Sub-Zero VAF433-T User manual

6Select number of poles.
7 Clear run hours.
Restore factory defaults
Error Messages
8
Index
Sr.
No. Description
Para.
1
3
4
5
Network selection either 3P-3W and 3P-4W.
Select PT secondary ratio.
Select PT primary ratio.
2
Select CT primary ratio.
Index
Sr.
No. Description
User Interface.
Technical Specification.
Parameter setting mode.
Para.
Home Page Screen Description
Home Page Screen Description
Automatic Mode / Manual Mode Settings :
Press A/M mode for 4 seconds to toggle between
Automatic/Manual Mode.
Note : By Default unit operates in automatic mode. In automatic
mode online pages scroll automatically at the rate of 5 sec per
page.In automatic mode if any key is pressed,unit temporarily
switched to manual mode and the appropriate page is displayed.
In Automatic Mode :
1st Screen Displays Line to Neutral voltage of all
3 Phase
2nd Screen Displays Line to Line voltage of all 3
Phase
3rd Screen rpm
4th Screen Displays current of all 3 Phase
5th Screen Displays Run Hours
6th Screen Displays Power Factor of Line to Line
Voltage.
7th Screen Displays Line to Neutral voltage, current
and frequency of first Phase
8th Screen Displays line to neutral voltage, current
and frequency of second Phase
10th Screen Displays average line to neutral voltage,
average current of three phase and
frequency.
11th Screen Displays average line to line voltage,
average current of three phases and
frequency of present phase.
9th Screen Displays line to neutral voltage, current
and frequency of third Phase
1. Display Descriptions in 3Ø – 4W :
Operating Manual
VAF433-T
Dimensions & Panel Cutout
Caution for your Safety
Maintenance: Cleaning: Clean the surface of the controller with a soft
moist cloth. Do not use abrasive detergents, petrol, alcohol or solvents.
WIRING: The probe and its corresponding wires should never be
installed in a conduit next to control or power supply lines. The electrical
wiring should be done as shown in the diagram. The power supply
circuit should be connected to a protection switch. The terminals admit
wires of upto 2.5sq mm.
WARNING: Improper wiring may cause irreparable damage and
personal injury. Kindly ensure that wiring is done by qualified personnel
only.
Notice: The information in this document is subject to change in order
to improve reliability , design or function without prior notice and does
not represent a commitment on the part of the company. In no event will
the company be liable for direct, indirect, special, incidental or
consequential damage arising out of the use or inability to use the
product or documentation, even if advised of the possibility of such
damages. No part of this manual may be reproduced or transmitted in
any form or by any means without the prior written permission of the
company.
Probe :To give a correct reading, the probe must be installed in a place
protected from thermal influences, which may affect the temperature to
be controlled.
Controller :Controller should be installed in a place protected by
vibration, water and corrosive gasses and where ambient temperature
does not exceed the values specified in the technical data.
Introduction
Connection Diagram
1 2 3456 7
11 12
S1 S2 N
8 9 10
VRVYVB
I1I2I3
L N
230V
S1 S2 S1 S2
18 19 20
VRVBVY
3P4W
3P3W
Technical Specification
Housing : Front Cover: Polycarbonate Plastic
Dimensions : Frontal : 96 X 96mm, Depth : 61mm
Operating humidity : 20% to 85% (non-condensing)
Measuring Range
: 19 to 865 V AC (L-L)
Input Rated Current
: Nominal 5A AC
PT Primary : 100 V to 500 kV
Connections : Terminal connectors.
< 2.5sq mm terminal only with U-type
Data storage : Non-volatile flash memory
Panel Cutout : 91 X 91mm
lugs.
Display : 3 X 17mm 7 segment White display,
Power Input : 240 Vac ±20 % , 50/60Hz Standard.
Operating temp. : 0°C to 60°C (non-condensing)
Storage temp : -25°C to 60°C (non-condensing)
Mounting : Flush panel mounting with Fasteners
Protection : IP65 Front
Back Cover: ABS Plastic
15 Iconic LEDs for Indication
Wiring Input : 3ø-4W, 3ø-3W system.
Input Rated Voltage : 5 11 to 00 V AC (L-N)
CT Primary : 5 A to 10 kA
CT Secondary
: 5 A
PT Secondary
: 100 to 500 V AC (L-L)
Electrical Connection
: 3ø-4W, 3ø-3W, 2ø-3W, 1ø-2W.
Resolution
Current / Voltage : Resolution depends upon CT,
PT Primary settings
RPM : 0.1
Run Hour : 0.1 Hr
Accuracy
± 1% of F.S. ± 2 digitsCurrent & Average Current :
: ± 0.1 Hz ± 1 digit
Frequency
: ± 1%Run Hour
± 0.5% RPM :
Display Scrolling : Automatic or Manual
Voltage : ± 0.5% of F.S. ± 2 digits.
(Programmable)
Power Consumption : 1.5VA Max
RPM : 1350 to 1950
Pole: 0
(Range: 0-98, selectable in steps
of 2)
Run Hours : 0 to 99999.9 Hrs
Burden : 0.5VA @5A per phase
Frequency : 45-65 Hz
Sr.
No. Description
1Electrical parameters like AC Voltage, AC Current,
RPM, Frequency and Power Factor will be seen as Per
screen no and auto or manual mode.Kindly refer Home
Page Descriptor.
2
3
4Unit KiloVolts
5Unit Volts
User Interface
11
12
13
14
15
VAF433-T
Vr
IhAM
AVG
1
2
3
4
5
6
7
8
9
10
17 18 19
16
6
7
Kilo Ampere
Ampere
8
9
Unit for Run Hours
Power Factor
Down key/ I/ h :
Press this key for 1 second, the First Screen
Displays phase current of three phases. Line to
neutral and line to line voltage of three phases are
displayed one by one.
In Normal Mode (Auto/Manual):
Press this key for 3 seconds, to display Run
Hours (for non zero poles).
In Program Mode: To increase Parameter
value.
Note: To return back to current page, press
for 3 seconds. I
I
h
h
17
Next key :
In Manual Mode: To scroll for Next Screen.
In Program Mode: To scroll to Next Parameter.
Note: Kindly refer ‘Home Page Screen
Description’ for further details.
10
11
12
13
14
15
16
AVG
Frequency units Hertz
Line to Line value of corresponding parameter
Line to Neutral value of First Phase
Average value of corresponding parameter
Line to Neutral value of Second Phase
Line to Neutral value of Third Phase
18
Up key :
19
In Normal Mode (Auto/Manual):
In Program Mode: To increase Parameter
value.
Note: To return back to current page, press
for 3 seconds.
Press this key for 1 second.
The First Screen displays line to neutral voltage
of three phases.
The Second Screen displays line to line voltage
of three phases.
Press this key for 3 seconds.
Displays rpm for non zero poles.
Vr
Note: Kindly refer ‘Home Page Screen
Description’ for further details.
Exit key :
In Program Mode:
Press this key for 4 seconds to toggle
between Automatic/Manual Mode.
To save the changed Parameter and exit to
Normal mode.
In Normal Mode:
AM
Front View
96
96
91mm
91mm
91
Side View
Panel Cutout
All dimensions are in MM.
The VAF is a panel mounted 96 x 96mm Digital Panel Meter for the
measurement of important electrical parameters like AC Voltage, AC
Current, RPM, Frequency and Power Factor VAF can be configured
and Programmed On site for the following :
PT Primary, PT Secondary, CT Primary, CT Secondary (5A or 1A) and
System Type 3 phase 3W or 4W or single phase system.
The front panel has Four keys using which the user can scroll through
different screens and configure the product.

Min Max
Fac.
Min Max
Fac.
100 V 350 V
500 V
Min Max
Fac.
0 098
Function: To select PT Secondary ratio.
5
Parameter
PT Secondary: To select PT Secondary ratio.
Function: To select no. of Poles.
6
Parameter
To select number of poles.
Function: To clear run hours.
7
Parameter
If selected yes run hours will be cleared
Function : To restore default settings of
the controller.
8
Parameter
Useful to debug setting related problems.
When set to YES all parameters are programmed to factory
values.
1st Screen Displays Line to line voltage of all 3
Phase
2nd Screen rpm
3rd Screen Displays Line to line current of all 3 Phase
4th Screen Displays run hours
5th Screen Displays Power Factor of Line to Line
Voltage
6th Screen Displays Line to line voltage, current and
frequency of first Phase
7th Screen Displays line to line voltage, current and
frequency of second Phase
8th Screen Displays line to line voltage, current and
frequency of third Phase
9th Screen Displays average line to line voltage,
average current of three phase and
frequency
2. Display Descriptions in 3Ø – 3W :
In Manual Mode :
1. Display Descriptions in 3Ø – 4W :
To scroll through next screen press key.
1st Screen Displays Line to Neutral voltage, current
and frequency of first Phase.
2nd Screen Displays line to neutral voltage, current
and frequency of second Phase
3rd Screen Displays line to neutral voltage, current
and frequency of third Phase
4th Screen Displays average line to neutral
voltage,average current of three phase
and frequency
5th Screen Displays average line to line voltage,
average current of three phases and
frequency of present phase.
6th Screen Displays Power Factor of Line to Line
Voltage.
2. Display Descriptions in 3Ø – 3W :
1st Screen Displays Line to line voltage, current and
frequency of first Phase
2nd Screen Displays line to line voltage, current and
frequency of second Phase
3rd Screen Displays line to line voltage, current and
frequency of third Phase
4th Screen Displays average line to line voltage,
average current of three phase and
frequency
5th Screen Displays Power Factor of Line to Line
Voltage
Parameter Setting Mode
Function: To enter into Program Mode.
1Program
Mode
Function: Network selection.
Function: To select CT Primary ratio.
2
3
Parameter
Parameter
Min Max
Fac.
3P3
3P4
Min Max
Fac.
5 A 5 A
10 kA
Network selection ie, either 3 Phase 3 wire or 3 Phase 4 wire.
To select CT Primary ratio.
Function: To select PT Primary ratio.
4
Parameter
Min Max
Fac.
100 V 350 V
500 kV
PT Primary: To select PT Primary ratio.
Press & hold key for 4 second.
Press the key to save the set value and to come out of
parameter setting after changing the set value.
Press & hold key for 4 seconds to enter into Program
Mode. When release the key, second display will flash .
Press UP/DOWN keys to modify the set value and to go to the
next parameter by pressing key.
3P4
Error Messages
Message Description
Power factor of corresponding phase
shows this error message when input of
corresponding is open.
It indicates corresponding parameter
reach above specified measuring range.
Typical Wiring Diagram
2 ø- 3 Wire, 2 CT's and 2 PT's
S1 S2 S1 S2 S1 S2
I1I2I3
L N
LINE L1
L2
LOAD
N
1 2 3456 7 8 9 10
11 12 18 19 20
N VR VY VB
3P4W
3P3W
VR VY VB
2 Phase - 3 Wire
3 ø- 3 Wire, 2 CT's and 2 PT's
3P3W
S1 S2 S1 S2 S1 S2
I1I2I3
L N
L1
L2
L3
LOAD
LINE
1 2 3456
11 12 18 19 20
VR VY VB
Note : Do not use 7,8 , 9 & 10 connector for 3P 3W.
3 Phase - 3 Wire
Disclaimer: This manual & its contents remain the sole property of
PVR CONTROLS . India and shall not be reproduced or distributed
without authorization. Although great care has been taken in the
preparation of this document, the company or its vendors in no event
will be liable for direct, indirect, special, incidental or consequential
damage arising out of the use or inability to use the product or
documentation, even if advised of the possibility of such damages. No
part of this manual may be reproduced or transmitted in any form or by
any means without the prior written permission of the company. PVR
CONTROLS., reserves the right to make and changes or improvements
without prior notice.
Warranty: This product is warranted against defects in materials and
workmanship for a period of one year from the date of purchase. During
the warranty period, product determined by us to be defective in form or
function will be repaired or, at our option, replaced at no charge. This
warranty does not apply if the product has been damaged by accident,
abuse, and misuse or as a result of service or modification other than by
the company. This warranty is in lieu of any other warranty expressed or
implied. In no event shall the company be held liable for incidental or
consequential damages, including lost revenue or lost business
opportunity arising from the purchase of this product.
Min Max
Fac.
TM
OUR OTHER PRODUCTS
Digital Panel Meter
Power Analyzer
Timer , PLC , HMI
Data Logger
REV0 / 26.09.2020
1 Phase - 2 Wire
1 ø- 2 Wire, 1 CT's
S1 S2 S1 S2 S1 S2
I1I2I3
L N
L1
N
LOAD
LINE
1 2 3456 7 8 9 10
11 12
N VR VY VB
3P4W
18 19 20
3P3W
VR VY VB
#
##
#
##
#
3 Phase - 4 Wire
3 ø- 4 Wire, 3 CT's and 3 PT's
S1 S2 S1 S2 S1 S2
I1I2I3
L N
LINE L1
L2
L3
LOAD
N
1 2 3456 7 8 9 10
11 12
N VR VY VB
3P4W
18 19 20
3P3W
VR VY VB
3 Phase - 4 Wire
1 2 3456 7 8 9 10
11 12
S1 S2 S1 S2 S1 S2 N VR VY VB
I1I2I3
L N
LINE L1
L2
L3
N
LOAD
18 19 20
3P4W
3P3W
VR VY VB
3 ø- 4 Wire, 3 CT's
#
#
#
#
#
NOTE : # All fuse types : 0.5A class CC UL type ;
0.5A fast acting 600V
Other Sub-Zero Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Siemens
Siemens SENTRON PAC3200T product manual

Pneumercator
Pneumercator TMS1000N Operation & maintenance manual

Niigata seiki
Niigata seiki EOM133 Series instruction manual

TREND
TREND HMM Series installation instructions

Endress+Hauser
Endress+Hauser Prosonic M FMU40 operating instructions

GOK
GOK SmartBox 1 Assembly and operating manual

Hanna Instruments
Hanna Instruments HI96802 instruction manual

ALPA
ALPA MEGAtower Use and maintenance manual

Leica
Leica 2700-B instructions

Ibiza
Ibiza IBIZA400RGB 15-1567 user manual

PCB Piezotronics
PCB Piezotronics 339B01 Installation and operating manual

CI Systems
CI Systems ControlMaster SR-800R Operation manual