
13
1.7 FE 7 remote control
26_03_01_0107
With the FE 7 remote control, the following
options are available:
– changing the set room temperature for
heating for heating circuit 1 or 2 by ± 5 °C.
– changing the operating mode.
It offers the following controls:
one rotary selector for changing the set
room temperature
one rotary selector with the following
positions
Automatic mode
Constant setback mode
Constant day mode
The remote control is only active when
the LZM ll is in automatic mode.
1.9 What to do if . . . ?
. . . the fan symbol flashes on the
display:
Clean the extract filter, as described in section
1.8
. . no hot water is available:
Should you fail to obtain hot water at any
time, you can take the following steps to
remedy that situation.
No electrical power:
Check the fuse/circuit breaker in your fuse box.
If it has blown/tripped, replace/reset the fuse/
MCB. Notify your local contractor if the fuse/
MCB blows/trips again.
Despite electrical power:
Check, whether the air inlet/outlet is blocked.
. . . the safety valve of the cold water supply
line drips:
This may occur during the heat-up phase and
is completely normal as water expands when
heated.
. . . the pumps start briefly outside the heating
period:
An automatic pump start (10 s) is
programmed, to prevent the pumps from
seizing up outside the heating periods.
... the red indicator in the fascia illuminates:
In this situation the safety pressure limiter
has responded and may only be reset by your
contractor.
After a heat pump has been switched OFF, a
fixed residual idle time of 20 minutes is set
to protect the compressor. The heat pump
restarts automatically at the end of the idle
time.
Always notify your local contractor in
case of any other faults.
1.8 Maintenance and cleaning
Maintenance work, e.g. checking the
electrical safety, must only be carried
out by qualified personnel.
Protect the equipment from dust and dirt
ingress during building work.
A damp cloth is sufficient for cleaning all
plastic parts. Never use scouring or solvent-
based cleaning agents.
Keep the air inlet and outlet
apertures in the outside walls free
from snow and leaves.
A contractor should check and possibly clean
the evaporator and fan at least once a year.
Condensate drain
Check the condensate drain at least once every
month. Remove dirt and blockages.
External wall valves
Regularly check, clean and, if required, replace
the filters in the external wall valves.
Replace the filter elements at least annually.
Cleaning the extract air filters
Switch the ventilation system OFF before
26_03_01_0109
opening the filter cassette.
The LZM II contains a filter cleaning indicator
that automatically reminds users every 3
months to clean the filters. This is indicated by
a flashing fan symbol on the display.
The display can be reset at the control level
2 under parameter VENTILATION under
Filter reset by pressing PRG and setting the
system to ON and repeatedly pressing PRG.
The controller switches automatically over to
standby mode if no reset has been carried out
after 7 days.
A
The filter retainer can only be withdrawn to-
wards the front. This enables you to pull out
the filter and check it for contamination.
Replace the filter if it is heavily soiled (solid
layer of dust on the top of the filter mat). Clean
the filter with a vacuum cleaner, if it is only
lightly soiled. The filter cannot be washed.
Washing would mat the fabric, leaving too lit-
tle air to flow through the filter. After inserting
the filter, refit the cover.
When inserting the filter ensure that the solid,
fine-pored side is turned towards the r.h. side,
i.e. towards the evaporator.
Never adjust the ventilation and extract air
valves inside the rooms. These have been
adjusted during commissioning.
All other work on the equipment
must only be carried out by qualified
contractors. Never adjust the ventilation and
extract air valves inside the rooms. These
have been adjusted during commissioning.
Never make any modifications to the inter-
nal equipment electrics or controls.