (one for each wireless telephone)
will be needed to connect telephone lines to each MCU.
Wiring details may differ based on the model of MCU you are installing.
Refer to the appropriate Appendix.
Inform the system administrator which ports have been designated for use with the
wireless telephones.
If the wiring between the Link 150 and the telephone system leaves the
building, consult your telephone system manual for instructions on providing
adequate lightning and other over-current protection. The telephone system
must be listed with a safety agency such as Underwriter’s Laboratories (UL).
Isolation between the public telephone network and the Link 150 is provided
by the listed telephone system equipment.
4.1.2 Dedicated Line for Diagnostic Modem
The Link 150 can be accessed remotely using an internal modem. To use the modem for
remote access, a dedicated dial-in line must be provided. On digital interface systems this
line must be terminated as a digital extension to the MCU.
Inform the system administrator which port has been designated for the modem.
4.2 Connections to Base Stations
The Base Station locations should be designated on the building floorplans provided to the
installer.
Base Stations can be mounted easily on raised or acoustical ceiling tiles, or on the wall.
Avoid locating Base Stations in high or hard-to-reach places, as this will hinder
maintenance, testing, or repositioning.
The customer's wire contractor is responsible for adhering to all local codes
for wiring.

SpectraLink Link 150 Installation and Operation
12/28/98 12
Most installations run four pair cable, but you can run cable with fewer pairs, subject to
the length restrictions in the following table. The wire should be Level 3 or better
telephone wire.
22 AWG Wire Distances
Distance to Base
Station Wire Pairs
0-733 Feet 2
734-1467 Feet 3
1468-2200 Feet 4
24 AWG Wire Distances
Distance to Base
Station Wire Pairs
0-455 Feet 2
456-910 Feet 3
911-1365 Feet 4
Install an extra 50 feet of wire to allow for future relocation of a Base Station.
4.2.1 Pull Wire to Base Station Locations
Pull the wire from the MCU location (usually in the telephone equipment room) to the
Base Station locations designated on the floorplans.
1. Determine the amount of wire needed to connect the Base Station to the MCU by
scaling from a floorplan or a sketch, pacing, measuring, or estimating. Remember
to include enough wire to reach the ceiling.
2. Pull the wire between the Link 150 and the Base Station locations. Wire a surface
mount or similar jack to each end. Refer to 4.2.2 Terminate Wire to Base
Stations below.
If the wiring exits the building, refer to Wire Outdoor Base Stations below.
3. Create a permanent Base Station cable for each Base Station. Use 8 conductor
silver satin telephone cord or 22 AWG category 3 wire and crimp 8-pin modular
connectors to both ends.
Other manuals for Link 150
1
Table of contents
Other SpectraLink Telephone System manuals

SpectraLink
SpectraLink Link Wireless Instruction Manual

SpectraLink
SpectraLink 150 M3 MCU Operating instructions

SpectraLink
SpectraLink Link 150 Owner's manual

SpectraLink
SpectraLink JPI300 User manual

SpectraLink
SpectraLink Link 150 M3 Operating instructions

SpectraLink
SpectraLink ROLM PBX User manual

SpectraLink
SpectraLink SpectraLink 6300 MCU Operating and maintenance instructions

SpectraLink
SpectraLink JPI300 Setup guide

SpectraLink
SpectraLink Link 150 M3 Operating instructions

SpectraLink
SpectraLink JPI300 User manual