3.589.5275.90020
3.589.5275.900 Ed. 1 IT16
Le diverse configurazioni si possono riassumere in 4 modi ope-
rativi: considerando che, convenzionalmente, le valvole a 3 vie
rotative sono chiuse quando è necessario raffreddare il fluido
controllato (posizione fluido freddo).
Scegliere uno dei modi operativi a, b, c, d ed iniziare l’installazio-
ne della valvola. Si noti che è possibile modificare i modi di ope-
razione in campo senza dover rimuovere la valvola dalla linea.
The various configuration can be indicated to 4 modes of
operations considering that, conventionally, rotary 3 ways valves
are considered closed when it is not necessary to cold the
controlled fluid (cold position).
Select one of the valve operation mode a, b, c, d and start
mounting the valve. Note that it is possible to change modes of
operation without removing the valve from the line.
Modi operativi con rotazione antioraria del motore
Modes of operation with counterclockwise rotation
Modi operativi con rotazione oraria del motore
Modes of operation with clockwise rotation
A
C
BAB
C CC
BBAA
Modo / Mode “a” Modo / Mode “b” Modo / Mode “c” Modo / Mode “d”
Configurazione DD e MC
Configuration DD and MC
Configurazione DA e MB
Configuration DA and MB
Configurazione DC e MD
Configuration DC and MD
Configurazione DB e MA
Configuration DB and MA
Porta B - Sempre aperta
Port Always open
Porta A - Chiusa per bassa temperatura
Port Closed at lower temperature
Porta C - Chiusa per alta temperatura
Port Closed at upper temperature
Porta B - Chiusa per alta temperatura
Port Closed at upper temperature
Porta C - Chiusa per bassa temperatura
Port Closed at lower temperature
Porta A - Sempre aperta
Port Always open
Porta B - Chiusa per bassa temperatura
Port Closed at lower temperature
Porta C - Chiusa per alta temperatura
Port Closed at upper temperature
Porta A - Sempre aperta
Port Always open
Porta B - Sempre aperta
Port Always open
Porta C - Chiusa per bassa temperatura
Port Closed at lower temperature
Porta A - Chiusa per alta temperatura
Port Closed at upper temperature
Valvole illustrate nella posizione di fluido freddo Valves illestrated in “Cold Position”
3.3 Valve installation
Model RSW, RSO valves need no support except that provided
by connecting pipes. Pipework should not be subjected to
excessive bending. Line up pipework before tightening the valve
flange bolts. If the valve is mounted in a high point in the system,
the system should be properly vented to prevent trapping air in
the valve housing. Allow sufficient space above, below and around
valve for easy removal of parts during maintenance.
Before installing the control valve
- Blow or flush out pipe lines
- Use a self-cleaning strainer to protect control valve and allied equipment
- Install stop valves in inlet and outlet lines so that control valve
may be isolated when maintenance is to be performed
- By-passes should be installed around valve if service is critical
and system cannot be shut down during needed maintenance
- Install the valve with self-centering flat ring gaskets and DIN
flanges. Use either Class flanges, as designated on the valve
data plate. Before installation, remove foreign material such
as weld spatter, oil, grease, and dirt from the valve, flanges
and pipeline.
- Close the valve, align the pipeline on all sides of the valve and
ensure that the flanges, gaskets and valve are centered before
tightening the flanges bolts or studs. Tighten the bolts or studs
evenly, in a crisscross pattern.
- Manually rotate the valve. As the rotor rotates a variable orifice
is formed with the circular seat in the body. The valve actuator
is connected to the valve shaft, and positions the plug at the
open, closed, and intermediate positions.
- The open and closed positions are determined by the actuator.
Refer to the Actuator Instructions for adjusting the open position
stop. A line is stamped on the top of the valve stem to indicate
the angular position of the plug when the plug is not visible.
Refer to the top view of the shaft (see fig. 16).
Note that motor is set in the factory and normally there is no
need for field calibration.
3.3 Installazione valvola
Le valvole RSW, RSO non necessitano di specifici supporti ad
eccezione di quelli forniti dalle tubazioni di linea. Le tubazioni
non devono presentare curve eccessive. Allineare le tubazioni
alla valvola prima di stringere i bulloni delle flange. Se la valvola
viene montata in un punto alto del sistema occorre avere un si-
stema di sfiati per evitare l’accumulo di aria nella valvola. Fare in
modo che ci sia spazio sufficiente sopra, sotto ed intorno alla
valvola per facilitare le operazioni di manutenzione.
Prima di installare la valvola
- Soffiare le tubazioni
- Utilizzare un filtro sulla linea per proteggere la valvola
- Installare delle valvole manuali per isolare la valvola in caso di
manutenzione
- Se il processo è critico installare una valvola di by-pass per
consentire il funzionamento del sistema anche durante la ma-
nutenzione
- Installare la valvola sulla tubazione dopo aver montato e cen-
trato le guarnizioni tra le flangie della valvola e quelle analo-
ghe delle tubazioni. Rimuovere materiale estraneo quali resi-
dui di saldatura, oli, grassi e sporcizia in genere dalle tubazio-
ni, valvola, flange etc.
- Chiudere la valvola, allineare le tubazioni sui tre lati della val-
vola, ed assicurarsi che flange, guarnizioni e valvola siano
centrati prima di stringere i dadi. Stringere in modo incrociato
con una coppia come indicato a pag. 25 (fig. 21).
- Ruotare manualmente la valvola per verificare la sua funzio-
nalità nelle varie posizioni di aperto, chiuso e posizioni inter-
medie
- Le posizioni di apertura e chiusura sono determinate
dall’attuatore. Riferirsi al manuale dell’attuatore (SG) per tarare
i fine corsa. Sull’albero della valvola è stampigliata la lettera P
in corrispondenza della posizione del rotore in modo da identi-
ficare sempre la posizione del rotore anche quando non è più
visibile (vedere fig. 16)
Normalmente il motore è tarato in fabbrica e non è necessario
l’intervento in campo.
P
Riferimento per la posizione otturatore
Riference engraved for the trim position
Fig.