SSTTEEPP11..11::IInnssttaallllGGFFCCIIBBrreeaakkeerr
((OOvveerrccuurrrreennttPPrrootteeccttiioonn))
The SunTouch mat must be pro-tect-
ed by a ground fault circuit interrupter
(GFCI). This can be done either by the
internal GFCI in the SunTouch FloorStat
(as long as it directly controls the mat)
or an indicating-type GFCI
circuit breaker. This GFCI serves as a
local disconnect.
Note: Follow all local building and
electrical codes.
Note: It is possible to branch from
an existing circuit, but this is not
recommended. Please consult with a
qualified electrician to determine if
the circuit can handle the load and
if the circuit is GFCI-protected.
The size of the breaker is determined
by the total square footage of heating
mat. (Depending on local codes, you
may need multiple breakers for systems
larger than 20 amps.)
Typical Amperage Requirement:
120 VAC SunTouch mats:
0.1 amps per sq.ft., or
10 amps per 100 sq.ft. of mat.
240 VAC SunTouch Mats:
0.05 amps per sq.ft., or
5 amps per 100 sq.ft. of mat.
SSTTEEPP11..22::IInnssttaallllEExxtteerrnnaall
CCoonnttaaccttoorr((rreellaayy))
Depending on the amperage require-
ments of the mat(s), an external contac-
tor may be required. Consult with an
electrician to determine the type and size
of contactor. Do not load the FloorStat
control with more than 15 amps. Be sure
to protect this contactor circuit with a
GFCI breaker.
SSTTEEPP11..33::IInnssttaallllEElleeccttrriiccaall
BBooxxeess
Thermostats are usually located near
the power leads. However, they can
be located almost anywhere, because
the power leads and the sensor wire can
be routed to electrical junction boxes
and extended to a location outside the
heated room (such as a utility room or
basement).
TThheerrmmoossttaatt::Install a 4"-square,
2-1/8" deep electrical box with a
1-gang mud ring. Electrical boxes
should be located on interior walls, typi-
cally 60" from the floor, according to
NEC or other local code requirements.
Note: The FloorStat sensor wire
can be extended up to a maximum of
50', if necessary.
SSTTEEPP11..44::BBoottttoommPPllaatteeWWoorrkk
Drill or saw holes at the bottom plate
as indicated at right. One hole is for
routing the power leads or conduit and
the other is for the thermostat sensor.
These holes should be directly below the
electrical box(es) (see photos at right).
SSTTEEPP11..55::IInnssttaallllPPoowweerrLLeeaadd
CCoonndduuiittaannddTThheerrmmoossttaattSSeennssoorr
PPoowweerrLLeeaaddCCoonndduuiitt::The armored
power lead can be installed with or with-
out electrical conduit depending on code
requirements. In either case, remove one
of the knock-outs in the 4" box to route
the lead. If electrical conduit is not
required by code, install a wire collar to
secure the leads where they enter the
box. If conduit is required by code,
install 1/2" (minimum) conduit from the
bottom plate up to the electrical box. For
multiple power leads (multiple mats)
install 3/4" conduit, which will accom-
modate multiple power leads.
TThheerrmmoossttaattSSeennssoorr::Afloor sensor
comes with our FloorStat control. It can
be installed in a conduit separate from
the electrical power lead although this is
not necessary. If a conduit is installed,
the tip of the conduit should be metallic
in order for the sensor to give a true
temperature reading. Open a second
knock-out in the bottom of the thermo-
stat box. Feed the sensor (and conduit)
through the knock-out, down through the
cut-out in the bottom plate, and out into
the floor where the heating mat will be
installed. If you have the thermostat and
sensor, install the sensor now, but wait
to install the thermostat until after the
mat is installed.
Note: The sensor is located in the
thermostat packaging.
SSTTEEPP11..66::RRoouugghh--iinnWWiirriinngg
Install appropriate electrical wire
(conductor) from the power source and
breaker protection to the thermostat fol-
lowing all codes. Leave 6"–8" extra wire
at the thermostat box. Refer to the
Typical Wiring Diagrams at the end of
this manual for help.
MMaattAAmmppeerraaggeeRReeqquuiirreemmeennttss
Mat Size Square Footage Amp Draw
112200VVAACC,,1122""--wwiiddeemmaatt
12" x 10' 10 sq. ft. 1.0
12" x 15' 15 sq. ft. 1.5
12" x 20' 20 sq. ft. 2.0
12" x 25' 25 sq. ft. 2.5
12" x 30' 30 sq. ft. 3.0
12" x 35' 35 sq. ft. 3.5
12" x 40' 40 sq. ft. 4.0
12" x 45' 45 sq. ft. 4.5
12" x 50' 50 sq. ft. 5.0
112200VVAACC,,2244""--wwiiddeemmaatt
24" x 5' 10 sq. ft. 1.0
24" x 10' 20 sq. ft. 2.0
24" x 15' 30 sq. ft. 3.0
24" x 20' 40 sq. ft. 4.0
24" x 25' 50 sq. ft. 5.0
24" x 30' 60 sq. ft. 6.0
24" x 35' 70 sq. ft. 7.0
24" x 40' 80 sq. ft. 8.0
112200VVAACC,,3366""--wwiiddeemmaatt
36" x 5' 15 sq. ft. 1.5
36" x 6'8" 20 sq. ft. 2.0
36" x 8'4" 25 sq. ft. 2.5
36" x 10' 30 sq. ft. 3.0
36" x 15' 45 sq. ft. 4.5
36" x 20' 60 sq. ft. 6.0
______________________________________________
224400VVAACC,,1122""--wwiiddeemmaatt
12" x 20' 20 sq. ft. 1.0
12" x 30' 30 sq. ft. 1.5
12" x 40' 40 sq. ft. 2.0
12" x 50' 50 sq. ft. 2.5
224400VVAACC,,2244""--wwiiddeemmaatt
24" x 10' 20 sq. ft. 1.0
24" x 15' 30 sq. ft. 1.5
24" x 20' 40 sq. ft. 2.0
24" x 25' 50 sq. ft. 2.5
24" x 30' 60 sq. ft. 3.0
24" x 35' 70 sq. ft. 3.5
24" x 40' 80 sq. ft. 4.0
24" x 45' 90 sq. ft. 4.5
24" x 50' 100 sq. ft. 5.0
24" x 60' 120 sq. ft. 6.0
24" x 70' 140 sq. ft. 7.0
24" x 80' 160 sq. ft. 8.0
224400VVAACC,,3366""--wwiiddeemmaatt
36" x 10' 30 sq. ft. 1.5
36" x 13'4" 40 sq. ft. 2.0
36" x 16'8" 50 sq. ft. 2.5
36" x 20' 60 sq. ft. 3.0
36" x 30' 90 sq. ft. 4.5
36" x 40' 120 sq. ft. 6.0
PPhhaassee11..EElleeccttrriiccaallRRoouugghh--iinn..RReeffeerrttooaallllddrraawwiinnggssoonnppaaggeess1111,,1166,,aanndd1177bbeeffoorreebbeeggiinnnniinnggeelleeccttrriiccaallwwoorrkk..
SunTouch Space Warming Manual 5
Power lead
conduit Power
lead
conduit
Floor sensor
conduit
Power lead
NailTite
Wire Clip
Sensor wire
Power lead
Sensor
wire