9
Chilled Water
24” Chilled Water
CRS-180-C
Total Capacity Sensible Capacity Flow Rate
GPM
Total System
Pressure Drop,
Ft. H2O
BTU/H kW BTU/H kW
100˚FDB/ 69.2˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 263,192 77.1 250,429 73.3 54.5 39.4
12˚F ∆T 251,539 73.7 245,539 71.9 43.5 26.8
45˚F EWT 10˚F ∆T 219,854 64.4 219,854 64.4 45.9 29.2
12˚F ∆T 211,927 62.1 211,927 62.1 37.0 20.2
50˚F EWT 10˚F ∆T 192,259 56.3 192,259 56.3 40.5 23.4
12˚F ∆T 186,556 54.6 186,556 54.6 32.8 16.5
95˚FDB/67.7˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 242,729 71.1 227,717 66.7 50.5 34.8
12˚F ∆T 230,726 67.6 222,663 65.2 40.1 23.3
45˚F EWT 10˚F ∆T 199,089 58.3 199,089 58.3 41.8 24.9
12˚F ∆T 190,287 55.7 190,287 55.7 33.4 17.0
50˚F EWT 10˚F ∆T 170,772 50.0 170,772 50.0 36.2 19.4
12˚F ∆T 164,228 48.1 164,228 48.1 29.0 13.4
90˚FDB/66.1˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 221,108 64.7 204,623 59.9 46.2 29.8
12˚F ∆T 207,922 60.9 199,053 58.3 36.2 19.6
45˚F EWT 10˚F ∆T 177,357 51.9 177,357 51.9 37.4 20.3
12˚F ∆T 167,355 49.0 167,355 49.0 29.5 14.0
50˚F EWT 10˚F ∆T 148,407 43.5 148,407 43.5 31.6 15.4
12˚F ∆T 141,408 41.4 141,408 41.4 25.2 10.8
85˚FDB/64.5˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 199,491 58.4 180,880 53.0 41.8 25.0
12˚F ∆T 184,737 54.1 174,604 51.1 32.4 16.3
45˚F EWT 10˚F ∆T 154,771 45.3 154,771 45.3 32.9 16.7
12˚F ∆T 144,039 42.2 144,039 42.2 25.6 11.1
50˚F EWT 10˚F ∆T 125,357 36.7 125,357 36.7 27.0 12.1
12˚F ∆T 117,882 34.5 117,882 34.5 21.3 8.5
80˚FDB/62.8˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 176,442 51.7 156,565 45.8 37.2 20.6
12˚F ∆T 159,804 46.8 149,444 43.8 28.2 13.0
45˚F EWT 10˚F ∆T 130,953 38.3 130,953 38.3 28.2 12.9
12˚F ∆T 119,742 35.1 119,742 35.1 21.6 8.7
50˚F EWT 10˚F ∆T 101,625 29.8 101,625 29.5 22.3 9.0
12˚F ∆T 93,093 27.3 93,093 27.3 17.1 6.3
PERFORMANCE DATA