Stulz CyberRow CRS-090-C Installation and operation manual

1
STULZ CyberRow
®
Engineering Manual
Engineering Manual
EM
13-77 kW
Chilled Water
Row-Based Data Center Cooling
Utilizing EC Fan Technology
(60 Hz Data)
Indoor Cooling
Row

STULZ
Our Mission
STULZ mission is to be the premier provider of energy efficient temperature and humidity control
solutions for mission critical applications.
STULZ is dedicated to providing innovative solutions for critical temperature and humidity control
needs. STULZ designs and manufactures specialized, energy efficient, environmental control
equipment. STULZ serves a diverse marketplace; our customers represent a variety of industries
including telecommunications, information technology, medical, financial, educational, industrial
process and government. Our world-class “island” manufacturing processes takes place in a
modern, 150,000 ft2facility located in Frederick, MD USA. STULZ combines a global network of sales and service companies
with an extensive factory engineering staff and highly flexible manufacturing resources dedicated to providing world-class quality,
innovation and customer service.
This commitment to excellence, along with a standard two year warranty, fast lead times, and outstanding customer service,
make STULZ the perfect choice for all your environmental control needs.
ISO-9001 Quality Registered
STULZ is committed to satisfying customer expectations by meeting and exceeding requirements. Our Quality Policy ensures that
every Employee is committed to Customer Satisfaction, Teamwork and utilizing Continuous Process Improvement methods in
order to deliver an exceptional product. We will continually measure our performance to improve the effectiveness of our quality
management system.
STULZ CyberRow®
Designed for scalability, reliability, and seamless integration into new or existing data centers; STULZ CyberRow® rack cooling
systems are suitable for use in open and contained hot-aisle and cold-aisle configurations. STULZ CyberRow® is ideal for hot
spot cooling in small to enterprise size data centers.
Typical applications include:
• Internet/Web Hosting
• Telecommunications
• Financial/Banking
• Insurance
• Airlines/Mass Transit
• Legal Services
• Entertainment
• Government
• Colleges/Universities
• Data Centers
•
Computer/LAN Rooms
• Telecommunications Rooms
• Co-location Centers
• ISP (Internet Service Providers)
• ASP (Applications Service Providers)
• Hospital Operating & Isolation Rooms
2

Table of Contents
Model Nomenclature .............................................4
CyberRow® Features.............................................5
Configurations .......................................................6
Technical Data ........................................................7
Performance Data ..................................................8
Electrical and Sound Data ...................................10
Dimensional Data.................................................11
Standard Product Features..................................13
Product Guide Specifications ..............................14
Chilled Water
TABLE OF CONTENTS
3

4
MODEL NOMENCLATURE
CyberRow® Row-Based System
Nominal Capacity in 1,000 of BTU/H
CyberRow System
Chilled Water System
CRS-180-C
CyberRow®

5
FEATURES
CyberRow® Chilled Water (C)
Chilled water (C) is supplied to the CyberRow® unit via building chiller or other chilled water plant. Chilled water has
high affinity for heat, thus making it a very efficient cooling method. Stulz E² controller allows for independent valve
and fan control so the unit can adjust immediately and precisely, to varying heat loads and optimize energy efficiency.
Features
• Highest cooling capacities in the industry
• 12" and 24" cabinet widths
• 3 EC fans: Independently and infinitely adjustable EC fans
ensure maximum efficiency
• Used in containment, open architecture, and hot spot
reduction applications
• Adapts to both high and low density IT environments
• Wide range of cooling capacities available
• 100% front and rear service access
• Adapts to all major manufacturers racks and rack
containment systems
• Seamless integration with all BMS platforms
• pLAN link to 8 units without a BMS
• High air flow with less noise
• Built in redundancy and capacity assist functions
• 2-Way or 3-Way control valves
• Top and bottom piping options
• Casters and Leveling Feet included
• Indoor use only
• Installation on raised and non-raised floors
Traditional
Hybrid Free Cooling
Chilled Water

6
Open aisle configuration organizes racks in a single row
or in hot and cold aisle rows, but without containment.
The Stulz CyberRow® draws hot air from the external
environment or hot aisle, removes the heat, and supplies
cooled air to the front of IT equipment in the cold aisle.
Hot aisle containment captures the hot exhaust air from
IT equipment and prevents from mixing with cool air. The
front of IT equipment is accessed in the external cold
aisle. The Stulz CyberRow® draws the contained hot air
from the hot aisle, removes the heat, and supplies cooled
air into the external cold aisle.
Cold aisle containment captures cooled air from the
Stulz CyberRow® and prevents it from mixing with hot
air. The front of IT equipment is accessed in the contained
cold aisle. The Stulz CyberRow® draws hot air from the
external environment, removes the heat, and supplies
cooled air back into the contained cold aisle.
CONFIGURATIONS
CyberRow®

7
TECHNICAL DATA
Chilled Water
Model 12” Chilled Water 24” Chilled Water
CRS-090-C CRS-180-C
Chilled Water Control Valve
2-way (standard) - Modulating
Valve Pressure Rating - psi 400 400
Close-off Pressure Rating - psi 200 200
3-way (optional) - Modulating
Valve Pressure Rating - psi 400 400
Close-off Pressure Rating - psi 200 200
Chilled Water Coil - Aluminum Fin, Copper Tube
Rows/Face Area (ft2) 4 / 5.8 4 / 11.6
Face Velocity, fpm 500 500
Blower/Motor - Backward Curved Direct Driven EC
Horsepower (Each) 1/4 H.P. 1-1/4 H.P.
CFM 2,900* 5,800
Quantity of Blowers 3 3
Drive Method Direct Direct
Humidification: Electrode Steam Canister Humidifier with Adjustable Output (Optional)
Lbs/Hr. (kW Input) N/A 5 (1.7)
Std Control N/A Proportional
Washable Filters
Nom. Size (in.), (Qty.) 10.5 x 37.38 x .43 (2) 22.0 x 37.38 x .43 (2)
Connection Sizes (Copper)
Condensate Drain, (w/ pump) 1/2” FPT 1/2” FPT
Humidifier Inlet N/A 1/4” OD
Water In/Out 1-1/4” NPT 1-1/2” NPT
Physical Data
Approx. Weight (Lbs) 384 550
Dimensions: (H”xW”xD”) 78.5” x 11.6” x 42.1” 78.5” x 23.4” x 42.1”
Approx. Shipping Weight (lbs) 570 711
Approx. Shipping Dimensions (H”xW”xD”) 84” x 22” x 48” 84” x 32” x 48”
(*Note: When 110v/1Ph/60Hz Power Input is selected, unit airflow is decreased by 200 CFM, which will result in capacity
reduction of 3.5% or less.)

8
PERFORMANCE DATA
12” Chilled Water
CRS-090-C
Total Capacity Sensible Capacity Flow Rate
GPM
Total System
Pressure Drop,
Ft. H2O
BTU/H kW BTU/H kW
100˚FDB/ 69.2˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 127,008 37.2 125,200 36.7 25.7 18.0
12˚F ∆T 119,461 35.0 119,461 35.0 20.2 12.2
45˚F EWT 10˚F ∆T 107,333 31.4 107,333 31.4 21.8 13.7
12˚F ∆T 102,855 30.1 102,855 30.1 17.4 9.6
50˚F EWT 10˚F ∆T 95,717 28.0 95,717 28.0 19.5 11.4
12˚F ∆T 91,561 26.8 91,561 26.8 15.5 8.0
95˚FDB/67.7˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 116,107 34.0 113,554 33.2 23.5 15.5
12˚F ∆T 108,271 31.7 108,271 31.7 18.3 10.5
45˚F EWT 10˚F ∆T 96,465 28.2 96,465 28.2 19.6 11.6
12˚F ∆T 91,834 26.9 91,834 26.9 15.6 8.2
50˚F EWT 10˚F ∆T 84,669 24.8 84,669 24.8 17.3 9.5
12˚F ∆T 80,417 23.5 80,417 23.5 13.7 6.8
90˚FDB/66.1˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 108,988 31.9 108,988 31.9 22.1 14.0
12˚F ∆T 103,324 30.3 103,324 30.3 17.5 9.7
45˚F EWT 10˚F ∆T 96,139 28.2 96,139 28.2 19.5 11.5
12˚F ∆T 91,959 26.9 91,959 26.9 15.6 8.2
50˚F EWT 10˚F ∆T 84,788 24.8 84,788 24.8 17.3 9.5
12˚F ∆T 80,524 23.6 80,524 23.6 13.7 6.8
85˚FDB/64.5˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 93,105 27.3 89,517 26.2 18.9 11.0
12˚F ∆T 84,791 24.8 84,791 24.8 14.4 7.4
45˚F EWT 10˚F ∆T 73,674 21.6 73,674 21.6 15.0 7.8
12˚F ∆T 68,684 20.1 68,684 20.1 11.7 5.6
50˚F EWT 10˚F ∆T 61,689 18.1 61,689 18.1 12.7 6.2
12˚F ∆T 56,942 16.7 56,942 16.7 9.8 4.6
80˚FDB/62.8˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 81,155 23.8 77,151 22.6 16.6 9.0
12˚F ∆T 72,250 21.2 72,250 21.2 12.3 6.0
45˚F EWT 10˚F ∆T 61,703 18.1 61,703 18.1 12.6 6.2
12˚F ∆T 56,587 16.6 56,587 16.6 9.7 4.5
50˚F EWT 10˚F ∆T 49,488 14.5 49,488 14.5 10.2 4.8
12˚F ∆T 44,393 13.0 44,393 13.0 7.7 3.7
CyberRow®

9
Chilled Water
24” Chilled Water
CRS-180-C
Total Capacity Sensible Capacity Flow Rate
GPM
Total System
Pressure Drop,
Ft. H2O
BTU/H kW BTU/H kW
100˚FDB/ 69.2˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 263,192 77.1 250,429 73.3 54.5 39.4
12˚F ∆T 251,539 73.7 245,539 71.9 43.5 26.8
45˚F EWT 10˚F ∆T 219,854 64.4 219,854 64.4 45.9 29.2
12˚F ∆T 211,927 62.1 211,927 62.1 37.0 20.2
50˚F EWT 10˚F ∆T 192,259 56.3 192,259 56.3 40.5 23.4
12˚F ∆T 186,556 54.6 186,556 54.6 32.8 16.5
95˚FDB/67.7˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 242,729 71.1 227,717 66.7 50.5 34.8
12˚F ∆T 230,726 67.6 222,663 65.2 40.1 23.3
45˚F EWT 10˚F ∆T 199,089 58.3 199,089 58.3 41.8 24.9
12˚F ∆T 190,287 55.7 190,287 55.7 33.4 17.0
50˚F EWT 10˚F ∆T 170,772 50.0 170,772 50.0 36.2 19.4
12˚F ∆T 164,228 48.1 164,228 48.1 29.0 13.4
90˚FDB/66.1˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 221,108 64.7 204,623 59.9 46.2 29.8
12˚F ∆T 207,922 60.9 199,053 58.3 36.2 19.6
45˚F EWT 10˚F ∆T 177,357 51.9 177,357 51.9 37.4 20.3
12˚F ∆T 167,355 49.0 167,355 49.0 29.5 14.0
50˚F EWT 10˚F ∆T 148,407 43.5 148,407 43.5 31.6 15.4
12˚F ∆T 141,408 41.4 141,408 41.4 25.2 10.8
85˚FDB/64.5˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 199,491 58.4 180,880 53.0 41.8 25.0
12˚F ∆T 184,737 54.1 174,604 51.1 32.4 16.3
45˚F EWT 10˚F ∆T 154,771 45.3 154,771 45.3 32.9 16.7
12˚F ∆T 144,039 42.2 144,039 42.2 25.6 11.1
50˚F EWT 10˚F ∆T 125,357 36.7 125,357 36.7 27.0 12.1
12˚F ∆T 117,882 34.5 117,882 34.5 21.3 8.5
80˚FDB/62.8˚FWB Entering Air Temperature
40˚F EWT 10˚F ∆T 176,442 51.7 156,565 45.8 37.2 20.6
12˚F ∆T 159,804 46.8 149,444 43.8 28.2 13.0
45˚F EWT 10˚F ∆T 130,953 38.3 130,953 38.3 28.2 12.9
12˚F ∆T 119,742 35.1 119,742 35.1 21.6 8.7
50˚F EWT 10˚F ∆T 101,625 29.8 101,625 29.5 22.3 9.0
12˚F ∆T 93,093 27.3 93,093 27.3 17.1 6.3
PERFORMANCE DATA

10
(Note: All sound testing is performed in accordance to ISO 9614-2 Determination of Sound Power Levels.
ISO 9614-2 Specifies a method for measuring the component of sound intensity normal to a measurement
surface which is chosen so as to enclose the noise source(s) of which the sound power level is to be deter-
mined.)
Sound Data CRS-090-C
Sound Pressure
LpA, free field (dBA) in a 121.13 ft² (3.43m³) room at
3.28 (1.0m) distance
Fan
Speed %
Airflow
(SCFM)
63 125 250 500 1000 2000 4000 8000 Total
dBA
NR
Value
50% 1800 15.8 19.7 31.3 35.0 38.8 35.1 25.3 10.9 42.0 39
75% 2150 13.1 41.6 42.7 45.2 48.1 46.2 38.5 23.4 52.6 48
100% 2900 19.6 47.2 49.8 51.4 53.6 51.7 45.0 30.6 58.4 54
Fan
Speed %
Airflow
(SCFM)
CRS-180-C
Sound Pressure
LpA, free field (dBA) in a 146.91 ft² (4.16m³) room at
3.28 ft (1.0m) distance
50% 4100 29.4 42.5 46.6 48.6 52.3 52.5 41.5 26.1 57.0 54
75% 5000 34.9 49.7 57.3 59.7 62.8 60.5 56.0 40.3 67.0 63
100% 5800 43.0 52.6 61.5 64.0 67.0 64.2 59.6 45.8 71.1 67
(Note: Standard 1 KAIC rating, optional 65 KAIC rating available.)
Electrical
Data
CRS-090-C CRS-180-C
FLA MCA MFS FLA MCA MFS
COOLING ONLY
120/1/60 8.3 10.4 15 N/A N/A N/A
208/1/60 5 6.2 15 N/A N/A N/A
208/3/60 5 6.2 15 9.3 11.6 15
460/3/60 2.5 3.2 15 4.5 5.6 15
575/3/60 2.1 2.7 15 3.7 4.6 15
COOLING AND HUMIDIFIER
120/1/60 N/A N/A N/A N/A N/A N/A
208/1/60 N/A N/A N/A N/A N/A N/A
208/3/60 N/A N/A N/A 18.5 23.2 25
460/3/60 N/A N/A N/A 8.7 10.9 15
575/3/60 N/A N/A N/A 7.1 8.9 15
ELECTRICAL AND SOUND DATA
CyberRow®

11
DIMENSIONAL DATA
CRS-090-C Chilled Water
Top Piping Option Bottom Piping Option
11.6"
77.8"
42.1"
CONDENSATE
CONNECTION
PIPING
CONNECTION
POWER
CONNECTION
AIR OUT
AIR IN
CONDENSATE
CONNECTION
PIPING
CONNECTION
POWER
CONNECTION
AIR OUT
AIR OUT
AIR IN
AIR IN
POWER
POWER
CONNECTIONS
CONNECTIONS
PIPING
PIPING
CONNECTIONS
CONNECTIONS
CONDENSATE
CONDENSATE
CONNECTION
CONNECTION
POWER
POWER
CONNECTIONS
CONNECTIONS
PIPING
PIPING
CONNECTIONS
CONNECTIONS
CONDENSATE
CONDENSATE
CONNECTION
CONNECTION
11.6"
11.6"
77.8"
77.8"
42.1"
42.1"
Side Diverted Front Panel Option
11.6"
77.8"
48.3"
11.6"
11.6"
77.8"
77.8"
48.3"
48.3"

12
DIMENSIONAL DATA
CRS-180-CCyberRow®
23.4"
77.8"
42.1"
AIR IN
AIR OUT
CONDENSATE
CONNECTION
PIPING
CONNECTIONS
POWER
CONNECTIONS
HUMIDIFIER
CONNECTIONS
CONDENSATE
CONNECTION
HUMIDIFIER
CONNECTIONS
POWER
CONNECTIONS
PIPING
CONNECTIONS
Top Piping Option Bottom Piping Option
Side Diverted Front Panel Option
HUMIDIFIER
HUMIDIFIER
CONNECTIONS
CONNECTIONS
POWER
POWER
CONNECTIONS
CONNECTIONS
PIPING
PIPING
CONNECTIONS
CONNECTIONS
CONDENSATE
CONDENSATE
CONNECTION
CONNECTION
AIR IN
AIR IN
AIR OUT
AIR OUT
PIPING
PIPING
CONNECTIONS
CONNECTIONS
POWER
POWER
CONNECTIONS
CONNECTIONS
HUMIDIFIER
HUMIDIFIER
CONNECTIONS
CONNECTIONS
CONDENSATE
CONDENSATE
CONNECTION
CONNECTION
23.42
77.80
48.30
42.1"
42.1"
23.4
23.4
77.8
77.8
48.3
48.3
23.4"
23.4"
77.8"
77.8"
48.3"
48.3"
23.4"
23.4"
77.8"
77.8"
42.1"
42.1"

13
STANDARD PRODUCT FEATURES
MODEL CRS-090-C CRS-180-C PAGE
CABINET 14
Galvannealed Steel, Black Powder Coated Finish Standard Standard
AIR PATTERN AND FILTRATION 14
Front Discharge Standard Standard
Front Diverted Plenum Discharge Optional Optional
Permanent Washable Filters Standard Standard
MECHANICAL COMPONENTS 14
Backward Inclined, Plenum Style Fan, with an EC Motor Standard Standard
Chilled Water Cooling Coil Standard Standard
Piping Configuration (Top, or Bottom) Selectable*Selectable*
Condensate Pump Standard Standard
2-Way Modulating Chilled Water Control Valve Standard Standard
3-Way Modulating Chilled Water Control Valve Optional Optional
Electrode Steam Canister Humidifier N/A Optional
ELECTRICAL SYSTEM 16
Automatic Dual Power Transfer Switch Optional Optional
Remote Stop/Start Contacts Standard Standard
Main Power Switch Standard Standard
E² MICROPROCESSOR CONTROLLER 16
A/C Grouping pLAN Interface Optional Optional
BMS Interface Optional Optional
Common Alarm, Dry Contact Standard Standard
OPTIONAL ACCESSORIES 17
Mechanical Flow Switch Optional Optional
Differential Temperature Flow Optional Optional
Smoke Detection Optional Optional
Firestat Optional Optional
Remote Water Detector Optional Optional
CODE CONFORMANCE 18
ETL Conformance Compliance to UL 1995 Standard Standard Standard
CAN/CSA C22.2 No. 236 Standard Standard
STANDARD PRODUCT FEATURES
(*Note: Piping connection location to be specified at time of order.)
Chilled Water

CABINET
Side access panels shall be fabricated from 20 gauge
galvannealed steel and shall be securely bolted to a 14
gauge base and the top plate. The top plate, front and rear
panels shall be fabricated from 16 gauge galvannealed
steel. The cabinet shall be powder coated with a satin
black finish to provide durability, and to protect from
corrosion. Armaflex elastomeric thermal insulation shall
be used to insulate the cabinet, block noise and prevent
damage from vibration. Casters and leveling feet shall be
included to ease the installation and level the equipment
with existing IT solutions.
AIRFLOW PATTERNS
All units shall be designed using a front discharge with
a rear return airflow pattern. An optional plenum with a
front diverted discharge pattern is available.
AIR FILTRATION
All units shall be equipped with removable, washable
filters. These filters shall consist of an open cell structured
polyurethane foam with a roll formed 3000 series
aluminum frame. Filters shall meet both UL 900 and UL
94 HF-1 standards.
MECHANICAL COMPONENTS
BACKWARD INCLINED, PLENUM STYLE FAN,
WITH AN EC MOTOR
The blowers shall be backward inclined plenum style
fans with an Electronically Commutated (EC) motor,
for maintenance free operation. The motor shall
include: integrated electronic control board and direct
microprocessor control signaling for fan speed control,
soft-starting capabilities, and integrated current limitations.
Each fan shall be low noise, low vibration manufactured
with an anti-corrosive aluminum impeller. Each fan
impeller shall be dynamically and statically balanced in two
planes to minimize vibration during operation.
CHILLED WATER COOLING COIL
The coil shall be constructed of seamless drawn copper
tubes, mechanically bonded to tempered aluminum fins
with enhanced fin design for maximum heat transfer, and
STULZ CyberRow®
13 - 77 kW Row-Based
Precision Control Air Conditioners Chilled
Water Systems
SUMMARY
This specification describes requirements for a precision
environmental control system. The STULZ CyberRow® is
a row-based cooling system that shall provide precision
temperature control (and humidity control for the
24” model) for computer rooms or rooms containing
telecommunications or other highly sensitive heat load
equipment where continuous 24 hour a day, 365 days a
year air conditioning is required.
Designed with both front and rear access, CyberRow®
systems require minimum floor space. The supplied system
shall be provided with ETL Certification. The CyberRow®
model number shall be, CRS- - .
DESIGN REQUIREMENTS
The environmental control system shall be a STULZ
CyberRow® Chilled Water factory-assembled unit. The
unit shall be designed for a row-based installation with
removable front and rear access panels. No allowance for
side service access shall be required, however removable
side access panels shall be provided for additional access.
The CyberRow® units are especially adapted for both
raised and unraised floors. The air handling section shall
be specifically designed for high sensible heat ratio. Each
system shall be capable of handling CFM at inches
of water external static pressure. The unit shall have the
cooling capacity of BTU/H, and the sensible cooling
capacity of BTU/H based on entering air condition of
°F dry bulb and °F (°C) wet bulb. The humidifier (only
available in the 24” unit) shall have the capacity of 5 Lbs/hr.
The main fan motors shall be HP. The unit shall have a
power supply of volts.
QUALITY ASSURANCE
The manufacture shall maintain a set of international
standards of quality management to insure product quality.
Each system shall be subjected to a complete operational
and functional test procedure at the factory prior to
shipment.
14
PRODUCT GUIDE SPECIFICATIONS
CyberRow®

The humidifier assembly shall include integral fill cup, fill
and drain valves and associated piping.
The canister shall be designed to collect the mineral
deposits in the water and provide clean particle free steam
to the air stream, thereby reducing maintenance cost.
The microprocessor control shall maintain humidifier
operation through fill and drain cycles based on the water
conductivity. Overflow and loss of flow protection shall be
provided along with a manual drain switch. A high water
alarm with built-in time delay shall provide an indication
to change canister. The humidification system shall require
no cleaning maintenance during the cylinder life.
The humidifier shall discharge steam at 212 degrees F.
and atmospheric pressure. It shall be capable of operating
with water in the range of 200 to 1500 micromhos. The
steam shall be introduced into the air stream, after the
evaporator, by a calibrated discharge tube designed to
equally distribute the steam to the air stream without
condensation. The humidifier shall have a capacity of 5
Lbs/hr.
A factory wired and installed humidifier drain pump shall
be installed. This pump is designed to operate with the
higher condensate temperatures caused by the flush
and drain cycle of the electrode canister humidifiers.
The humidifier drain line will be connected to the main
condensate line prior to exiting the cabinet.
DEHUMIDIFICATION CYCLE
The CyberRow® unit shall be provided with a
dehumidification control mode. During dehumidification
demand, the control mode shall permit chilled water
valve operation and EC motor speed control to condense
moisture on the cooling coil.
ELECTRICAL SYSTEM
The electrical system shall conform to National Electrical
Code (NEC) requirements. In accordance with NEC Class II
circuits, the control circuit shall be 24 volts AC and control
circuit wiring shall not be smaller than 18 AWG. All wiring
shall be neatly wrapped, run in conduit or cable trays, and
routed in bundles. Each wire shall end with a service loop
and be securely fastened by an approved method. Each
wire in the unit shall be numbered for ease of service
tracing.
All electrically actuated components shall be easily
accessible from the front and rear of the unit without
reaching over exposed high voltage components or
15
Chilled Water
mounted in a stainless steel condensate drain pan. The
coil shall be designed for a maximum of 500 ft./min. face
velocity. The water circuit shall be designed to distribute
water into the entire coil face area.
PIPING CONFIGURATION
Top Piping: When top piping is specified, the CyberRow®
units shall be provided with connections for both the
chilled water piping and condensate discharge on the top
of the cabinet.
Bottom Piping: When bottom piping is specified (e.g.
raised floor applications), the CyberRow® units shall be
provided with connections for both chilled water piping
and condensate pump discharge on the bottom of the
cabinet.
CONDENSATE PUMP
The CyberRow® shall include a factory wired and installed
in-pan condensate pump. The condensate pump shall
have the capacity of 3 gal/hr. at 3 ft. of lift with a maximum
shut off (head) of 40 ft. The condensate pump shall be
piped with either top or bottom discharge connections to
remain consistent with top or bottom chilled water piping
connections.
2-WAY (STANDARD)
A 2-way modulating valve rated for a maximum 400 psig
w.w.p. shall be factory piped and wired. The 2-way chilled
water modulating valve shall automatically meter the
flow of chilled water to the cooling coil in response to a
proportional signal (0-10 VDC) provided to the valve by the
microprocessor controller w.w.p.
3-WAY (OPTIONAL)
The water circuit shall include a factory mounted, 3-way
modulating (0 - 10 VDC) control valve. Design pressure
shall be 400 psig.
STEAM GENERATING HUMIDIFIER
(OPTIONAL FOR 24” CABINET DESIGN)
The humidifier shall be of a self-contained steam generating
electrode type, utilizing a plastic disposable cylinder with
full probes, connected to electric power via cylinder plugs
that slide onto the electrode pins. The electrode pins shall
be constructed from expanded low carbon steel, zinc
plated, and dynamically formed for precise current control.
PRODUCT GUIDE SPECIFICATIONS

rotating parts. Each high voltage circuit shall be individually
protected by circuit breakers or manual motor starters on
all three phases. The blower motor shall have thermal and
short circuit protection. Line voltage and 24 volt control
circuit wiring shall be routed in separate bundles. The
electric box shall include all the contactors, starters, fuses,
circuit breakers and terminal boards required for operation
of the CyberRow® unit and shall allow for full service via
front and rear access panel.
AUTOMATIC DUAL POWER TRANSFER
SWITCH (OPTIONAL)
Two individual main power input disconnect switches shall
be provided, one for each incoming power source. In the
event the primary power fails or a phase loss/imbalance
occurs, the automatic transfer switch transfers power to the
secondary power source. Once the primary power has been
restored, the transfer switch automatically shifts the power
load back to the primary power. The transfer time from one
source to the other is user adjustable to allow staging or
sequence restart of load.
In addition to the automatic transfer switch function, the
local controller display shall indicate which power source
has failed. This indication is a visual depiction that allows
the user to determine the status of the input source.
This status can also be conveyed thru the BMS serial
communication link.
REMOTE STOP/START CONTACTS
Included in the system’s electrical control circuit shall be
a 2-pin terminal connection for remote stop/start of the
CyberRow® air conditioner by remote source.
MAIN POWER SERVICE SWITCH
The CyberRow unit shall be provided with a unit mounted
main power service switch.
16
E² SERIES CONTROLLER DESCRIPTION
GENERAL
The advanced microprocessor based E² Series controller
shall be equipped with flexible software capable of meeting
the specific needs of the application. The setpoints shall
be default and their ranges shall be easily viewed and
adjusted from the user interface display. The program and
operating parameters shall be permanently stored on a
non-volatile system in the event of power failure.
The controller shall be designed to manage temperature
and relative humidity (RH) levels to a user defined setpoint
via control output signals to the CyberRow® unit. Control
parameters have variable outputs from 0 to 100% of the
full rated capacity.
The controller shall receive inputs for measurable control
conditions (temperature, relative humidity, and dew point)
via return air or room mounted sensors. The internal logic
will then determine if the conditions require cooling,
humidification or dehumidification. Control setpoints
shall be established to maintain design conditions of
the installation. The controller will respond accordingly
to changes in these conditions and control the output/
demand for the appropriate mode of operation until user
defined conditions are achieved.
FIELD CONFIGURABLE
The program for the E² Series controller shall be field
configurable, allowing the operator the capability of
selecting control setpoints specific to the application.
Operator interface for the E² controller is provided
via a door mounted user interface display panel. The
display panel shall have a backlit LCD graphical display
and function keys giving the user complete control and
monitoring capability of the precision cooling system. The
menu driven interface shall provide users the ability to
scroll through and enter various menu screens.
PASSWORD PROTECTION
Access to the Info Menu, Alarms Log, and the ability to
monitor room conditions shall be allowed without the
use of a password. Modifications to the control setpoints
shall require the use of a password. The controller shall be
programmed to recognize predetermined security levels
before allowing access to display screens containing critical
variables. Three secured menu levels (Control, Service
and Factory) will support unique passwords that must be
PRODUCT GUIDE SPECIFICATIONS
CyberRow®

BMS INTERFACE
The E² series controller may incorporate a 10 Mbps
communication interface port that can be field connected
through a serial interface to a Building Management
System via Modbus, BACnet, SNMP, or HTTP as configured
by the factory. A controller interfaced to a network must
be configured for BMS communication.
ALARMS
Alarm conditions shall activate a red LED indicator that
backlights the alarm function key. As an option, an alarm
condition may also be enunciated by an audible alarm
signal. An alarm is acknowledged by pressing the alarm
key. This calls up alarm display screens that provide a text
message detailing the alarm conditions. After an alarm
condition is corrected, the alarm can be cleared by pressing
the alarm key.
SMALL BEZEL DISPLAY PANEL
The small bezel user interface display panel features an
easy to read, backlit liquid-crystal alphanumeric display
equipped with contrast adjustment and LED illuminated
function keys. The screens that appear on the user
interface display panel present data that originates from
the controller I/O module. The controller is operated via a
6-key menu-driven loop structure and offers an alarm log
plus four different interface menu levels to the operator:
Information, Control, Service, and Factory. These menus
permit the user to easily view, control, and configure
operating parameters for the CyberRow® unit.
OPTIONAL ACCESSORIES
MECHANICAL FLOW SWITCH (OPTIONAL)
A shipped loose flow switch shall activate a loss of flow
alarm in the event of chilled water flow interruption.
DIFFERENTIAL TEMPERATURE
FLOW (OPTIONAL)
A factory mounted and wired temperature sensor for inlet
and outlet water temperatures shall permit a loss of flow
alarm in the event the temperature difference is within 1°
F (adjustable) during chilled water valve operation.
17
Chilled Water
entered to access the menu screens so only authorized
personnel may perform modifications to the settings.
RESTORABLE PARAMETERS/FACTORY
DEFAULTS
Upon initial start-up the CyberRow® system shall operate
using the setpoints programmed by the factory. The
customer may enter new operating parameters in the
Control menu and the system will then operate accordingly.
The new setpoints may be stored as, "Customer Default
Setpoints". The primary setpoints entered by the factory
still remain stored in the controllers’ memory as, "Factory
Setpoints". The setpoints for the system may be re-
adjusted in the Control menu at any time. If it becomes
necessary, the customer may restore the setpoints back
to the Customer Default setpoint values or to the original
Factory (primary) setpoint values.
TIMER FEATURE
The timer shall allow the user to set up an operating
schedule to automatically scale back or shut down the air
conditioner during low demand or unoccupied periods.
This is an energy saving feature offering the user the ability
to create an operating schedule tailored to the needs of the
building. An evening (night-setback) schedule may also be
created, allowing the CyberRow® unit to operate at night
with relaxed temperature/humidity setpoints and offsets.
A/C GROUPING pLAN OPERATION
Multiple CyberRow® system controllers shall be able to be
connected (grouped) to a pLAN local network, allowing
the communication of data and information from each
controller to a central control terminal or Lead controller.
The Lead controller display screens can be used to monitor
and adjust group control variables for the individual system
controllers. Each E² controller connected to the pLAN
network shall be identified with its own unique address.
Multiple CyberRow® units consisting of up to eight
STULZ precision air conditioners equipped with like
controllers may be controlled and monitored via the E²
series controller. With multiple CyberRow® units each
unit can selectively be configured as “Active” to operate
as a primary A/C, “Capacity Assist” for staged operation,
or as “Standby” to come online in case of a failed air
conditioning unit to ensure continuous availability. The
controller may also be configured to rotate units with
timed duty cycling to promote equal run-time and assure
that each CyberRow® unit within the rotating group is
operationally exercised on a periodic timed basis.
PRODUCT GUIDE SPECIFICATIONS

SMOKE DETECTION
A photo-electric smoke detector shall be factory installed
and wired in the evaporator section of the suction side of
the evaporator blower. The air conditioner will shut down
upon sensing smoke in the return air stream.
FIRESTAT
The air conditioner shall be provided with a factory wired
and mounted firestat. The firestat will shut down the air
conditioner upon sensing a high return air temperature.
REMOTE WATER DETECTOR: SPOT TYPE
A remote single point water and leak detector shall
be factory supplied and shall ship separately for field
installation. Upon sensing a water leak, the normally closed
water detector control circuit shall open, thereby shutting
down the CyberRow® unit’s water producing components.
REMOTE WATER DETECTOR: STRIP TYPE
A 20 ft. long remote strip/cable type water and leak detector
shall be provided for remote field installation. Upon sensing
a water leak, the normally closed water detector control
circuit shall open, thereby shutting down the CyberRow®
unit’s water producing components.
CODE CONFORMANCE
The unit shall be designed and built to conform to UL STD
1995, certified to CAN/CSA C22.2 No. 236. and listed with
ETL.
18
PRODUCT GUIDE SPECIFICATIONS
CyberRow®

19
Chilled Water
NOTES

© Aug., 2013
QEWR001B
Specifications subject to change without notice.
ISO 9001 Quality Management System - Requirements
ISO9001
Registered
Quality System
STULZ Air Technology Systems, Inc.
1572 Tilco Drive, Frederick, Maryland 21704
Phone: 301.620.2033, Fax: 301.662.5487
E-mail: [email protected]
www.STULZ.com
®
STULZ mission is to be the premier provider of
energy efficient temperature and humidity control
solutions for mission critical applications.
Production Facilities: U.S.A. •Germany • Italy •China •India
This manual suits for next models
1
Table of contents
Other Stulz Computer Hardware manuals
Popular Computer Hardware manuals by other brands

Autocall
Autocall A100-3109 IDNet 2 installation instructions

Mellanox Technologies
Mellanox Technologies MCX4131A-BCAT user manual

RME Audio
RME Audio AEB4/8-1 user guide

Renesas
Renesas M3A-HS19G50 installation manual

ekwb
ekwb EK-FB ASUS R4BE Monoblock installation manual

Avalue Technology
Avalue Technology ECM-EHL3 user manual