Sumitomo HF-520 Series User manual

Technical Manual
CC-Link
Type SI-C3/V-H
Inverter HF-520 Option
Manual
NOTICE
1. Make sure that this technical manual is delivered to
the end user of inverter unit.
2. Read this manual before installing or operating the
inverter unit, and store it in a safe place for
reference.
No.DM2304E-1

2
Copyright © 2014 Sumitomo Heavy Industries, LTD.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic,
photocopying, recording, or otherwise, without the prior written permission of Sumitomo. No patent liability is assumed with respect to the use of the information contained
herein. Moreover, because Sumitomo is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice.
Every precaution has been taken in the preparation of this manual. Sumitomo assumes no responsibility for errors or omissions. Neither is any liability assumed for damages
resulting from the use of the information contained in this publication.

3
Table of Contents
1 PREFACE AND SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 PRODUCT OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 RECEIVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 CC-LINK OPTION COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5 INSTALLATION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 CC-LINK OPTION DRIVE PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7 BASIC FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8 CC-LINK DATA TABLE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10 CC-LINK CODE NUMBERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
11 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
12 WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

4
1 Preface and Safety
1 Preface and Safety
Sumitomo manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of
Sumitomo products remain the responsibility of the equipment manufacturer or end user. Sumitomo accepts no responsibility for the way its
products are incorporated into the final system design. Under no circumstances should any Sumitomo product be incorporated into any product or
design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under
all circumstances. All systems or equipment designed to incorporate a product manufactured by Sumitomo must be supplied to the end user with
appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Sumitomo must be promptly provided
to the end user. Sumitomo offers an express warranty only as to the quality of its products in conforming to standards and specifications published
in the Sumitomo manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. Sumitomo assumes no liability for any personal
injury, property damage, losses, or claims arising from misapplication of its products.
◆Applicable Documentation
The following manuals are available for the CC-Link Option:
◆Terms
Note: Indicates supplementary information that Sumitomo highly recommends be followed, even though equipment may not be at risk.
◆Registered Trademarks
• CC-Link is a registered trademark of the CC-Link Partner Association.
• Other company names and product names listed in this manual are registered trademarks of those companies.
Option Unit
HF-520 Option CC-Link Installation Manual
Manual No. : DM2303E
Read this manual first.
The installation manual is packaged with the CC-Link Option and contains a basic overview of wiring, settings, functions, and fault diagnoses.
HF-520 Option CC-Link Technical Manual
Manual No. : DM2304E
The technical manual contains detailed information and command registers.
To obtain the technical manual access the site below:
http://www.shi.co.jp/PTC/
Inverter
HF-520 Technical Manual
Manual No. : DM2302E
This manual describes installation, wiring, operation procedures, functions, troubleshooting, maintenance, and inspections to perform before operation.
To obtain instruction manuals for Sumitomo products, access the site below:
http://www.shi.co.jp/PTC/
HF-520 Operating and Maintenance Manual
Manual No. : DM2301E
This manual is packaged together with the product. It contains basic information required to install and wire the drive. This manual provides basic
programming and simple set-up and adjustment.
Drive: HF-520 Series
CC-Link Option: HF-520 Option CC-Link
L.RUN
L.ERR
SD
RD
STOP
(Hz)
(Hz)
(A)
(V)
FreqReference
FWD/ REV Sel
OutputFreq
OutputCurrent
SelectedMonitor
Monitor
Verify
SetUpGuide
ParameterSet
Auto-Tuning
HF-520
:
:
:
:
:
:
:
:
:
:
Risque de décharge
électrique.
Lire le manuel avant l'installation.
Attendre 5 minutes après la coupurede l'alimentation,
pour permettre la décharge des condensateurs.
Pour répondre aux exigences , s assurer que le
neutre soit relié à la terre, pour la série 400V.
Read manual before installing.
Wait 5 minutes for capacitordischarge after
disconnecting power supply.
Toconform to requirements, make sure
to ground the supply neutral for 400V class.
Risk of electric shock.
WARNI NG
AVERTISSEMENT

1 Preface and Safety
5
◆Supplemental Safety Information
Read and understand this manual before installing, operating, or servicing this option unit. The option unit must be installed according to this
manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or possibly
even fatal injury or damage to the products or to related equipment and systems.
■General Safety
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates an equipment damage message.
General Precautions
• The diagrams in this section may include option units and drives without covers or safety shields to illustrate details. Be sure to reinstall covers
or shields before operating any devices. The option should be used according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this
manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to
improve the product and/or the manual.
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual.
NOTICE
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the option unit.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
SUMITOMO is not responsible for any modification of the product made by the user. This product must not be modified.

1 Preface and Safety
6
■Option Unit Label Warnings
Warning information is displayed on the option unit as shown in the figure below. Follow all warnings and safety instructions when using the
product.
■Warning Contents
HF-520
L.RUN
L.ERR
SD
RD
Read manual before installing.
Wait 5 minutes for capacitor discharge after
disconnecting power supply.
To conform to requirements, make sure
to ground the supply neutral for 400V class.
Warning
information
AVERTISSEMENT
Lire le manuel avant l'installation.
Attendre 5 minutes apres la coupure de l'alimentation,
pour permettre la decharge des condensateurs.
Pour repondre aux exigences , s assurer que le
neutre soit relie a la terre, pour la serie 400V.
WARNING
Risk of electric shock.
Risque de decharge
electrique.
Read manual before installing.
Wait 5 minutes for capacitor discharge after
disconnecting power supply.
To conform to requirements, make sure
to ground the supply neutral for 400V class.
AVERTISSEMENT
Lire le manuel avant l'installation.
Attendre 5 minutes apres la coupure de l'alimentation,
pour permettre la decharge des condensateurs.
Pour repondre aux exigences , s assurer que le
neutre soit relie a la terre, pour la serie 400V.
WARNING
Risk of electric shock.
Risque de decharge
electrique.

2 Product Overview
7
2 Product Overview
◆About This Product
CC-Link Option (Model: SI-C3/V-H) is designed for connecting a drive to a field network using the CC-Link protocol. This option is conforming to
CC-Link Ver.1.10.
By installing the CC-Link Option to a drive, it is possible to do the following from a CC-Link master device:
• operate the drive
• monitor the operation status of the drive
• change parameter settings.
Figure 1
Figure 1 CC-Link Approved

8
3 Receiving
3 Receiving
Please perform the following tasks after receiving the CC-Link Option:
• Inspect the CC-Link Option for damage.
• Verify receipt of the correct model by checking the information on the nameplate (see Figure 2).
• If you have received the wrong model or the CC-Link Option does not function properly, contact your supplier.
◆Contents and Packaging
Table 1 Contents of Package
◆Tool Requirements
Note: Tools required to prepare CC-Link cables for wiring are not listed in this manual.
Description: Option unit Ground Cables Warning Label Stickers Installation Manual
–
Quantity: 1411
A Phillips screwdriver (M3, M3.5 to M5 <1>) metric or (#1, #2 <1>) U.S. standard size is required to install the CC-Link Option.
<1> Screw sizes vary by drive capacity. Select a screwdriver that matches the drive capacity.
MANUAL

4 CC-Link Option Components
9
4 CC-Link Option Components
◆CC-Link Option
Figure 2
Figure 2 Option Unit
Note: For details on the LEDs, Refer to CC-Link Option LED Display on page 10 and Fault LED Display on CC-Link Option Side on page 24.
◆Dimensions
The installed CC-Link Option adds 27 mm to the total depth of the drive.
Figure 3
Figure 3 Dimensions
◆Terminal Block
Table 2 Terminal Descriptions
Figure 4
Figure 4 CC-Link Option Terminal Block
A – LED (SD) H – Nameplate
B – LED (RD) I – Function Earth cable connection (FE)
C – Option cover J – Mounting clip
<1> Cables are not connected to the CC-Link Option and are packaged separately in the box.
D – LED (L.ERR) K – Ground Cable <1>
E – LED (L.RUN) L – Through-hole for cable
F – CC-Link PCB M – Terminal block
G – Attachment screw hole for option cover N – Option connector
Terminal Name Description
1DA
Comm. Data +
2DB
Comm. Data –
3DG
Signal Ground
4SLD
Shield
5SLD
Shield
L.RUN
L.ERR
SD
RD
A
E
DB
C
CC-Link with cover attached
FE
N
J
G
F
J
K
I
LM
H
CC-Link with cover removed
underside
27 mm
Front View
(looking from the front of the CC-Link Option)
DA DB DG
SLD SLD
Bottom View

4 CC-Link Option Components
10
◆CC-Link Option LED Display
Table 3 CC-Link Operation LED Status
◆Setting Station Address
Set drive parameter F6-10 to a station address (Range 1 to 64) unique to the network. If set to 0, the L.ERR light will turn on and a Station Address
Error (AEr) will occur.
Name Indication Operating Status Remarks
Color Status
L.RUN Green
ON Normal operation • Receiving data normally
OFF Timed out
• Timed out waiting to receive
• Logging onto the network
• During reset
L.ERR Red
ON CRC error •CRC error
• Station address setting error (F6-10 = 0)
OFF During communications • Normal communications
• During reset
SD Red
ON Sending data • Sending data
Note: LED may appear to flash with slower baud rates.
OFF No data transfer • No data being sent
• During reset
RD Red
ON Detecting data received • Detecting data that was received
Note: LED may appear to flash with slower baud rates.
OFF Waiting for data • Data not yet received
• During reset

5 Installation Procedure
11
5 Installation Procedure
◆Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive, wait at least five minutes after all indicators are off, measure the DC bus voltage to confirm safe level, and
check for unsafe voltages before servicing to prevent electric shock. The internal capacitor remains charged even after the power supply is turned
off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc.
WARNING
Electrical Shock Hazard
Do not remove option cover while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include option units and drives without covers or safety shields to show details. Be sure to reinstall covers or
shields before operating any devices. The option should be used according to the instructions described in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment, and
maintenance of this product.
Do not remove option cover while the power to the drive is on.
Failure to comply could result in death or serious injury.
Do not use damaged wires, place excessive stress on wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
NOTICE
Damage to Equipment
Observe proper electrostatic discharge procedures (ESD) when handling the option unit, drive, and circuit boards.
Failure to comply may result in ESD damage to circuitry.
Never shut the power off while the drive is outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the drive.
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
Properly connect all pins and connectors.
Failure to comply may prevent proper operation and possibly damage equipment.
Check wiring to ensure that all connections are correct after installing the option unit and connecting any other devices.
Failure to comply may result in damage to the option unit.

5 Installation Procedure
12
◆Wiring Diagram
Table 4 Wiring Diagram
Using a single drive
<1> The user must set up the drive for terminal resistor. For instructions, see Terminal Resistor Connection on page 16.
<2> Make sure that the FG terminal on the master drive is grounded properly.
<3> The FE terminal on the CC-Link Option is supplied with a ground cable that should be connected to the ground terminal on the drive.
Using multiple drives
CC-Link
Option
DA
DB
DG
SLD
SLD
DA
DB
DG
SLD
FG
Master
device
CC-Link cable
DRIVE
Terminal resistor <1>
FE
<2>
<3>
CC-Link
Option
DA
DB
DG
SLD
SLD
CC-Link
Option
DA
DB
DG
SLD
SLD
DA
DB
DG
SLD
FG
CC-Link
Option
DA
DB
DG
SLD
SLD
Master
device DRIVE
DRIVE
DRIVE
CC-Link cable
Terminal resistor
<1>
FE
FE
FE
<2>
<3>
<3>
<3>

5 Installation Procedure
13
◆Installing the Option Unit
Remove the front cover of the drive before installing the CC-Link Option. Follow the directions below for proper installation.
1. Switch off the power supply to the drive.
DANGER! Electrical Shock Hazard - Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before installing the
CC-Link Option, disconnect all power to the drive. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish
when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe
level.
2. Remove the front cover.
The original drive front cover may be discarded because it will be replaced by the CC-Link Option cover in step 8.
Figure 5
Figure 5 Remove Front Cover
3. Remove the bottom cover and connect the CC-Link Option ground cable to the ground terminal.
Figure 6
Figure 6 Connect Ground Cable
Note: The four different ground cables packaged with the CC-Link Option connect the unit to different models. Select the proper ground cable from the CC-Link Option kit
depending on drive size.
Figure 7
Figure 7 Ground Cable
Note: Cover removal for certain larger models with a Terminal Cover:
-Single-Phase 200 V Class: HF520S-A75 to 2A2
-Three-Phase 200 V Class: HF5202-1A5 to 7A5
-Three-Phase 400 V Class: All models
Remove the terminal cover before removing the bottom cover to install the CC-Link Option. Replace the terminal cover after wiring the CC-Link Option.
Figure 8
Figure 8 Models with Terminal Cover
4. Reattach the bottom cover.
A – Option unit connection: screw size = M3
B – Drive-side connection: screw size = M3.5 to M6
ground terminal
ground cable
bottom cover
A
B

5 Installation Procedure
14
5. Connect the CC-Link Option to the drive.
Properly secure the tabs on the left and right sides of the CC-Link Option to the drive case.
Figure 9
Figure 9 Attach CC-Link Option
6. Connect the ground cable from the drive ground terminal to the CC-Link Option ground.
When wiring the CC-Link Option, pass the ground cable through the inside of the drive bottom cover, then pass the ground cable into the
through-hole at the front of the CC-Link Option.
Figure 10
Figure 10 Ground Cable Connection
7. Connect the communications cable to the terminal block. Refer to Procedure on page 15.
8. Attach the CC-Link Option cover to the front of the CC-Link Option.
Figure 11
Figure 11 Attach Cover
tabs should line up
tabs should line up
ground
cable
drive ground terminal
Pass the ground cable through
the bottom cover of the drive.
through-hole
for ground cable
ground cable
tabs should line up

5 Installation Procedure
15
◆Communication Cable Wiring
■Procedure
Follow the instructions below to connect the communications cable to the terminal block.
NOTICE: Tighten all terminal screws according to the specified tightening torque. Tightening screws too tight could damage the terminal block, and leaving screws too loose
can cause a short-circuit or drive malfunction.
1. Connect the communications cable to the terminal block as shown in the diagram below.
Note: Communication lines should be separated from main circuit wiring and other electrical lines. (Tightening torque: 0.22 to 0.25 (Nm))
Figure 12
Figure 12 Comm Cable Wiring
2. Ensure all wiring connections are tightened and wire insulation is not pinched in the terminal block. Remove any stray wire strands that touch
other terminals.
3. After the terminal block is fully attached to the option unit, tighten the screws on the left and right sides of the terminal block. (Tightening
torque: 0.22 to 0.25 (Nm))
Note: Be sure to put the option cover back on after you have completed all necessary wiring.
Figure 13
Figure 13 Terminal Block Installation
■Communication Cable Specifications
Use only CC-Link dedicated communication cable; the Sumitomo warranty does not cover other cable types. For more information on cables, refer
to the CC-Link website at http://www.cc-link.org/.
Sumitomo recommends using CC-Link cables suitable for the conditions listed in Table 5.
Table 5 Communication Cable Requirements
Specifications
Cable Type triple-core shielded twisted-pair cable
Gauge 8.0 mm max
Drain Wire 20 lines / 0.18 mm or 24 lines / 0.18 mm
Electrical
Characteristics
Conductor Resistance (20°C) 37.8 Ω/km
Insulation Resistance 10000 MΩkm or more
Voltage Tolerance 500 Vdc, 60 s
Capacitance (1 kHz) 60 nF/km max
Impedance 1 MHz 110 ±15 Ω
5 MHz 110 ± 6 Ω
Attenuation (20°C) 1 MHz 1.6 dB / 100 m max
5 MHz 3.5 dB / 100 m max
DA DB DG SLD SLD
Terminal block
Preparing wire ends: Screwdriver blade size
When not using
terminal extensions
about 5.5 mm
up to
2.5 mm
Blade width
up to 0.4 mm
Pull back the sheilding and lightly
twist the end with fingers, keeping
the ends from fraying
CC-Link comm cable
(do not soldered ends)
Loosen the screws and
insert the cable into the
opening on the terminal block
screwdriver blade size
up to
3.5 mm
blade width
up to 0.6 mm

5 Installation Procedure
16
Figure 14
Figure 14 Cable Diagram
■Terminal Resistor Connection
When the CC-Link Option is the last station connected in a CC-Link network, the terminal resistor needs to be set to that CC-Link Option. Follow
the instructions below.
1. Cut the terminal resistor tube as shown.
Note: For the terminal resistor, either use what is already built into the master unit, or use a standard-market resistor of 110 Ω, ±5% (1/2 W).
Figure 15
Figure 15 Terminal Resistor
2. Loosen the attachment screw and insert the terminal resistor described in the first step between terminals DA and DB.
Note: Make sure that the option cover is put back on after wiring is complete.
Figure 16
Figure 16 Terminal Resistor Wiring
A – sheath F – drain (concentrated)
B– shield G–DB
C – aluminum tape H – DA
D – DG I – drain (spread out)
E – ground
A
B
C
D
E
H
G
F
white
blue
yellow
A
B
C
D
E
H
G
I
white
blue
yellow
j
umper
cut here
cut
DA DB DG SLD SLD

6 CC-Link Option Drive Parameters
17
6 CC-Link Option Drive Parameters
Confirm proper setting of the all parameters in Table 6 before starting network communications.
Table 6 Parameter Settings
No. Name Description Default
b1-01
<1> To start and stop the drive with the CC-Link master device using serial communications, set b1-02 to “3”. To control the frequency reference of the drive via the master device, set b1-01
to “3”.
<2> If set to 3, then the drive will continue to operate when a fault is detected. Take proper measures such as installing an emergency stop switch.
<3> The drive default setting is 2.0 s, but this default setting will automatically be changed to 0.0 s when SI-C3/V is connected.
<4> Power must be cycled in order for any setting changes to take affect.
<5> All station addresses must be unique. If set to 0, the L.ERR light will turn on and a Station Address Error (AEr) will occur.
<6> A total of 42 nodes can be connected, assuming that all connections are inverter drives.
The following conditions apply when connecting devices that are not drives to the network:
Frequency Reference Selection <1>
Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
1
b1-02 Run Command Selection <1>
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS communications
3: Option PCB
1
F6-01 Operation Selection after
Communications Error
Determines drive response when a bUS error is detected during communications with the CC-Link Option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only <2>
1
F6-02 External Fault Detection Conditions
(EF0)
Sets the condition for external fault detection (EF0)
0: Always detected.
1: Detected only during operation.
0
F6-03 Stopping Method for External Fault
from Communication Option
Determines drive response for external fault input (EF0) detection during CC-Link communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only <2>
1
F6-04 bUS Error Detection Delay Time Set the maximum time the drive should wait for a communication error to occur (bUS).
Range 0.0 to 5.0 s
0.0 s
<3>
F6-07 NetRef/ComRef Selection Function 0: Multi-step speed reference disabled
1: Multi-step speed reference allowed 1
F6-08 Reset Communication Related
Parameters
Determines which communication-related parameters are set back to their original default values when the drive is
initialized.
0: Do not reset F6- and F7- parameters when the drive is initialized using parameter A1-03.
1: Rest F6- and F7- parameters when the drive is initialized using parameter A1-03.
Note: Setting this parameter does not affect communication-related parameters.
0
F6-10
<4> Station Address <5> <6> 0 to 64 0
F6-11
<4> Comm Speed
0: 156 kbps
1: 625 kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
0
A: number of remote I/O nodes........ 64 max
B: number of remote device nodes... 42 max
C: number of local nodes.................. 26max
a: number of units that occupies 1 node b: number of units that occupies 2 nodes
c: number of units that occupies 3nodes d: number of units that occupies 4 nodes
{(1×a)+(2×b)+(3×c)+(4×d)} ≦64
{(16×A)+(54×B)+(88×C)} ≦2304
(
()
)

18
7 Basic Functions
7 Basic Functions
This interface allows the drive to be connected to a CC-Link network as a remote device, making it possible to operate, adjust settings, and monitor
the operation status of the drive using the PLC program. Both bit and word data cyclic transmission are available, and high speed communication up
to 10 Mbps is possible.
Below is a description of the basic CC-Link functions that can be performed by the PLC.
Note: Set parameters when operating the drive from a PLC. For instructions, see CC-Link Option Drive Parameters on page 17.
◆Switching Between Command/Reference Sources
The Run command, Stop command, and the frequency reference can be entered directly from the operator or given from a separate control device.
To use a separate control device to issue the Run command and frequency reference, the drive needs to be set so that it accepts theses commands
from an external source.
■Selecting an External Source
Follow the directions below set the drive up to accept commands from an external controller.
• Using Parameters to Select the Command/Reference Source
• Using the External Terminals to Switch the Command/Reference Source
• Using a PLC as the Command/Reference Source
■Using Parameters to Select the Command/Reference Source
Selecting the Run Command Source
Set b1-02 (Run Command Selection) to 3 ("Option PCB").
Selecting the Source of the Frequency Reference
Set b1-01 (Frequency Reference Selection) to 3 (“Option PCB”).
■Using the External Terminals to Switch the Command/Reference Source
Selecting the Run Command Source 2
Set b1-16 (Run Command Source 2) to 3 (“Option unit”).
Selecting the Source of the Frequency Reference 2
Set b1-15 (Frequency Reference Source 2) to 3 (“Option unit”).
Selecting the Run Command and Frequency Reference Source
By setting one of the multi-function input terminals S1 through S7 to supply auxiliary reference (H1-01 to H1-07 = 2), then the frequency reference
set to b1-15 and the run command source set to b1-16 will become enabled.
■Using a PLC as the Command/Reference Source
Using Parameters to Switch Sources
Note: By setting H1- = 2, then parameters b1-15 and b1-16 will become enabled when that terminal is switched on.
• Selecting the Run Command Source
Send write data “3” for command code 2181H to the drive.
The setting for parameter b1-02 changes to “3”.
• Frequency Reference Source Selection
Send write data “3” for command code 2180H to the drive.
The setting for parameter b1-01 changes to “3”.
Using NetRef and NetCtrl
It is also possible to change the source of the frequency reference and the Run command using remote register RWW2 command code 00FBH.
If the power is shut off, however, the drive will use the original setting for the command/reference source once the power is turned back again. This
method should therefore only be used when briefly switching between command/reference sources.

7 Basic Functions
19
■Command/Reference Source Priority Using a PLC
Run Command Source
Table 7 Run Command Source Priority
Note: Dash indicates that the setting has no effect on the source of the Run command.
Frequency Reference Source
Table 8 Frequency Reference Source Priority
Note: 1. When the multi-function input terminals are set up for Multi-Step Speed operation, parameters d1-01 through d1-16 take priority as the source of the frequency reference
(assuming that F6-07 = 1).
2. Dash indicates that the setting has no effect on the source of the frequency reference.
3. Refer to the HF-520 Technical Manual for more details on parameter settings.
◆Monitors
The user can monitor drive operating status from a PLC.
To do so, the monitor should be set up as follows:
1. Sets the monitor code to the remote register RWW0.
2. Switch the RYC signal on.
• Data for the monitor code is stored in the PLC’s buffer memory.
Note: Monitor codes and units are listed in Monitor Codes on page 29.
◆Reading and Setting Parameters
The PLC can write drive parameters, read drive data and operation status, and change settings.
Follow the directions below.
1. Set the command code to remote register RWW2.
• Set the write data to RWW3 as needed.
2. Switch on the RYF signal (request to execute the command code).
• Drive executes the process and reply data that correspond with the command code.
• Command codes for drive parameters should be calculated by adding the values shown below to the MEMOBUS register number.
Read command code: MEMOBUS register + 1000H
Write command code: MEMOBUS register + 2000H
EXAMPLE: Acceleration time command code for C1-01 is 200H. Get the read command code by adding 1000H, yielding 1200H
Note: 1. For a list of command codes, write data units, and setting ranges, refer to Command Codes on page 27 and Extended Command Codes on page 28.
2. Refer to the MEMOBUS/Modbus Data Table in Appendix C of the HF-520 Technical Manual for a list of monitor data using the MEMOBUS/Modbus message area.
Setting Status
NetCtrl 100000
LOCAL/REMOTE Selection – LOCAL REMOTE
Switching Command Source –– OFF ON
Run Command Selection 1
b1-02 ––3not 3––
Run Command Selection 2
b1-16 ––––3not 3
Run Command Source PLC Operator PLC Determined by b1-02 PLC Determined by
b1-16
Setting Status
NetRef 1 0 0 0 0 0
LOCAL/REMOTE Selection – LOCAL REMOTE
Switching Reference Source –– OFF ON
Frequency Reference Selection 1
b1-01 – – 3 not 3 – –
Frequency Reference Selection 2
b1-15 ––––3not 3
Frequency Reference Source PLC Operator PLC Determined by b1-01 PLC Determined by
b1-15

20
8 CC-Link Data Table
8 CC-Link Data Table
◆Remote I/O
The drive takes up a single station address in the buffer memory or the PLC. The table below shows the drive I/O as seen from the PLC side.
Note: Refer to the PLC’s programming manual for information on the PLC’s buffer memory.
■PLC → Drive
Table 9 Remote I/O Table (PLC → Drive)
Note: 1. If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. Using RYE (Frequency Reference 2 flag) too often can shorten the
performance life of the drive's internal memory.
2. Although RYE and RYF are triggered by the rising edge of the signal, they are otherwise enabled depending on the value that is input.
When switching between monitors using RYC (Monitor Reference), RYC needs to be turned off and then back on again after the monitor code has been changed.
Signal Name Description Default
RY0 Forward Run ON: Forward Run Command, OFF: Stop –
RY1 Reverse Run ON: Reverse Run Command, OFF: Stop –
RY2 Terminal S3 Function Multi-function input: H1-03 (H1-03 = 24: External Fault)
RY3 Terminal S4 Function Multi-function input: H1-04 (H1-04 = 14: Fault Reset)
RY4 Terminal S5 Function Multi-function input: H1-05 (H1-05 = 3: Multi-Step Speed 1)
RY5 Terminal S6 Function Multi-function input: H1-06 (H1-06 = 4: Multi-Step Speed 2)
RY6 Terminal S7 Function Multi-function input: H1-07 (H1-07 = 6: Jog Reference)
RY7, 8 Reserved – –
RY9 Drive Output Interrupt ON: Motor coasts to stop.
OFF: Drive will begin operating as soon as a Run command is given. –
RYA External Fault ON: External Fault Input (EF0) –
RYB Motor Revolutions / Output
Frequency Switch
Data contents for the remote register RWR1 switches between motor revolutions and
output frequency.
Motor rotations are displayed
only when H6-01 = 3 and
A1-02 = 0.
RYC Monitor Reference ON: Monitor data specified in the monitor code is set to remote register RWR0.–
RYD Frequency Reference 1 Frequency set to remote register RWW1 becomes the operating frequency for the drive. –
RYE Frequency Reference 2
Sets the frequency in the remote register RWW1 to parameter d1-01 (Frequency Reference
1) and as the drive’s main frequency reference at the same time.
Note: If the frequency reference is set to be provided by the LED operator
(i.e, b1-01 = 0), then switching on RYE changes the frequency
reference.
All parameter settings are saved
when this flag is switched on.
Triggered by the rising edge of
the signal.
RYF Command Code Execute Request Request to execute the command code.Triggered by the rising edge of
the signal.
RY10 to 13 Reserved – –
RY14 Terminal S1 Function Multi-function input: H1-01
Function is disabled when for the
Forward Run Command (H1-01
= 40).
RY15 Terminal S2 Function Multi-function input: H1-02
Function is disabled when for the
Reverse Run Command (H1-02 =
41).
RY16 to 19 Reserved – –
RY1A Fault Reset Resets a drive fault –
RY1B to 1F Reserved – –
Other manuals for HF-520 Series
2
Table of contents
Other Sumitomo Inverter manuals

Sumitomo
Sumitomo CAI Series User manual

Sumitomo
Sumitomo HF-430 Series Operating instructions

Sumitomo
Sumitomo HF-520 Series Operating instructions

Sumitomo
Sumitomo HF-430NEO Series User manual

Sumitomo
Sumitomo HF-520 Series User manual

Sumitomo
Sumitomo SF-320 User manual

Sumitomo
Sumitomo CAI40C User manual